HOJA DE CALCULO

PLANTA DE TRATAMIENTO DE AGUA POTABLE PARA LA LOCALIDAD DE ORELLANA

FLOCULADORES DE FLUJO HORIZONTAL

Tramo Nº 01 Tramo Nº 02 Tramo Nº 03V1 = 0.21 m/s V2 = 0.18 m/s V3 = 0.10 m/sT1 = 7.00 min T2 = 7.00 min T3 = 7.00 min

Longitudes TotalesL1 = 0.21 x 7.00 x 60 = 88.20 mL2 = 0.18 x 7.00 x 60 = 75.60 mL3 = 0.10 x 7.00 x 60 = 42.00 m

Para un Caudal de = 21 lps

Seccion del CanalA1 = 0.021 m3/seg ⁄ 0.21 m/s = 0.10 m2A2 = 0.021 m3/seg ⁄ 0.18 m/s = 0.12 m2A3 = 0.021 m3/seg ⁄ 0.10 m/s = 0.21 m2

Usando Tabiques de = 1.20 x 2.40 H = 0.80 m

A1 = 0.10 ⁄ 0.80 = 0.13 mA2 = 0.12 ⁄ 0.80 = 0.15 mA3 = 0.21 ⁄ 0.80 = 0.26 m

Espaciamiento entre la punta del tabique y la pared seran

Z1 = 1.50 x 0.13 = 0.19 mZ2 = 1.50 x 0.15 = 0.22 mZ3 = 1.50 x 0.26 = 0.39 m

Cantidades de Paneles por compartimiento

Lt1 = 2.40 + 1.50 x 0.13 = 2.59 mLt2 = 2.40 + 1.50 x 0.15 = 2.62 mLt3 = 2.40 + 1.50 x 0.26 = 2.79 m

CantidadesTramo Nº 01 = 88.20 ⁄ 2.59 = 34 Paneles > 34Tramo Nº 02 = 75.60 ⁄ 2.62 = 29 Paneles > 29Tramo Nº 03 = 42.00 ⁄ 2.79 = 15 Paneles > 15

Tramo m/seg V2/2g h1=3N V2/2g S=(Vn/r(2/3))2 h2 =SL hf = h1 + h2 R = Radio Hidr.

1 0.21 0.225 23.01 3.32E-04 2.930 25.94 0.06

2 0.18 0.165 14.32 2.02E-04 1.526 15.84 0.07

3 0.10 0.051 2.30 3.10E-05 0.130 2.43 0.11

P1 = 25.94 x 1000 ⁄ 7.00 x 60 = 61.76 gr-cm/seg - ltP2 = 15.84 x 1000 ⁄ 7.00 x 60 = 37.72 gr-cm/seg - lt

Calculo de Potencia Pot = γ hf/to

HOJA DE CALCULO

PLANTA DE TRATAMIENTO DE AGUA POTABLE PARA LA LOCALIDAD DE ORELLANA

FLOCULADORES DE FLUJO HORIZONTALP3 = 2.43 x 1000 ⁄ 7.00 x 60 = 5.79 gr-cm/seg - lt

Formula para Calcular la gradiente

Del cuadro Anexo: valores de potencia Vs. Gradiente

G1 = 80

G2 = 60

G3 = 20

G = (g x P / u)^0.50

seg -1

seg -2

seg -3