    SERVICE BULLETIN

    Page 1 WAUKESHA ENGINEDRESSER, INC.WAUKESHA, WI 53188-4999

    The tables in this Service Bulletin list Alarm andShutdown setpoints by engine series for variousengine operation parameters. These values can be

    used as a guide when designing engine protection ormonitoring systems.

    The alarm values shown are suggested values; theycan be changed to suit a specific application or mea-

    surement device. By using controls that simulta-neously shut off the fuel supply and ignition system

    upon reaching a shutdown value, the potential forengine damage is reduced.

    Alarm and shutdown

    values indicate devia-

    tion from designed operation and are not meant

    for continuous engine service. Engine and control

    systems must be designed to and operated at nor-

    mal values. Disregarding this information could

    result in product damage and/or personal injury.

    Alarm and shutdown values are based on using natural gas of 900 BTU/cu.ft. (35.38 MJ[25,V(0;101.325)]) Saturated Lower Heating Va

    (SLHV) as fuel. Refer to the Gaseous Fuel Speciftion for Waukesha Enginesstandard sheet, S-788

    or latest version, and the Lubricating Oil Recommdations for Waukesha Engines standard sh

    S-1015-29 or latest version, for typical changesoperating temperatures for jacket water and lubewhen running on landfill or digester gas fuels.

    Refer to the most recent version of the Gas Eng

    Price Bookto determine which shutdown devices included as standard equipment with any speengine model.

    TOPIC: Accessories

    IDENT NO: 1-2620F

    SUPERSEDES: 1-2620E

    DATE: November 15, 2007

    SUBJECT: Engine Protection Shutdown

    MODELS AFFECTED: All Waukesha Engines

    CAUTION

  • 7/30/2019 01-2620f - Limites de Paradas

    2/8

    Service Bulletin No. 1-2620F

    Page 2 of 8WAUKESHA ENGINEDRESSER, INC.WAUKESHA, WI 53188-4999

    12V/18V220GL

    NOTES:

    1Alarm and shutdown functionality provided by ESM.2Alarm functionality provided by Auxiliary Systems Interface.

    AT25GL/AT27GL

    NOTES:

    1Waukesha Power Systems Engomatic Control Model 1105,

    1105A, or equivalent pressure/temperature shutdown system is

    recommended when jacket water temperature exceeds 210 F

    (99C).

    2Do not revise any values on this page without revising the same

    values on the AT General Operating Limits and Diagram Tempera-

    ture/Pressure Test Points and Pump Settings S-sheets for the 8L,

    12V, and/or 16VATGL engines.

    3Waukesha Power Systems Control is required to have an 8 second

    delay after engine start.

    JACKET WATER (HT) OUTLET TEMPERATURE

    Normal 100 C (212 F)

    Alarm 103 C (217 F)1

    Shutdown 108 C (226 F)1

    LUBE OIL HEADER TEMPERATURE

    Normal 75 C (167 F)

    Alarm 77 C (171 F)

    Shutdown 80 C (176 F)

    LUBE OIL HEADER PRESSURE

    IdleRated Speed

    (1200 or 1500 rpm)

    Normal 4.2 bar (61 psi) 5.3 bar (77 psi)

    Alarm 2.3 bar (33 psi)1 4.0 bar (58 psi)1

    Shutdown 2.0 bar (29 psi)1 3.5 bar (51 psi)1

    INTAKE MANIFOLD TEMPERATURE

    Normal Up to 10 C (9 F) above design intercooler

    water inlet temperature.

    Alarm10 C (18 F) above design intercooler

    water inlet temperature1.

    Shutdown20 C (36 F) above design intercooler

    water inlet temperature1.

    INTAKE MANIFOLD PRESSURE

    Contact Waukesha Sales Engineering

    GAS PRESSURE AT GAS TRAIN INLET

    Normal 4 6 bar (58 87 psi)

    Alarm 6.5 bar (94 psi)2

    OVERSPEED

    Shutdown Not to exceed 7% over governed speed.

    FUEL PRESSURE

    AlarmThe minimum fuel pressure at the regulator

    (from Tech Data Book)

    Shutdown 85% of the alarm value

    JACKET WATER OUTLET TEMPERATURE

    Standard Cooling System

    Normal180 F (82 C) for continuous rating200 F (93 C) for intermittent rating

    Alarm 10 F (5.5 C) abovenormal/design temperature

    Shutdown

    20 F (11 C) above

    normal/design temperature

    Elevated Temperature Solid Water Cooling System

    Normal 210 250 F (99 121 C) solid water

    Alarm 5 F (3 C) above normal/design temperature1

    Shutdown 10 F (5.5 C) above normal/design temperature1

    LUBE OIL HEADER TEMPERATURE

    Normal 172 F (78 C)

    Alarm 187 F (86 C)

    Shutdown 197 F (92 C)

    LUBE OIL HEADER PRESSURE

    Normal 60 65 psi (415 450 kPa)

    Alarm 50 psi (345 kPa)3

    Shutdown 45 psi (310 kPa)3

    INTAKE MANIFOLD TEMPERATURE AT25GL MODEL

    NormalUp to 10 F (5.5 C) above designintercooler water inlet temperature

    Alarm20 F (11 C) above design intercooler water inlet

    temperature

    Shutdown30 F (17 C) above design intercooler water inlet

    temperature

    INTAKE MANIFOLD TEMPERATURE AT27GL MODEL

    Normal Up to 10 F (5.5 C) above design intercooler

    water inlet temperature

    Alarm 15 F (11 C) above design intercooler water inlet

    temperature

    Shutdown 20 F (17 C) above design intercooler water inlet

    temperature

    INTAKE MANIFOLD PRESSURE

    Contact Waukesha Sales Engineering

    MAIN BEARING TEMPERATURE

    Shutdown 250 F (121 C)

    OVERSPEED

    Shutdown Not to exceed 10% over governed speed.

    FUEL PRESSURE

    AlarmThe minimum fuel pressure at theregulator (from Tech Data Book)

    Shutdown 85% of the alarm value

  • 7/30/2019 01-2620f - Limites de Paradas

    3/8

    Service Bulletin No. 1-262

    Page 3 WAUKESHA ENGINEDRESSER, INC.WAUKESHA, WI 53188-4999

    VHP VHP (continued)

    NOTES:

    1For engines equipped with ESM, refer to ECU calibration

    appropriate S-08312-XX sheet to determine limits of oper

    conditions.2Alarm and shutdown functionality provided on engines equip

    with ESM.3Waukesha Power Systems Engomatic Control Model 1

    1105A, or equivalent shutdown system is recommended w

    jacket water temperature exceeds 210 F (99 C).4Waukesha Power Systems Engomatic Control Model 1

    1106A, or equivalent shutdown system is recommended

    ebulliently cooled engines.5Waukesha Power Systems Control is required to have an 8 se

    delay after engine start.

    JACKET WATER OUTLET TEMPERATURE1

    Standard Cooling System

    Normal180 F (82 C) for continuous rating200 F (93 C) for intermittent rating

    Alarm10 F (5.5 C) above

    normal/design temperature2

    Shutdown 20

    F (11

    C) abovenormal/design temperature2

    Waukesha Power Systems Std.

    Alarm 205 F (96 C)

    Shutdown 215 F (102 C)

    Note: Alarm and shutdown differ because of the10% overload for 2 hours in 24.

    Elevated Temperature Solid Water Cooling System(All Applications)

    Normal 210 235 F (99 113 C)for solid water

    Alarm5 F (3 C) above

    normal/design temperature2,3

    Shutdown10 F (5.5 C) above

    normal/design temperature2,3

    Ebullient Water Cooling System (All Applications)

    Normal 212 250 F (100 121 C)

    Alarm See Note 4

    Shutdown See Note 4

    LUBE OIL HEADER TEMPERATURE

    Normal 180 F (82 C)

    Alarm 195 F (91 C)2

    Shutdown 205 F (96 C)2

    Naturally Aspirated Standby Rating withauxiliary cooling connected to jacket cooling.

    Alarm 200 F (93 C)

    Shutdown 205 F (96 C)

    WED Code 1107

    Alarm 200 F (93 C)

    Shutdown 205 F (96 C)

    LUBE OIL HEADER PRESSURE

    6 and 12 Cylinder Models

    Normal 50 60 psi (345 415 kPa)

    Alarm 35 psi (241 kPa)2, 5

    Shutdown 30 psi (207 kPa)2, 5

    16 Cylinder Models

    Normal 30 50 psi (207 345 kPa)

    Alarm 30 psi (207 kPa)5

    Shutdown 25 psi (172 kPa)5

    LUBE OIL FILTER DIFFERENTIAL PRESSURE

    Normal 2 15 psi (14 103 kPa differential)

    Alarm 15 psi (103 kPa differential)2

    INTAKE MANIFOLD TEMPERATURE2

    Normal Up to 10 F (5.5 C) above design

    intercooler water inlet temperature

    Alarm15 F (8.5 C) above design intercool

    water inlet temperature2

    Shutdown20 F (11 C) above design intercool

    water inlet temperature2

    INTAKE MANIFOLD PRESSURE

    Contact Waukesha Sales Engineering

    MAIN BEARING TEMPERATURE

    Shutdown 250 F (121 C)

    WED Code 6010, Eutectic alloy melting point is 252 F

    Oil pressure switch pressure setting is 20 Psig5

    OVERSPEED

    Shutdown 10% over governed speed2

    Waukesha Power System

    Shutdown 1015% over governed speed,not to exceed 1320 RPM

    Caution

    When setting engine overspeed

    shutdown, do not exceed the lesser oengine or driven equipments speed liits. To avoid equipment damage, cons

    the driven equipment manufacturerfor maximum overspeed value.

    FUEL PRESSURE

    AlarmThe minimum fuel pressure at theregulator (from Tech Data Book)

    Shutdown 85% of the alarm value

  • 7/30/2019 01-2620f - Limites de Paradas

    4/8

    Service Bulletin No. 1-2620F

    Page 4 of 8WAUKESHA ENGINEDRESSER, INC.WAUKESHA, WI 53188-4999

    16V150LTD

    NOTES:

    1Alarm and shutdown functionality provided by ESM.

    F1197

    F817

    JACKET WATER (HT) OUTLET TEMPERATURE

    Normal 99 C (210 F)

    Alarm 105 C (220 F)1

    Shutdown 110 C (230 F)1

    LUBE OIL HEADER TEMPERATURE

    Normal 88 C (190 F)

    Alarm 93 C (199 F)

    Shutdown 96 C (204 F)

    LUBE OIL HEADER PRESSURE

    IdleRated Speed

    (1500 or 1800 rpm)

    Normal 2.4 bar (35 psi) 3.6 bar (52 psi)

    Alarm 2.0 bar (29 psi)1 2.8 bar (40 psi)1

    Shutdown 1.6 bar (24 psi)1 2.4 bar (35 psi)1

    INTAKE MANIFOLD TEMPERATURE

    Normal Up to 10 C (9 F) above design

    intercooler water inlet temperature.

    Alarm11 C (20 F) above design intercooler water

    inlet temperature1.

    Shutdown14 C (25 C) above design intercooler water

    inlet temperature1.

    INTAKE MANIFOLD PRESSURE

    Contact Waukesha Sales Engineering.

    GAS PRESSURE AT GAS TRAIN INLET

    Normal 0.05 0.09 bar (0.75 1.25 psi)

    OVERSPEED

    Shutdown50 Hz: 1750 rpm

    60 Hz: 1980 rpm

    FUEL PRESSURE

    AlarmThe minimum fuel pressure at theregulator (from Tech Data Book)

    Shutdown 85% of the alarm value

    JACKET WATER OUTLET TEMPERATURE

    Normal 180 F (82 C)

    Alarm 200 F (93 C)

    Shutdown 210 F (99 C)

    LUBE OIL HEADER TEMPERATURE

    Normal 160 210 F (71 99 C)

    Alarm 225 F (107 C)

    Shutdown 235 F (113 C)

    LUBE OIL HEADER PRESSURE

    Normal 40 50 psi (276 345 kPa)

    Alarm 15 psi (103 kPa)

    Shutdown 10 psi (69 kPa)

    INTAKE MANIFOLD TEMPERATURE

    Not Applicable

    INTAKE MANIFOLD PRESSURE

    Contact Waukesha Sales Engineering

    MAIN BEARING TEMPERATURE

    Contact Waukesha Sales Engineering

    OVERSPEED

    Shutdown Not to exceed 15% over governed speed

    JACKET WATER OUTLET TEMPERATURE

    Normal 180 F (82 C)

    Alarm 195 F (91 C)

    Shutdown 205 F (96 C)

    LUBE OIL HEADER TEMPERATURE

    Normal 160 230 F (71 110 C)

    Alarm 240 F (116 C)

    Shutdown 250

    F (121

    C)LUBE OIL HEADER PRESSURE

    Normal 35 45 psi (241 310 kPa)

    Alarm 15 psi (103 kPa)

    Shutdown 10 psi (69 kPa)

    INTAKE MANIFOLD TEMPERATURE

    Not Applicable

    INTAKE MANIFOLD PRESSURE

    Contact Waukesha Sales Engineering

    OVERSPEED

    Shutdown Not to exceed 15% over governed speed

  • 7/30/2019 01-2620f - Limites de Paradas

    5/8

    Service Bulletin No. 1-262

    Page 5 WAUKESHA ENGINEDRESSER, INC.WAUKESHA, WI 53188-4999

    VGF VGF (continued)

    NOTES:

    1Waukesha Power Systems Engomatic Control Model 1

    1105A, or equivalent pressure/temperature shutdown syste

    recommended when jacket water temperature exceeds 210

    (99 C).2Waukesha Power Systems Control is required to have an 8 se

    delay after engine start.3Waukesha Power Systems Control is required to have a 5 m

    delay after engine start for all applications that run with (less tha

    equal to) 125 F intercooler water.

    JACKET WATER OUTLET TEMPERATURE

    Standard Cooling SystemEngines less than or equal to 176 BMEP

    Normal180 F (82 C) for continuous rating200 F (93 C) for intermittent rating

    Alarm 10 F (5.5 C) above

    normal/design temperature

    Shutdown 20 F (11 C) abovenormal/design temperature

    Waukesha Power Systems Std

    Alarm 205 F (96 C)

    Normal 215 F (102 C)

    ShutdownAlarm and Shutdown differ because of

    the 10% overload for 2 hours in 24

    Elevated Temperature, Solid Water Cooling SystemEngines less than or equal to 176 BMEP

    All Applications

    Normal 210 265 F (99 130 C)for solid water

    Alarm5 F (3 C) above

    normal/design temperature1

    Shutdown10 F (5.5 C) above

    normal/design temperature1

    Elevated Temperature, Solid Water Cooling System200 BMEP Engines All Applications

    Normal 210 F (99 C) solid water

    Alarm10 F (5.5 C) above

    normal/design temperature1

    Shutdown15 F (8.5 C) above

    normal/design temperature1

    LUBE OIL HEADER TEMPERATURE

    Jacket Water Temperature of 180 F (82 C) andIntercooler Temperature of 85 130 F (29 54 C)Engines less than or equal to 176 BMEP All Models

    Normal 170 195 F (76.5 90.5 C)

    Alarm 200 F (93 C)

    Shutdown 205 F (96 C)

    Jacket Water Temperature of 265 F (129 C) and IntercoolerTemperature of 85 130 F (29 54 C)

    Engines less than or equal to 176 BMEP All Models

    Normal 170 195 F (76.5 90.5 C)

    Alarm 200 F (93 C)

    Shutdown 205 F (96 C)

    Jacket Water Temperature of 210 F (99 C) andIntercooler Temperature of 158 176 F (70 80 C)

    200 BMEP GLD Engines Only

    Normal 190 F (88 C)

    Alarm 200 F (93 C)

    Shutdown 205 F (96 C)

    LUBE OIL HEADER PRESSURE

    F18/H24 Models

    Normal 67 83 psi (462 572 kPa)

    Alarm 40 psi (276 kPa)2

    Shutdown 35 psi (241 kPa)2

    L36/P48 Models

    Normal 66 82psi (455 565 kPa)

    Alarm 40 psi (276 kPa)2

    Shutdown 35 psi (241 kPa)2

    INTAKE MANIFOLD TEMPERATURE

    With Standard Intercooler Water Temperaturesof 85 130 F (29 54 C)GL/GLD/GSI/GSID Engines

    with less than or equal to 176 BMEP

    NormalUp to 10 F (5.5 C) above designintercooler water inlet temperature

    Alarm 15 F (8.5 C) above design intercoole

    water inlet temperature

    Shutdown20 F (11 C) above design intercoole

    water inlet temperatureWith Elevated Intercooler Water Temperatures

    of 131 176 F (55 80 C)

    NormalUp to 10 F (5.5 C) above designintercooler water inlet temperature

    Alarm 10 F (5.5 C) above design intercoolewater inlet temperature

    Shutdown15 F (8.5 C) above design intercoole

    water inlet temperature

    With Elevated Intercooler Water Temperaturesof 158 176 F (70 80 C)200 BMEP GLD Engines Only

    Normal Up to 10 F (5.5 C) above design

    intercooler water inlet temperature

    Alarm 10 F (5.5 C) above design intercoolewater inlet temperature

    Shutdown15 F (8.5 C) above design intercoole

    water inlet temperature

    INTAKE MANIFOLD PRESSURE

    Contact Waukesha Sales Engineering

    MAIN BEARING TEMPERATURE

    Contact Waukesha Sales Engineering

    OVERSPEED

    Shutdown Not to exceed 15% over governed spee

    FUEL PRESSURE

    AlarmThe minimum fuel pressure at theregulator (from Tech Data Book)

    Shutdown 85% of the alarm value

  • 7/30/2019 01-2620f - Limites de Paradas

    6/8

    Service Bulletin No. 1-2620F

    Page 6 of 8WAUKESHA ENGINEDRESSER, INC.WAUKESHA, WI 53188-4999

    VSGJACKET WATER OUTLET TEMPERATURE

    Normal 180 F (82 C)

    Alarm 200 F (93 C)

    Shutdown 210 F (99 C)

    LUBE OIL HEADER TEMPERATURE

    with a Jacket Water Temperature of 180 F (82 C)

    F11G Model

    Normal 205 F (96 C)

    Alarm 215 F (102 C)

    Shutdown 225 F (107 C)

    F11GSI Model

    Normal 190 F (89 C)

    Alarm 200 F (93 C)

    Shutdown 210 F (99 C)

    LUBE OIL HEADER PRESSURE

    Normal 65 87 psi (448 600 kPa)

    Alarm 40 psi (276 kPa)

    Shutdown 30 psi (207 kPa)

    INTAKE MANIFOLD TEMPERATURE (GSI)

    Normal Up to 15 F (8.5 C) above design

    intercooler water inlet temperature

    Alarm 20 F (11 C) above design intercoolerwater inlet temperature

    Shutdown25 F (14 C) above design intercooler

    water inlet temperature

    INTAKE MANIFOLD PRESSURE

    Contact Waukesha Sales Engineering

    MAIN BEARING TEMPERATURE

    Contact Waukesha Sales Engineering

    OVERSPEED

    ShutdownNot to exceed 15% over

    governed speed.

    FUEL PRESSURE

    AlarmThe minimum fuel pressure at theregulator (from Tech Data Book)

    Shutdown 85% of the alarm value

  • 7/30/2019 01-2620f - Limites de Paradas

    7/8

    Service Bulletin No. 1-262

    Page 7 WAUKESHA ENGINEDRESSER, INC.WAUKESHA, WI 53188-4999

    GENERATOR ALARMS AND SHUTDOWNSKATO CLASS F INSULATION GENERATORS See Katodrawing for setpoint recommendations on standby units

    Generator Winding (Prime Power)

    Alarm 311 F (155 C)

    Shutdown 329 F (165 C)

    Generator Bearing

    Alarm 185 F (85 C)Shutdown 203 F (95 C)

    MARATHON ELECTRIC MAGNAMAX DVR GENERATORS

    Prime Power (105 C) Generator Winding

    Alarm 293 F (145 C)

    Shutdown 311 F (155 C)

    Prime Power (105 C) Generator Bearing

    Alarm 230 F (110 C)

    Shutdown 248 F (120 C)

    Standby Power (130 C) Generator Winding

    Alarm 338 F (170 C)

    Shutdown 356 F (180 C)

    Standby Power (130 C) Generator Bearing

    Alarm 230 F (110 C)

    Shutdown 248 F (120 C)

    Prime or Standby Generator WindingTemperature Switch (GWTS)

    Shutdown 302 9 F (150 5 C) Switch N.O. or N.C.

    Comments

    GWTS is not located in the winding a lot likethe RTD or thermocouple so a lower tempera-

    ture device is used. No alarm GWTS isavailable at this time.

    LEROY SOMER CLASS F INSULATION GENERATORS

    Prime Power (105 C) Generator Winding

    Alarm 302 F (150 C)

    Shutdown 311 F (155 C)

    Prime Power (105 C) Generator (Sleeve or Roller) Bearing

    Alarm 194 F (90 C)

    Shutdown 203 F (95 C)

    Standby Power (130 C) Generator Winding

    Alarm 347 F (175 C)

    Shutdown 356 F (180 C)

    Standby Power (130 C) Generator (Sleeve or Roller) Bearing

    Alarm 239 F (115 C)

    Shutdown 248 F (120 C)

    LEROY SOMER CLASS H INSULATION GENERATORS

    Prime Power (105 C) Generator Winding

    Alarm 194 F (90 C)

    Shutdown 203 F (95 C)

    Prime Power (105 C) Generator (Sleeve or Roller) Bearin

    Alarm 194 F (90 C)

    Shutdown 203 F (95 C)

    Standby Power (130 C) Generator Winding

    Alarm 392 F (200 C)

    Shutdown 401 F (205 C)

    Standby Power (130 C) Generator (Sleeve or Roller) Bear

    Alarm 392 F (200 C)

    Shutdown 401 F (205 C)

    Comments:

    Class H is Leroy Somer standard. Only claH settings should be used for the LSA461LSA51 low voltage generators. These valu

    are ISO standard and should be used as mmums only.

    LEROY SOMER NA (MAGNETEK)

    CLASS F INSULATION GENERATORSGenerator Winding (Prime Power)

    Alarm 311 F (155 C)

    Shutdown 329 F (165 C)

    Generator Bearing

    Alarm 185 F (85 C)

    Shutdown 194 F (90 C)

  • 7/30/2019 01-2620f - Limites de Paradas

    8/8

    Service Bulletin No. 1-2620F

    Page 8 of 8WAUKESHA ENGINEDRESSER, INC.WAUKESHA, WI 53188-4999

    NEWAGE GENERATORS

    GENERATOR WINDING

    COMMENTS: These values are recommended by the British Standard BS4999 Part 72, which Newage Int. follow.

    INSULATION CLASS WARNING SHUTDOWN

    F C F C

    A 194 90 230 110

    E 230 110 266 130

    B 248 120 284 140

    F 284 140 320 160

    H 338 170 374 190