SERVICE BULLETIN
Page 1 WAUKESHA ENGINEDRESSER, INC.WAUKESHA, WI 53188-4999
The tables in this Service Bulletin list Alarm andShutdown setpoints by engine series for variousengine operation parameters. These values can be
used as a guide when designing engine protection ormonitoring systems.
The alarm values shown are suggested values; theycan be changed to suit a specific application or mea-
surement device. By using controls that simulta-neously shut off the fuel supply and ignition system
upon reaching a shutdown value, the potential forengine damage is reduced.
Alarm and shutdown
values indicate devia-
tion from designed operation and are not meant
for continuous engine service. Engine and control
systems must be designed to and operated at nor-
mal values. Disregarding this information could
result in product damage and/or personal injury.
Alarm and shutdown values are based on using natural gas of 900 BTU/cu.ft. (35.38 MJ[25,V(0;101.325)]) Saturated Lower Heating Va
(SLHV) as fuel. Refer to the Gaseous Fuel Speciftion for Waukesha Enginesstandard sheet, S-788
or latest version, and the Lubricating Oil Recommdations for Waukesha Engines standard sh
S-1015-29 or latest version, for typical changesoperating temperatures for jacket water and lubewhen running on landfill or digester gas fuels.
Refer to the most recent version of the Gas Eng
Price Bookto determine which shutdown devices included as standard equipment with any speengine model.
TOPIC: Accessories
IDENT NO: 1-2620F
SUPERSEDES: 1-2620E
DATE: November 15, 2007
SUBJECT: Engine Protection Shutdown
MODELS AFFECTED: All Waukesha Engines
CAUTION
7/30/2019 01-2620f - Limites de Paradas
2/8
Service Bulletin No. 1-2620F
Page 2 of 8WAUKESHA ENGINEDRESSER, INC.WAUKESHA, WI 53188-4999
12V/18V220GL
NOTES:
1Alarm and shutdown functionality provided by ESM.2Alarm functionality provided by Auxiliary Systems Interface.
AT25GL/AT27GL
NOTES:
1Waukesha Power Systems Engomatic Control Model 1105,
1105A, or equivalent pressure/temperature shutdown system is
recommended when jacket water temperature exceeds 210 F
(99C).
2Do not revise any values on this page without revising the same
values on the AT General Operating Limits and Diagram Tempera-
ture/Pressure Test Points and Pump Settings S-sheets for the 8L,
12V, and/or 16VATGL engines.
3Waukesha Power Systems Control is required to have an 8 second
delay after engine start.
JACKET WATER (HT) OUTLET TEMPERATURE
Normal 100 C (212 F)
Alarm 103 C (217 F)1
Shutdown 108 C (226 F)1
LUBE OIL HEADER TEMPERATURE
Normal 75 C (167 F)
Alarm 77 C (171 F)
Shutdown 80 C (176 F)
LUBE OIL HEADER PRESSURE
IdleRated Speed
(1200 or 1500 rpm)
Normal 4.2 bar (61 psi) 5.3 bar (77 psi)
Alarm 2.3 bar (33 psi)1 4.0 bar (58 psi)1
Shutdown 2.0 bar (29 psi)1 3.5 bar (51 psi)1
INTAKE MANIFOLD TEMPERATURE
Normal Up to 10 C (9 F) above design intercooler
water inlet temperature.
Alarm10 C (18 F) above design intercooler
water inlet temperature1.
Shutdown20 C (36 F) above design intercooler
water inlet temperature1.
INTAKE MANIFOLD PRESSURE
Contact Waukesha Sales Engineering
GAS PRESSURE AT GAS TRAIN INLET
Normal 4 6 bar (58 87 psi)
Alarm 6.5 bar (94 psi)2
OVERSPEED
Shutdown Not to exceed 7% over governed speed.
FUEL PRESSURE
AlarmThe minimum fuel pressure at the regulator
(from Tech Data Book)
Shutdown 85% of the alarm value
JACKET WATER OUTLET TEMPERATURE
Standard Cooling System
Normal180 F (82 C) for continuous rating200 F (93 C) for intermittent rating
Alarm 10 F (5.5 C) abovenormal/design temperature
Shutdown
20 F (11 C) above
normal/design temperature
Elevated Temperature Solid Water Cooling System
Normal 210 250 F (99 121 C) solid water
Alarm 5 F (3 C) above normal/design temperature1
Shutdown 10 F (5.5 C) above normal/design temperature1
LUBE OIL HEADER TEMPERATURE
Normal 172 F (78 C)
Alarm 187 F (86 C)
Shutdown 197 F (92 C)
LUBE OIL HEADER PRESSURE
Normal 60 65 psi (415 450 kPa)
Alarm 50 psi (345 kPa)3
Shutdown 45 psi (310 kPa)3
INTAKE MANIFOLD TEMPERATURE AT25GL MODEL
NormalUp to 10 F (5.5 C) above designintercooler water inlet temperature
Alarm20 F (11 C) above design intercooler water inlet
temperature
Shutdown30 F (17 C) above design intercooler water inlet
temperature
INTAKE MANIFOLD TEMPERATURE AT27GL MODEL
Normal Up to 10 F (5.5 C) above design intercooler
water inlet temperature
Alarm 15 F (11 C) above design intercooler water inlet
temperature
Shutdown 20 F (17 C) above design intercooler water inlet
temperature
INTAKE MANIFOLD PRESSURE
Contact Waukesha Sales Engineering
MAIN BEARING TEMPERATURE
Shutdown 250 F (121 C)
OVERSPEED
Shutdown Not to exceed 10% over governed speed.
FUEL PRESSURE
AlarmThe minimum fuel pressure at theregulator (from Tech Data Book)
Shutdown 85% of the alarm value
7/30/2019 01-2620f - Limites de Paradas
3/8
Service Bulletin No. 1-262
Page 3 WAUKESHA ENGINEDRESSER, INC.WAUKESHA, WI 53188-4999
VHP VHP (continued)
NOTES:
1For engines equipped with ESM, refer to ECU calibration
appropriate S-08312-XX sheet to determine limits of oper
conditions.2Alarm and shutdown functionality provided on engines equip
with ESM.3Waukesha Power Systems Engomatic Control Model 1
1105A, or equivalent shutdown system is recommended w
jacket water temperature exceeds 210 F (99 C).4Waukesha Power Systems Engomatic Control Model 1
1106A, or equivalent shutdown system is recommended
ebulliently cooled engines.5Waukesha Power Systems Control is required to have an 8 se
delay after engine start.
JACKET WATER OUTLET TEMPERATURE1
Standard Cooling System
Normal180 F (82 C) for continuous rating200 F (93 C) for intermittent rating
Alarm10 F (5.5 C) above
normal/design temperature2
Shutdown 20
F (11
C) abovenormal/design temperature2
Waukesha Power Systems Std.
Alarm 205 F (96 C)
Shutdown 215 F (102 C)
Note: Alarm and shutdown differ because of the10% overload for 2 hours in 24.
Elevated Temperature Solid Water Cooling System(All Applications)
Normal 210 235 F (99 113 C)for solid water
Alarm5 F (3 C) above
normal/design temperature2,3
Shutdown10 F (5.5 C) above
normal/design temperature2,3
Ebullient Water Cooling System (All Applications)
Normal 212 250 F (100 121 C)
Alarm See Note 4
Shutdown See Note 4
LUBE OIL HEADER TEMPERATURE
Normal 180 F (82 C)
Alarm 195 F (91 C)2
Shutdown 205 F (96 C)2
Naturally Aspirated Standby Rating withauxiliary cooling connected to jacket cooling.
Alarm 200 F (93 C)
Shutdown 205 F (96 C)
WED Code 1107
Alarm 200 F (93 C)
Shutdown 205 F (96 C)
LUBE OIL HEADER PRESSURE
6 and 12 Cylinder Models
Normal 50 60 psi (345 415 kPa)
Alarm 35 psi (241 kPa)2, 5
Shutdown 30 psi (207 kPa)2, 5
16 Cylinder Models
Normal 30 50 psi (207 345 kPa)
Alarm 30 psi (207 kPa)5
Shutdown 25 psi (172 kPa)5
LUBE OIL FILTER DIFFERENTIAL PRESSURE
Normal 2 15 psi (14 103 kPa differential)
Alarm 15 psi (103 kPa differential)2
INTAKE MANIFOLD TEMPERATURE2
Normal Up to 10 F (5.5 C) above design
intercooler water inlet temperature
Alarm15 F (8.5 C) above design intercool
water inlet temperature2
Shutdown20 F (11 C) above design intercool
water inlet temperature2
INTAKE MANIFOLD PRESSURE
Contact Waukesha Sales Engineering
MAIN BEARING TEMPERATURE
Shutdown 250 F (121 C)
WED Code 6010, Eutectic alloy melting point is 252 F
Oil pressure switch pressure setting is 20 Psig5
OVERSPEED
Shutdown 10% over governed speed2
Waukesha Power System
Shutdown 1015% over governed speed,not to exceed 1320 RPM
Caution
When setting engine overspeed
shutdown, do not exceed the lesser oengine or driven equipments speed liits. To avoid equipment damage, cons
the driven equipment manufacturerfor maximum overspeed value.
FUEL PRESSURE
AlarmThe minimum fuel pressure at theregulator (from Tech Data Book)
Shutdown 85% of the alarm value
7/30/2019 01-2620f - Limites de Paradas
4/8
Service Bulletin No. 1-2620F
Page 4 of 8WAUKESHA ENGINEDRESSER, INC.WAUKESHA, WI 53188-4999
16V150LTD
NOTES:
1Alarm and shutdown functionality provided by ESM.
F1197
F817
JACKET WATER (HT) OUTLET TEMPERATURE
Normal 99 C (210 F)
Alarm 105 C (220 F)1
Shutdown 110 C (230 F)1
LUBE OIL HEADER TEMPERATURE
Normal 88 C (190 F)
Alarm 93 C (199 F)
Shutdown 96 C (204 F)
LUBE OIL HEADER PRESSURE
IdleRated Speed
(1500 or 1800 rpm)
Normal 2.4 bar (35 psi) 3.6 bar (52 psi)
Alarm 2.0 bar (29 psi)1 2.8 bar (40 psi)1
Shutdown 1.6 bar (24 psi)1 2.4 bar (35 psi)1
INTAKE MANIFOLD TEMPERATURE
Normal Up to 10 C (9 F) above design
intercooler water inlet temperature.
Alarm11 C (20 F) above design intercooler water
inlet temperature1.
Shutdown14 C (25 C) above design intercooler water
inlet temperature1.
INTAKE MANIFOLD PRESSURE
Contact Waukesha Sales Engineering.
GAS PRESSURE AT GAS TRAIN INLET
Normal 0.05 0.09 bar (0.75 1.25 psi)
OVERSPEED
Shutdown50 Hz: 1750 rpm
60 Hz: 1980 rpm
FUEL PRESSURE
AlarmThe minimum fuel pressure at theregulator (from Tech Data Book)
Shutdown 85% of the alarm value
JACKET WATER OUTLET TEMPERATURE
Normal 180 F (82 C)
Alarm 200 F (93 C)
Shutdown 210 F (99 C)
LUBE OIL HEADER TEMPERATURE
Normal 160 210 F (71 99 C)
Alarm 225 F (107 C)
Shutdown 235 F (113 C)
LUBE OIL HEADER PRESSURE
Normal 40 50 psi (276 345 kPa)
Alarm 15 psi (103 kPa)
Shutdown 10 psi (69 kPa)
INTAKE MANIFOLD TEMPERATURE
Not Applicable
INTAKE MANIFOLD PRESSURE
Contact Waukesha Sales Engineering
MAIN BEARING TEMPERATURE
Contact Waukesha Sales Engineering
OVERSPEED
Shutdown Not to exceed 15% over governed speed
JACKET WATER OUTLET TEMPERATURE
Normal 180 F (82 C)
Alarm 195 F (91 C)
Shutdown 205 F (96 C)
LUBE OIL HEADER TEMPERATURE
Normal 160 230 F (71 110 C)
Alarm 240 F (116 C)
Shutdown 250
F (121
C)LUBE OIL HEADER PRESSURE
Normal 35 45 psi (241 310 kPa)
Alarm 15 psi (103 kPa)
Shutdown 10 psi (69 kPa)
INTAKE MANIFOLD TEMPERATURE
Not Applicable
INTAKE MANIFOLD PRESSURE
Contact Waukesha Sales Engineering
OVERSPEED
Shutdown Not to exceed 15% over governed speed
7/30/2019 01-2620f - Limites de Paradas
5/8
Service Bulletin No. 1-262
Page 5 WAUKESHA ENGINEDRESSER, INC.WAUKESHA, WI 53188-4999
VGF VGF (continued)
NOTES:
1Waukesha Power Systems Engomatic Control Model 1
1105A, or equivalent pressure/temperature shutdown syste
recommended when jacket water temperature exceeds 210
(99 C).2Waukesha Power Systems Control is required to have an 8 se
delay after engine start.3Waukesha Power Systems Control is required to have a 5 m
delay after engine start for all applications that run with (less tha
equal to) 125 F intercooler water.
JACKET WATER OUTLET TEMPERATURE
Standard Cooling SystemEngines less than or equal to 176 BMEP
Normal180 F (82 C) for continuous rating200 F (93 C) for intermittent rating
Alarm 10 F (5.5 C) above
normal/design temperature
Shutdown 20 F (11 C) abovenormal/design temperature
Waukesha Power Systems Std
Alarm 205 F (96 C)
Normal 215 F (102 C)
ShutdownAlarm and Shutdown differ because of
the 10% overload for 2 hours in 24
Elevated Temperature, Solid Water Cooling SystemEngines less than or equal to 176 BMEP
All Applications
Normal 210 265 F (99 130 C)for solid water
Alarm5 F (3 C) above
normal/design temperature1
Shutdown10 F (5.5 C) above
normal/design temperature1
Elevated Temperature, Solid Water Cooling System200 BMEP Engines All Applications
Normal 210 F (99 C) solid water
Alarm10 F (5.5 C) above
normal/design temperature1
Shutdown15 F (8.5 C) above
normal/design temperature1
LUBE OIL HEADER TEMPERATURE
Jacket Water Temperature of 180 F (82 C) andIntercooler Temperature of 85 130 F (29 54 C)Engines less than or equal to 176 BMEP All Models
Normal 170 195 F (76.5 90.5 C)
Alarm 200 F (93 C)
Shutdown 205 F (96 C)
Jacket Water Temperature of 265 F (129 C) and IntercoolerTemperature of 85 130 F (29 54 C)
Engines less than or equal to 176 BMEP All Models
Normal 170 195 F (76.5 90.5 C)
Alarm 200 F (93 C)
Shutdown 205 F (96 C)
Jacket Water Temperature of 210 F (99 C) andIntercooler Temperature of 158 176 F (70 80 C)
200 BMEP GLD Engines Only
Normal 190 F (88 C)
Alarm 200 F (93 C)
Shutdown 205 F (96 C)
LUBE OIL HEADER PRESSURE
F18/H24 Models
Normal 67 83 psi (462 572 kPa)
Alarm 40 psi (276 kPa)2
Shutdown 35 psi (241 kPa)2
L36/P48 Models
Normal 66 82psi (455 565 kPa)
Alarm 40 psi (276 kPa)2
Shutdown 35 psi (241 kPa)2
INTAKE MANIFOLD TEMPERATURE
With Standard Intercooler Water Temperaturesof 85 130 F (29 54 C)GL/GLD/GSI/GSID Engines
with less than or equal to 176 BMEP
NormalUp to 10 F (5.5 C) above designintercooler water inlet temperature
Alarm 15 F (8.5 C) above design intercoole
water inlet temperature
Shutdown20 F (11 C) above design intercoole
water inlet temperatureWith Elevated Intercooler Water Temperatures
of 131 176 F (55 80 C)
NormalUp to 10 F (5.5 C) above designintercooler water inlet temperature
Alarm 10 F (5.5 C) above design intercoolewater inlet temperature
Shutdown15 F (8.5 C) above design intercoole
water inlet temperature
With Elevated Intercooler Water Temperaturesof 158 176 F (70 80 C)200 BMEP GLD Engines Only
Normal Up to 10 F (5.5 C) above design
intercooler water inlet temperature
Alarm 10 F (5.5 C) above design intercoolewater inlet temperature
Shutdown15 F (8.5 C) above design intercoole
water inlet temperature
INTAKE MANIFOLD PRESSURE
Contact Waukesha Sales Engineering
MAIN BEARING TEMPERATURE
Contact Waukesha Sales Engineering
OVERSPEED
Shutdown Not to exceed 15% over governed spee
FUEL PRESSURE
AlarmThe minimum fuel pressure at theregulator (from Tech Data Book)
Shutdown 85% of the alarm value
7/30/2019 01-2620f - Limites de Paradas
6/8
Service Bulletin No. 1-2620F
Page 6 of 8WAUKESHA ENGINEDRESSER, INC.WAUKESHA, WI 53188-4999
VSGJACKET WATER OUTLET TEMPERATURE
Normal 180 F (82 C)
Alarm 200 F (93 C)
Shutdown 210 F (99 C)
LUBE OIL HEADER TEMPERATURE
with a Jacket Water Temperature of 180 F (82 C)
F11G Model
Normal 205 F (96 C)
Alarm 215 F (102 C)
Shutdown 225 F (107 C)
F11GSI Model
Normal 190 F (89 C)
Alarm 200 F (93 C)
Shutdown 210 F (99 C)
LUBE OIL HEADER PRESSURE
Normal 65 87 psi (448 600 kPa)
Alarm 40 psi (276 kPa)
Shutdown 30 psi (207 kPa)
INTAKE MANIFOLD TEMPERATURE (GSI)
Normal Up to 15 F (8.5 C) above design
intercooler water inlet temperature
Alarm 20 F (11 C) above design intercoolerwater inlet temperature
Shutdown25 F (14 C) above design intercooler
water inlet temperature
INTAKE MANIFOLD PRESSURE
Contact Waukesha Sales Engineering
MAIN BEARING TEMPERATURE
Contact Waukesha Sales Engineering
OVERSPEED
ShutdownNot to exceed 15% over
governed speed.
FUEL PRESSURE
AlarmThe minimum fuel pressure at theregulator (from Tech Data Book)
Shutdown 85% of the alarm value
7/30/2019 01-2620f - Limites de Paradas
7/8
Service Bulletin No. 1-262
Page 7 WAUKESHA ENGINEDRESSER, INC.WAUKESHA, WI 53188-4999
GENERATOR ALARMS AND SHUTDOWNSKATO CLASS F INSULATION GENERATORS See Katodrawing for setpoint recommendations on standby units
Generator Winding (Prime Power)
Alarm 311 F (155 C)
Shutdown 329 F (165 C)
Generator Bearing
Alarm 185 F (85 C)Shutdown 203 F (95 C)
MARATHON ELECTRIC MAGNAMAX DVR GENERATORS
Prime Power (105 C) Generator Winding
Alarm 293 F (145 C)
Shutdown 311 F (155 C)
Prime Power (105 C) Generator Bearing
Alarm 230 F (110 C)
Shutdown 248 F (120 C)
Standby Power (130 C) Generator Winding
Alarm 338 F (170 C)
Shutdown 356 F (180 C)
Standby Power (130 C) Generator Bearing
Alarm 230 F (110 C)
Shutdown 248 F (120 C)
Prime or Standby Generator WindingTemperature Switch (GWTS)
Shutdown 302 9 F (150 5 C) Switch N.O. or N.C.
Comments
GWTS is not located in the winding a lot likethe RTD or thermocouple so a lower tempera-
ture device is used. No alarm GWTS isavailable at this time.
LEROY SOMER CLASS F INSULATION GENERATORS
Prime Power (105 C) Generator Winding
Alarm 302 F (150 C)
Shutdown 311 F (155 C)
Prime Power (105 C) Generator (Sleeve or Roller) Bearing
Alarm 194 F (90 C)
Shutdown 203 F (95 C)
Standby Power (130 C) Generator Winding
Alarm 347 F (175 C)
Shutdown 356 F (180 C)
Standby Power (130 C) Generator (Sleeve or Roller) Bearing
Alarm 239 F (115 C)
Shutdown 248 F (120 C)
LEROY SOMER CLASS H INSULATION GENERATORS
Prime Power (105 C) Generator Winding
Alarm 194 F (90 C)
Shutdown 203 F (95 C)
Prime Power (105 C) Generator (Sleeve or Roller) Bearin
Alarm 194 F (90 C)
Shutdown 203 F (95 C)
Standby Power (130 C) Generator Winding
Alarm 392 F (200 C)
Shutdown 401 F (205 C)
Standby Power (130 C) Generator (Sleeve or Roller) Bear
Alarm 392 F (200 C)
Shutdown 401 F (205 C)
Comments:
Class H is Leroy Somer standard. Only claH settings should be used for the LSA461LSA51 low voltage generators. These valu
are ISO standard and should be used as mmums only.
LEROY SOMER NA (MAGNETEK)
CLASS F INSULATION GENERATORSGenerator Winding (Prime Power)
Alarm 311 F (155 C)
Shutdown 329 F (165 C)
Generator Bearing
Alarm 185 F (85 C)
Shutdown 194 F (90 C)
7/30/2019 01-2620f - Limites de Paradas
8/8
Service Bulletin No. 1-2620F
Page 8 of 8WAUKESHA ENGINEDRESSER, INC.WAUKESHA, WI 53188-4999
NEWAGE GENERATORS
GENERATOR WINDING
COMMENTS: These values are recommended by the British Standard BS4999 Part 72, which Newage Int. follow.
INSULATION CLASS WARNING SHUTDOWN
F C F C
A 194 90 230 110
E 230 110 266 130
B 248 120 284 140
F 284 140 320 160
H 338 170 374 190