Concreto Armado, Cortante basal de estación de bomberos de 5 niveles
Citation preview
CARGAS DE SERVICIO EN CADA PISO DE LA EDIFICACION
CARGA SISMICA- 1ER PISODESCRIPCION BASE(X) ALTURA(Y) LARGO(Z) PESO UNITARIO CANTIDAD TOTAL
LOSA 5.00 8.00 1 420 5 10500MUROS 5.00 8.00 1 100 5 2500
ACABADOS 5.00 8.00 1 100 5 2500S/C 5.00 8.00 1 350 0.50 875
VIGA X-X 0.25 0.50 24.00 2400 4.5 32400VIGA Y-Y 0.35 0.65 28.00 2400 4.5 68796
COLUMNA CENTRAL 0.6 0.75 3 2400 8 25920COLUMNA LATERAL 0.55 0.60 3 2400 8 19008
COLUMNA ESQUINERA 0.5 0.6 3 2400 3 6480168979
CARGA SISMICA- 2DO PISODESCRIPCION BASE(X) ALTURA(Y) LARGO(Z) PESO UNITARIO CANTIDAD TOTALLOSA 5.00 8.00 1 420 4 8400MUROS 5.00 8.00 1 100 4 2000ACABADOS 5.00 8.00 1 100 4 2000S/C 5.00 8.00 1 350 0.5 875VIGA X-X 0.25 0.5 24.00 2400 4.5 32400VIGA Y-Y 0.35 0.65 28.00 2400 4.5 68796COLUMNA CENTRAL 0.60 0.75 3 2400 8 25920COLUMNA LATERAL 0.55 0.6 3 2400 8 19008COLUMNA ESQUINERA 0.50 0.6 3 2400 3 6480 165879
CARGA SISMICA- 3ER PISO
DESCRIPCION BASE(X) ALTURA(Y) LARGO(Z) PESO UNITARIO CANTIDAD TOTALLOSA 5.00 8.00 1 420 3 6300MUROS 5.00 8.00 1 100 3 1500ACABADOS 5.00 8.00 1 100 3 1500S/C 5.00 8.00 1 350 0.5 875VIGA X-X 0.25 0.5 24.00 2400 4.5 32400VIGA Y-Y 0.35 0.65 28.00 2400 4.5 68796COLUMNA CENTRAL 0.60 0.75 3 2400 8 25920COLUMNA LATERAL 0.55 0.6 3 2400 8 19008COLUMNA ESQUINERA 0.50 0.6 3 2400 3 6480 162779
CARGA SISMICA- 4TO PISODESCRIPCION BASE(X) ALTURA(Y) LARGO(Z) PESO UNITARIO CANTIDAD TOTALLOSA 5.00 8.00 1 420 2 4200MUROS 5.00 8.00 1 100 2 1000ACABADOS 5.00 8.00 1 100 2 1000S/C 5.00 8.00 1 350 0.5 875VIGA X-X 0.25 0.5 24.00 2400 4.5 32400VIGA Y-Y 0.35 0.65 28.00 2400 4.5 68796COLUMNA CENTRAL 0.60 0.75 3 2400 8 25920COLUMNA LATERAL 0.55 0.6 3 2400 8 19008COLUMNA ESQUINERA 0.50 0.6 3 2400 3 6480 159679
CARGA SISMICA- 5TO PISODESCRIPCION BASE(X) ALTURA(Y) LARGO(Z) PESO UNITARIO CANTIDAD TOTALLOSA 5.00 8.00 1 420 1 2100MUROS 5.00 8.00 1 100 1 500ACABADOS 5.00 8.00 1 100 1 500S/C 5.00 8.00 1 350 0.5 875VIGA X-X 0.25 0.5 24.00 2400 4.5 32400VIGA Y-Y 0.35 0.65 28.00 2400 4.5 68796COLUMNA CENTRAL 0.60 0.75 3 2400 8 25920COLUMNA LATERAL 0.55 0.6 3 2400 8 19008COLUMNA ESQUINERA 0.50 0.6 3 2400 3 6480 156579
PESO TOTAL: 813 895 Kg
CALCULO DE LA CORTANTE BASAL
ANALISIS ESTÁTICO:
Fórmula
FACTOR DE ZONA
CATEGORIA DE EDIFICIOS
ZONA Z CATEGORIA DESCRIPCION FACTOR U
3 0.4 A EDIFICACIONES ESENCIALES 1.5
2 0.3 B EDIFICACIONES IMPORTANTES 1.3
1 0.15 C EDIFICCIONES COMUNES 1.0
PARAMETROS DEL SUELO
TIPO DESCRIPCION Tp (s) S
S1 Suelo rígido 0.4 1.0
S2 Suelo intermedio 0.6 1.2
S3 Suelo flexible 0.9 1.4
V= Z .U .C . SR
. P
Factor de Amplificación Sísmica ( C ):
Fórmula
Periodo Fundamental:
CT 35CT 45CT 60
Fuerza cortante en la base:
Fórmula
Datos:
Z= 0.15 R= 8U= 1.5 hn= 15
C =2.5(TpT
) ; C ≤ 2.5T=
hnCT
V=¿ ZUCSR
. P ; CR
SISTEMAS ESTRUCTURA
L
SITEMA ESTRUCTURAL COEFICIENTE DE REDUCCION
( R )
CONCRETO Pórticos de concreto armado
8
C= 2.5 Ct= 35S= 1.4 P= 813895.0
0 Tp= 0.9
Tenemos que:
V = 80117.79 Kg
Revisando que cumpla el factor amplificación sísmica:
T = 0.43
C = 5.25 < 2.5 ----- NO CUMPLE
C = 2.5
Verificando que CR≥0.125 :
0.312 ≥ 0.125 ----- SI CUMPLE
NIVEL Pi(kg) Hi(m) PiHi(kg) PiHi/∑PiHi (PiHi/∑PiHi)x V(tn)
5 68796.00 15.00 1031940.00 0.50 39.8594 25920.00 12.00 311040.00 0.15 12.0143 19008.00 9.00 171072.00 0.08 6.6082 6480.00 3.00 19440.00 0.01 0.7511 168979.00 3.20 540732.80 0.26 20.886
TOTAL PiHi 2074224.80 V= 40.259