General catalogueEpoxy resin and silicon rubber insulators

Page 2: Aislador Epoxi Catalogo 2011 ENG

2

Page 3: Aislador Epoxi Catalogo 2011 ENG

1

Contents

Introduction 02

Insulators for indoor use 04

Insulators for outdoor use 27

Products for SF6 insulated switchgear 39

Page 4: Aislador Epoxi Catalogo 2011 ENG

2

Introduction

Veneta Isolatoriisa leadercompanyspecialisedintheproductionofMVepoxyresin insulatorsforelectricalandelectromechanicalindustry.Thecompanywasestablishedin1974,in1990itbecameasubsidiaryofCOMEMS.p.A,leaderinoiltransformercomponentandsolution.In2009alltheactivitiesweremovedtoanewfactorylocatedinCeggiaclosetoVenice.ThelongexperienceachievedbyVenetaIsolatorigavethepossibilitytodevelopawiderangeofproducts,havingsuitableandtestedelectricalandmechanicaltechnicalcharacteristics.Recentlythe company has also developed insulators in silicon rubber for outdoor installation. NowadaysVeneta Isolatori represents a reference point for many of electrical companies, that use VenetaIsolatori partnership for the development and realisation of insulators according to their ownbasic design. The export, almost 50% of the total production, cover a winde range of countriesandMVapplication.

Page 5: Aislador Epoxi Catalogo 2011 ENG

3

CertificationThe Quality System conforms to the ISO 9001 Standards, the Environmental Management System conforms to the ISO 14001 Standards and the Health and Safety Management System conforms to the OHSAS 18001 Standards, also regarding application in building site activities. All the systems are certified by an external independent organisation.

LaboratoriesThe Unit has internal laboratories equipped with state-of-theart apparatus for carrying out tests on materials, experimental, climatic, mechanical life, dielectric and partial discharge.

OperationEach design parameter is known, measured and recorded for each piece of insulator produced, so that their functional suitability can be declared in accordance with what is prescribed in the Standards. Production is also supported by lines which operate using the fabrication system with functional blocks. Thanks to this innovative system, the production lines can outfit each typical unit with maximum efficiency and speed.

Page 6: Aislador Epoxi Catalogo 2011 ENG

4

Insulators for indoor use

ISA 5

IPA 6

DC - DCP 8

DCL 10

SF - SC 12

SCD - SCB - SDY 14

IPAN 16

PSE/PSL 18

PRC 20

PRB 22

IPAR - ISOF - IPA 24

Page 7: Aislador Epoxi Catalogo 2011 ENG

5

Type ISALow voltage post insulators for indoor installation

GeneralcharacteristicsPost insulators made of epoxy resin (EP UL94V0) or polyesther reinforced with fiberglass (UP FG), suitable for indoor application with internal metal fitting. These insulators are particularly suitable to be used as single supports for bus-bars, fuses and for other equipment.

ApplicationFor indoor applications with working condition at max. operating temperature of 160 ºC (epoxy resin - EP UL94V0) and 130 ºC (polyesther - UP FG)

WorkingvoltageFrom 0,4 up to 2 kV

ReferencestandardsIEC 216 - DIN 53452 - DIN 53455

Identification

Type

ISA 30/30 M8

ISA 30/30 M6

ISA 40/40 M10

Fig.

1

2a

2b

3

Drawing

U2215

U3306

U3308

P3308

U4410

P4410

Maximumoperatingvoltage

0,4

0,75

2

1

2

kV

Ultimatebendingstress

1500

3000

7000

5000

4000

N (± 10%)

Ultimatetensilestress

2500

6000

12000

10000

8000

N (± 10%)

Material

EP UL 94V0

UP FG

EP UL 94V0

UP FG

EP UL 94V0

Color

RAL 9005

RAL 7030

RAL 9005

RAL 7030

RAL 9005

Weight

0,01

0,05

0,13

0,11

0,06

kg.

Technicaldata

ISA 20/20 M5

Fig. 1 Fig. 2a Fig. 2b Fig. 3

Page 8: Aislador Epoxi Catalogo 2011 ENG

6

Type IPApost insulators for indoor installation

GeneralcharacteristicsEpoxy resin post insulators, for indoor application, with internal metal fitting.These insulators are particularly suitable to be used as single supports for conductors, for fuses and for other equipment (as switchgears).

ApplicationFor indoor installation with working condition at T° max. 100 °C.

WorkingvoltageFrom 12 up to 36 kV(40,5 kV available on request)

ReferencestandardsIEC 60273 (CEI 36/12) - CENELEC HD 578 S1IEC 60660 (Fascicolo S/663)IEC 60137

Commercialcode1G101 + drawing (example IPA 7,2/4000 commercial code = 1G10107204)

Identification Technicaldata

TypeReference to

IECdesignation

IPA 7,2/4000

IPA 7,2/8000

IPA 12/4000

IPA 12/8000

IPA 12/16000

IPA 17,5/8000

IPA 17,5/16000

IPA 24/4000Standard

Enel DJ1053IPA 24/3000

StandardEnel DJ1056

IPA 24/4000

IPA 24/8000

IPA 24/10000

IPA 36/4000

IPA 36/8000

IPA 36/10000

JO 4 - 60

JO 8 - 60

JO 4 - 75

JO 8 - 75

JO 16 - 75

JO 8 - 95

JO 16 - 95

JO 4125

JO 8 - 125

JO 10 - 125

JO 4 - 170

JO 8 - 170

JO 10 - 170

Drawing

07204

07208

10010

10020

10025

20020

20026

24210

24220

24225

30030

30026

40010

40012

40026

Creepagedistance

>150

>235

>175

>230

>260

>300

>360

>370

>350

>400

>520

>520

>570

mm

Fins

3

4

5

8

7

13

12

10

Weight

0,6

0,7

0,8

1,5

1,1

2,2

1,1

1,2

1,6

2,6

1,8

2,9

3,4

kg.

Electricaldata Mechanicaldata

Maximum operation voltage

7,2

12

17,5

24

36

kV

Lightning impulse voltage

whitstand

60

75

95

125

170

kV

Dry power frequency

voltage whitstand

28

35

45

55

75

kV

Maximum deflection difference

between 20%and 50% of

the specifieldload

1,5

2

2,7

3,2

5

mm

Ultimatebending stress

4000

8000

4000

8000

16000

8000

16000

4000

8000

10000

4000

8000

10000

N

Page 9: Aislador Epoxi Catalogo 2011 ENG

7

95

130

175

210

225

310

mm. (+-1)

82

83

75

116

83

118

80

93

110

80

98

110

mm.

M12

M12

M16

M12

M16

M12

M16

M12

M16

18

18

25

18

25

25

18

25

18

25

mm. (min.)

M12

M16

M16

M20

M16

M20

M16

M20

M16

M20

25

25

32

25

32

25

32

25

32

mm. (min.)

0

18

14

18

36

35

36

0

18

35

42

32

60

42

mm.

M8

M6

M10

M6

M10

M6

M10

M6

M10

15

15

20

15

20

15

20

15

20

mm. (min.)

46

36

46

36

46

36

46

36

46

mm.

70

70

75

100

76

100

80

77

100

80

94

100

mm.

55

70

65

65

91

62

91

54,5

70

90

55

76

90

mm.

Technicaldata

h

Isnulatorheight

D

Maximumnominal

diameter ofinsulating

part

d1

Upperthreaded

centre hole(tapped)

t1

Holedepth

d1

d2

Basethreaded

centre hole(tapped)

t2

Holedepth

d2

L

Distancebetween base faceand lowerthreaded

end

d3

Auxiliaryupper

threadedhole

(tapped)

t3

Holedepth

d3

d

Distancebetween threaded

holesd3

D1

Maximumdiameter base face

D2

Maximumdiameter

upper face

AccessorIesNichel-plated male reduction.

3012Drawing 3016Drawing

Page 10: Aislador Epoxi Catalogo 2011 ENG

8

Type DC - DCPCapacitive insulators with low voltage lower reading connection

GeneralcharacteristicsEpoxy resin post insulators with capacitive devider for the reading of the voltage. Manufactured with internal metal fitting, they can be equipped with couplings and low voltage light signal box.These insulators are mainly suitable to be used as insulated supports of equipment, bus bar or fuses.

SafetyinformationThe insulators can be equipped with:- Safety valve type ATS drawing 4500 that, in case of incoming voltage higher than 600 V,

connect to earth the system;- Signal box type SF 5600, SC 5583, SCD 5500, and SCB 5590 that, through a gas arrester

installed inside, in case of incoming voltage higher than 600 V, automatically connect to earth the system. The heart connection system is self-resetting.

ApplicationIndoor installation at max working temperature of 85 °C.

WorkingvoltageFrom 12 to 36 kV.(40,5 available on request)

ReferencestandardsIEC 60137

Commercialcode1G103 + drawing (example DC 10 commercial code = 1G10350010)

Identification ElectricaldataMechani-caldata

H D1 D2 D Technicaldata

Type DrawingMaximum operation voltage

kV

DC 10 50010 12 75 35 220 3000 130 75 65 75 175 4 0,8

DC 15 50012 17,5 95 45 150 3000 175 76 62 83 260 5 1,1

DC 20 50013 24 125 55 150 3000 225 69 62 78 355 7 1,3

DC 30 50021 36 170 75 75 3000 310 80 55 80 520 13 1,8

DCP 10 50015 12 75 35 220 5000 130 70 65 75 175 4 0,8

DCP 15 50017 17,5 95 45 150 5000 175 76 62 83 260 5 1,1

DCP 20 50018 24 125 55 150 5000 225 76 69 85 350 7 1,6

DCP 30 50019 36 170 75 75 5000 310 94 76 98 520 12 2,9

Lightning impulse voltage

whitstand

kV

Dry power frequency

voltage whitstand

kV

Capaci-tance

pF

Ultimatebending stress (PO)

N

Insilatorheight

mm.

Diameter of base

face

mm.

Diameter of upper

face

mm.

Maximumnominaldiameter

ofinsulating

part

mm.

Creepagedistance

mm.

Fins

Weight

kg.

Page 11: Aislador Epoxi Catalogo 2011 ENG

9

typeDC

Upper

Base

typeDCP

Drawing 4500

Safety valve for overvoltage protection

typeATS

Steework hole Ø 16,5 mm

Voltagepresenceindicators

typeSF

drawing 5600

typeSC

drawing 5583

typeSCB

drawing 5590

typeSCD

drawing 5500

typeSDY

drawing 5811

StandardENELDY 811

ConnectiontypeATS4482

Insulator gaps

Grow

Washer

Grow

Tc M4

Screw M12/14

Page 12: Aislador Epoxi Catalogo 2011 ENG

10

Type DCLCapacitive insulators with low voltage side reading connection

GeneralcharacteristicsEpoxy resin post insulators with capacitive devider for thereading of the voltage Manufactured with internal metal fitting, they can be equipped with couplings and low voltage light signal box.These insulators are mainly suitable to be used as insulated supports of equipment, bus bar or fuses.

SafetyinformationThe insulators can be equipped with:- Safety valve type ALS drawing 4700 that, in case of

incoming voltage higher than 600 V, connects to earth the system;

- Signal box type SF 5600, SC 5583, SCD 5500 and SCB 5590 that, through a gas arrester installed inside, in case of incoming voltage higher than 600 V, automatically connect to earth the system. The heart connection system is

self-resetting.The DCL 24/I capacitive insulator, that utilise epoxy resin as dielectric; it has low capacitance condenser and low voltage outlet.

ApplicationIndoor installation at max working temperature of 85 °C.

WorkingvoltageFrom 12 to 36 kV

ReferencestandardsIEC 60137 (electrical tests)Enel standard DJ 1054 - DJ 1550 (DCL 24/I)

Commercialcode1G105 + drawing (example DCL 10 commercial code = 1G10550030)

DCL 10

DCL 15

DCL 24

DCL 24/IStandard

Enel DJ 1054

DCL 30

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

50030

50032

50031

50070

50072

50071

50040

50041

50042

52054

52050

52055

50310

50311

50312

12

17,5

24

24

36

75

95

125

125

170

35

45

55

55

75

220

150

150

7

75

standard

RG 58

standard

SF 5600

SC 5583

SCB 5590

SCD 5500

SDY 5811

SCB 5590

SCD 5500

SDY 5811

SF 5600

SC 5583

SCB 5590

SCD 5500

SDY 5811

Identification Electricaldata Technicaldata

Type Outlet Type DrawingMaximum operation

voltage

kV

Lightning impulse voltage

whitstand

kV

Dry power frequency

voltage whitstand

kV

Capacitance

±20% pF

Cable typeModel ofcomatiblesignal box

Page 13: Aislador Epoxi Catalogo 2011 ENG

11

IdentificationMechanical

dataH D1 D2 D3 Technicaldata

DCL 15

DCL 10

DCL 24

DCL 24/IStandard

Enel DJ 1054

DCL 30

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

Type Outlettype

50030

50032

50031

50070

50072

50071

50040

50041

50042

52054

52050

52055

50310

50311

50312

Drawing

4000

4000

3500

3500

3000

Ultimatebending stress

130

175

225

225

310

Insilatorheight

mm.

74

74

74

74

80

Diameter of base

face

mm.

53 87 165 5 0,9

53 87 245 7 1,1

55 87 350 9 1,4

55

55

Diameterof upper

face

mm. mm. mm. N° kg.

87

90

QuoteD3

350

490

Creepagedistance

9

13

Fins

1,75

2,2

Weight

Voltagepresenceindicators

typeSF

drawing 5600

typeSC

drawing 5583

typeSCB

drawing 5590

typeSCD

drawing 5500

typeSDY

drawing 5811

StandardENELDY 811

With type “C” outlet it is possible to connect safety valve type ALS drawing 4700 for over-voltage protection

L.V. Side reading connection type

Connection 1G10604580

Page 14: Aislador Epoxi Catalogo 2011 ENG

12

Type SF - SCVoltage presence indicators

GeneralcharacteristicsThe voltage presence indicators are devices used to supply information about the main circuit status inside the equipment where the devices are installed. To each lamp placed inside the indicator (L1 L2 L3) corresponds one phase of the input line. The line voltage presence is indicated by switching of the relevant lamp. The signal of voltage presence necessary to switch the lamps is sourced out by a capacitive coupling with an insulator equipped with capacitive output.

ApplicationIn MV cubicles for operating voltages from 1 to 36 kV.

TypeSFThe indicator SF is a light signal device made of one singlefix part. The indicator is equipped with a safety system, composed of one gas arrester for each phase, which connects the system to ground in case of overvoltage> 600 V. The arresters are self-resetting, this means that at the end of the discharge the device will start again to function normally.

TypeSCThe indicator SC is a light signal device made of one fix part and one mobile and removable part.The lamps are placed in the mobile part. The indicator is equipped with a safety system, composed of one gas arrester for each phase, which connects the system to ground in case of overvoltage > 600 V. The arresters are self-resetting, this means that at the end of the discharge the device will start again to function normally.

Capacitivesource Indicator SF5600-SC5583

Insulator type Maximum operation voltage

kV

DC - DCP - DCL 10 12 220 1,2 2 150

DC - DCP - DCL 15 17,5 150 1,1 2 130

DC - DCP - DCL 20/24 24 150 2 12 100

DCL 24/I 24 7 5 – 75

DC - DCP - DCL 30 36 75 1 10 145

Nominalcapacitance

pF ±20%

Pulsating lamplightning at

kV

Fix lamplightning at

kV

Voltage on indicator atmax. operating

voltage

V

Theabovementionedvalueswerereachedbyusingastandardcable(3meterslength)toconnectthecapacitiveinsulatorandthevoltageindicator.Thevalueshavea20%variability.

Page 15: Aislador Epoxi Catalogo 2011 ENG

13

typeSF5600

Front side Back side

Steelwork Lay-Out

typeSC5583

Back side

Mobile part

Complete set

Back side

Back side

Steelwork Lay-Out

Page 16: Aislador Epoxi Catalogo 2011 ENG

14

Type SCD - SCB - SDYVoltage presence indicators

GeneralcharacteristicsThe voltage presence indicators are devices used to supply information about the main circuit status inside the equipment where the devices are installed. To each lamp placed inside the indicator (L1 L2 L3) corresponds one phase of the input line. The line voltage presence is indicated by switching of the relevant lamp. The signal of voltage presence necessary to switch the lamps is sourced out by a capacitive coupling with an insulator equipped with capacitive output.

ApplicationIn MV cubicles for operating voltages from 1 to 36 kV.

TypeSCDThe indicator SCD is a light signal device made of one single fix part. Below each lamp there are relevant contact holes which allow to verify the phase accordance between two or more equipments, through the use of a phase accordance device DCF 6500. The indicator is equipped with a safety system, composed of one gas arrester for each phase, which connects the system to ground in case of overvoltage > 600 V. The arresters are self-resetting, this means that at the end of the discharge the device will start again to function normally. The signal device SCD can be used even to read a low input signal.

PhaseaccordancedeviceDCF6500Thanks to the phase accordance device DCF 6500 it is possible to verify if the lamps L1 (or L2 or L3) of two indicators SCD 5500 placed on two different equipments are connected to the same phase. When the phases are in accordance the lamp of the device DCF 6500 is off, while in case of non accordance of the phases the lamp is on.

TypeSCBThe indicator SCB is a light signal device made of one fix part and one mobile and removable part.The lamps are placed in the mobile part. The indicator is equipped with a safety system, composed of one gas arrester for each phase, which connects the system to ground in case of overvoltage > 600 V. The arresters are self-resetting, this means that at the The signal box SCB is used to read a low input signal.

TypeSDYThe signal device SDY is realized according to ENEL (National Power Company) specification DY 811. It is made of 1 front board base and of 3 mobile parts, one for each phase, equipped with removable and separated light indicators.The fix part is suitable to be connected with “RG DAT” monitoring device, according to Enel specification DY 1059.

Capacitivesource Indicator SCD5500-SCB5590-SDY5811

Insulator type Maximum operation voltage

kV

DC - DCP - DCL 10 12 220 1 2,5 50

DC - DCP - DCL 15 17,5 150 1 5 45

DC - DCP - DCL 20/24 24 150 1 13 38

DCL 24/I 24 7 3(*) – 36

DC - DCP - DCL 30 36 75 1 8 50

Nominalcapacitance

pF ±20%

Pulsating lamplightning at

kV

Fix lamplightning at

kV

Voltage on indicator atmax. operating

voltage

Volts

Theabovementionedvalueswerereachedbyusingastandardcable(3meterslength)toconnectthecapacitiveinsulatorandthevoltageindicator.Thevalueshavea20%variability.(*)ToreachthepulsationlevelrequiredbyDY811homologationitisnecessarytouseascreenedRG58cabletoconnectthecapacitiveinsulatorDCL

24/IandthevoltageindicatorSDY5811.

Page 17: Aislador Epoxi Catalogo 2011 ENG

15

tipeSCB5590

Back side

Mobile part

Complete set

Back side

Back side

Steelwork Lay-Out

typeSCD5500

Steelwork lay-out

Front side

serieSDY

Back side

Steelwork Lay-Out

Page 18: Aislador Epoxi Catalogo 2011 ENG

16

Type IPANBushing for indoor use

Generalcharacteristics12 ÷ 36 kV epoxy resin bushing insulators. The insulators can be fitted with copper bars designed from 250 up to 2000 A.They are equipped with internal metal fittings for installation on the relevant frame and with brass nuts and washers for fastening of phase connectors.

ApplicationIndoor installation at max working temperature of 85 ºC.

WorkingvoltageFrom 12 to 36 kV.

ReferencestandardsIEC 60137 (electrical tests).

Commercialcode1G107 + drawing (example IPAN 10/250 commercial code = 1G10781010)

Identification Electricaldata Technicaldata

Type Drawing

81010

81011

81012

81240

81014

81015

81016

82010

82011

82012

82240

82014

82015

82016

83010

83011

83012

83240

83014

83015

83016

84010

84011

84012

84013

84014

84015

84016

2,3

2,5

2,8

6

7

8,2

9

3,1

3,4

3,8

6,8

8

9,5

10,4

3,5

3,8

4,5

7,5

9

10,9

12

9,8

10,4

11,2

12,3

14,1

16,2

17,9

12

17,5

24

36

Maximumoperation voltage

kV

IPAN 10/250

IPAN 10/400

IPAN 10/630

IPAN 10/800

IPAN 10/1000

IPAN 10/1500

IPAN 10/2000

IPAN 15/250

IPAN 15/400

IPAN 15/630

IPAN 15/800

IPAN 15/1000

IPAN 15/1500

IPAN 15/2000

IPAN 20/250

IPAN 20/400

IPAN 20/630

IPAN 20/800

IPAN 20/1000

IPAN 20/1500

IPAN 20/2000

IPAN 30/250

IPAN 30/400

IPAN 30/630

IPAN 30/800

IPAN 30/1000

IPAN 30/1500

IPAN 30/2000

250

400

630

800

1000

1500

2000

250

400

630

800

1000

1500

2000

250

400

630

800

1000

1500

2000

250

400

630

800

1000

1500

2000

Nominalcurrent

A

35

45

55

75

Dry power frequency

voltage whitstand

kV

75

95

125

170

Lightning impulse voltage

whitstand

kV

220

390

480

620

230

330

440

Creepagedistance

mm.

3+3

6+6

8+8

8+8

4+4

Fins

Weight

kg.

Page 19: Aislador Epoxi Catalogo 2011 ENG

17

Identification Dimensionaldata

Type Drawing A B C D F G H L MR

Diameter Pitch Lenght

81010

81011

81012

81340

81014

81015

81016

140

205

260

405

260

405

520

810

8,5

10,5

140

205

280

410

106

106

106

160

75

75

75

120

87

87

87

118

380

510

620

940

M8x20

M8x20

M8x20

M10x20

12

16

20

24

30

36

42

12

16

20

24

30

36

42

12

16

20

24

30

36

42

12

16

20

24

30

36

42

1,5

1,5

1,5

2

2

2

3

1,5

1,5

1,5

2

2

2

3

1,5

1,5

1,5

2

2

2

3

1,5

1,5

1,5

2

2

2

3

45

45

45

60

55

55

70

70

8,5

8,5

175

215

175

215

350

430

134

134

134

110

110

110

126

126

126

470

550

670

960

82010

82011

82012

82240

82014

82015

82016

83010

83011

83012

83240

83014

83015

83016

84010

84011

84012

84013

84014

84015

84016

IPAN 10/250

IPAN 10/400

IPAN 10/630

IPAN 10/800

IPAN 10/1000

IPAN 10/1500

IPAN 10/2000

IPAN 15/250

IPAN 15/400

IPAN 15/630

IPAN 15/800

IPAN 15/1000

IPAN 15/1500

IPAN 15/2000

IPAN 20/250

IPAN 20/400

IPAN 20/630

IPAN 20/800

IPAN 20/1000

IPAN 20/1500

IPAN 20/2000

IPAN 30/250

IPAN 30/400

IPAN 30/630

IPAN 30/800

IPAN 30/1000

IPAN 30/1500

IPAN 30/2000

Steelwork holes Lay-Out

Page 20: Aislador Epoxi Catalogo 2011 ENG

18

Type PSE - PSLBushing for indoor/outdoor use

Generalcharacteristics12 ÷ 36 kV cicloaliphatic resin bushing insulators. The insulators can be fitted with copper bars designed from 250 up to 1000 A. They are equipped with internal metal fittings for installation on the relevant frame and they are supplied completed with:– Brass nuts and washer for fastening of phase connectors– O-Ring gasket– Screws and nuts for assembling of the bushing on the metallic frame

ApplicationOutdoor installation at max working temperature of 85 ºC.

WorkingvoltageFrom 12 to 36 kV.

ReferencestandardsIEC 60137 (electrical tests).

Commercialcode1G110 + drawing (example PSE 10/250 commercial code = 1G11071010)

Identification Electricaldata Technicaldata

Type Drawing

71010

71011

71012

71013

72010

72011

72012

72013

73010

73011

73012

73013

74010

74011

74012

74013

74014

73016

3,2

3,4

3,8

4,2

4,5

4,8

5,3

5,8

5,7

6

6,7

7,3

10,7

11,2

12

13

14,7

9,6

12

17,5

24

36

24

Maximumoperationvoltage

kV

PSE 10/250

PSE 10/400

PSE 10/630

PSE 10/800

PSE 15/250

PSE 15/400

PSE 15/630

PSE 15/800

PSE 20/250

PSE 20/400

PSE 20/630

PSE 20/800

PSE 30/250

PSE 30/400

PSE 30/630

PSE 30/800

PSE 30/1000

PSl 20/400

Standard Enel

250

400

630

800

250

400

630

800

250

400

630

800

250

400

630

800

1000

400

Nominalcurrent

A

35

45

55

75

55

Dry power frequency

voltage whitstand

kV

75

95

125

170

125

Lightning impulse voltage

whitstand

kV

350

540

740

860

740

Creepagedistanceside (B)

mm.

Weight

kg.

Page 21: Aislador Epoxi Catalogo 2011 ENG

19

Identification Dimensionaldata

Type Drawing A

mm.

A1

mm.

B

mm.

C

mm.

D

mm.

E

mm.

F

mm.

G

mm.

H

mm.

L

mm.

M

mm.

Diameter

mm.

R

Pitch

mm.

Thrededlenght

mm.

71010

71011

71012

71013

72010

72011

72012

72013

73010

73011

73012

73013

74010

74011

74012

74013

74014

73016

96

163

235

365

235

20

20

20

40

325

164

232

305

405

305

280

415

560

810

865

8,5

8,5

8,5

10,5

8,5

130

130

130

159

130

114

114

114

160

114

88

88

88

120

88

87

87

87

118

87

380

510

660

940

960

965

M8x20

M8x20

M8x20

M10x20

M8x20

12

16

20

24

12

16

20

24

12

16

20

24

12

16

20

24

30

16

1,5

1,5

1,5

2

1,5

1,5

1,5

2

1,5

1,5

1,5

2

1,5

1,5

1,5

2

2

1,5

45

45

45

60

70

45

PSE 10/250

PSE 10/400

PSE 10/630

PSE 10/800

PSE 15/250

PSE 15/400

PSE 15/630

PSE 15/800

PSE 20/250

PSE 20/400

PSE 20/630

PSE 20/800

PSE 30/250

PSE 30/400

PSE 30/630

PSE 30/800

PSE 30/1000

PSl 20/400

Standard Enel

Steelwork holes Lay-Out

Page 22: Aislador Epoxi Catalogo 2011 ENG

20

Type PRCProtection insulators

GeneralcharacteristicsEpoxy resin protection insulators, bell shaped, with internal metal fitting.

ApplicationIndoor application with working condition at T° max. 100° C.

WorkingvoltageFrom 12 to 36 kV.

Commercialcode1G123 + drawing (example PRC 12 commercial code = 1G12386010)

Technicaldata PRC12 PRC17 PRC24 PRC36

Drawing

H (mm.)

H1 (mm.)

D (mm.)

Maximum operation voltage (kV)

Dry power frequencyvoltage whitstand (kV)

Lightning impulse voltagewhitstand (kV)

Creepage distance (mm.)

Fins (N°)

Weight (kg.)

Tightening torque M10 (Nm)

86010

170

275

145

12

38

75

210

2

6

30

87015

230

335

140

17,5

50

95

280

3

7

30

88020

290

395

135

24

50

125

345

4

8

30

89030

350

455

130

36

75

170

430

5

9

30

Creepage distance

Steelwork holes Lay-Out

Page 23: Aislador Epoxi Catalogo 2011 ENG

21

Page 24: Aislador Epoxi Catalogo 2011 ENG

22

Type PRB 24-36 kVAir-air bushing for indoor use

GeneralcharacteristicsThe PRB bushings can be used as medium voltage inlet for indoor air insulated devices such as switchgears, in particular for applications in quite small machines.The bushings are realized on the one side with a coupling interface in accordance with EN 50180-50181 (DIN 47636; HN 52-S-61) standards. This type of interface allows a connection with the relevant moving connector. On the other part the sheded side allows a bare electrical wire connection.

AccessoriesPlastic cap for coupling interface protection.Only on request, alluminium flange suitable to fix the bushing to the steelwork.The fixing flange is necessary for the 400A version for mobile connector fastening.

Workingvoltage24-36 kV

ReferencestandardsIEC 60137 (electrical tests)EN 50180-50181 (DIN 47636; HN 52-S-61)

Commercialcode1G1240 + drawing (example PRB 24/400 commercial code = 1G12402430)

Identification

TypeFig.

1

2

3

DrawingMaximumoperationvoltage

kV

24

24

36

400

630

630

125

125

170

55

55

75

EN 50180EN 50181DIN 47636EN 50180EN 50181DIN 47636EN 50180EN 50181DIN 47636

IEC 137

IEC 137

IEC 137

Slidingcontact

M16

M16

380

380

730

2,65

2,65

4,2

A kV kV mm. kg.

Nominalcurrent

Lightning impulse voltage

whitstand

Dry power frequency

voltage whitstand

Couplingtype

Electricaltests

Connectiontype

Creepagedistance Weight

2430

2431

3670

Electricaldata Standards

PRB 24/400

PRB 24/630

PRB 36/630

Page 25: Aislador Epoxi Catalogo 2011 ENG

23

AssemblinginstructionsBushing insulator PRBPrepare the holes on the body of the tank as indicated in the steelwork holes Lay-out. Remove the paint, or any insulating coat in the area of fixing holes, in order to guarantee a correct earth connection of the bushing.Moreover, make sure that the surface where the bushing is placed is without any type of roughness or unevenness. It must be completely clean in order to guarantee a perfect tightness. It is recommended to use the fixing flange in order to strengthen the area where the bushing is fixed to the tank. For 400A version the use of the flange is necessary for mobile connector fastening. Place the flange, when used, and tighten the 3 fixing screws M6, together with their relevant washers, with a tightening force value of 9÷11 Nm. The tightening operation must be done crosswise. The lower connection (M16) must be fastened with a tightening force value of 90÷100 Nm.During mounting operations the plastic protective cap must be fitted and pressed right down on the bushing, in order to avoid faults caused by dirt or accidental scratching of the interface.

Color RAL 3013

Fig. 1

Color RAL 3013

Fig. 2

Page 26: Aislador Epoxi Catalogo 2011 ENG

24

Type IPAR - ISOF - IPAEpoxy resin insulators for rotative switchgear 24 kV

IPARThree phase rotating bushing block with recessedmetal fitting for assembling on the steelwork.

Commercialcode1G108 + drawing (example IPAR 65012 commercial code = 1G10865012)

ISOFDrawing: 69020Conductor connection insulator with air room for arc estinguishing.It’s equipped with internal metal fitting for the assembling on the steelwork and of the upper contact.

Referencestandards1G10869020

IPADrawing: technical at page 6Conductor connection insulator with internal metal fitting for the assembling on the steelwork and of the upper contact.

ApplicationFor indoor use, vertical and horizontal installation.

IPA

IPAR

ISOF

Page 27: Aislador Epoxi Catalogo 2011 ENG

25

Identification

A

Ø 20 mm.

Fig. Type Drawing L

mm.

690

770

870

B

mm.

210

250

300

Maximumoperationvoltage

W

12

17,5

24

24

Nominalcurrent

A

400

400

400

630

630

630

Lightning impulse voltage

whitstand

kV

75

95

125

125

Dry power frequency

voltage whitstand

kV

35

55

55

55

Creepagedistance

mm.

>350

>350

>350

Weight

kg.

11

12

13

2,3

Dimensionaldata Standards

1

2

IPAR

ISOF

65012

65017

65021

67012

67017

67021

69020

Alluminium

Alluminio

Alluminium

Copper - and silver plated alluminium

Copper - and silver plated alluminium

Copper - and silver plated alluminium

Copper - and silver plated alluminium

Fig. 1Three phase rotating bushing block type IPAR

IPARSpecial bushingblock IPAR for smallswitchgears (500 mm).

Drawing 65016

Fig. 2insulator with air room type

ISOF

Page 28: Aislador Epoxi Catalogo 2011 ENG

26

Page 29: Aislador Epoxi Catalogo 2011 ENG

27

Insulators for outdoor use

IPAE 28

PRG 24 30

PRG 36 32

PGS 24-36 34

BSL 36

Page 30: Aislador Epoxi Catalogo 2011 ENG

28

Type IPAEPost insulator for outdoor installation

GeneralcharacteristicsCicloaliphatic resin post insulators, for outdoor application, with internal metal fitting.These insulators are mainly indicated to be used as insulating supports for busbar, fuses and other equipment (as outdoor switchgears).

ApplicationFor outdoor installation with heavy (III) pollution level, according to IEC 60815, 71-2.Working condition temperatures: max 90 °C.

WorkingvoltageFrom 12 to 36 kV. (40,5 kV available on request)

ReferencestandardsIEC 60273 (CEI 36/12) - CENELEC HD 578 S1IEC 60660 (File S/663)IEC 60815, 71-2.

Commercialcode1G102 + drawing (example IPAE 10 commercial code = 1G10270100)

Identification Electricaldata Mechanicaldata Technicaldata

Creepagedistance Fins Weight

Maximum operation

voltage

Lightning impulsevoltage

whitstand

Dry power frequency

voltage whitstand

Ultimatebendingstress

Maximum deflection difference

between 20%and 50% of

the specifieldload

Type

IPAE 10

IPAE 15

IPAE 20

IPAE 30

Drawing

70100

70200

70300

70400

12

17,5

24

36

75

95

125

170

35

45

55

75

10000

8000

6000

4000

2

2,7

3,2

5

320

520

730

910

4

7

10

13

1,4

2,3

3,2

3,9

kV kV kV N mm mm N° kg.

Page 31: Aislador Epoxi Catalogo 2011 ENG

29

Identification Technicaldata

h

130

210

295

360

Insulatorheight

D

130

130

130

130

Maximumnominal

diameter ofinsulating

part

d1

M12

M12

M12

M12

Upperthreaded

centre hole(tapped)

t1

18

18

18

18

Holedepth

d1

d2

M16

M16

M16

M16

Basethreaded

centre hole

(tapped)

t2

26

26

26

26

Holedepth

d2

L

27

27

27

27

Distancebetween base faceand lowerthreaded

end

d3

M6

M6

M6

M6

Auxiliaryupper

threadedhole

(tapped)

t3

15

15

15

15

Holedepth

d3

d

36

36

36

36

Distancebetween threaded

holesd3

D1

90

90

90

90

Maximumdiameter

baseface

D2

70

70

70

70

Maximumdiameter

upper face

Type

IPAE 10

IPAE 15

IPAE 20

IPAE 30

Drawing

70100

70200

70300

70400

AccessoriesNichel-plated male reduction.

3012Drawing 3016Drawing

Page 32: Aislador Epoxi Catalogo 2011 ENG

30

Type PRG 24 kVSF6 - Air silicon rubber bushing

GeneralcharacteristicsThe PRG bushings can be used as medium voltage inlet for SF6 insulated devices such as switchgears suitable for outdoor applications. The external side is made by silicon rubber with internal core made by epoxy resin. The body guarantee solidity to the complex and perfect seal of SF6 gas filled in the inner part of electrical device.Is equipped with galvanized copper conductor and it is supplied completed with:- Top fixing cap made by galvanized brass brass;- Top connection fixing screw & nuts made by galvanized brass;- O-Ring gasket made by EPDM for SF6 gas seal;- Upon request, aluminium flange, screw & nuts for assembling of the bushing on the metallic frame.

ApplicationFor outdoor application and connection with bare electrical wire. The PRG bushings can be assembled in any position with the exception of the situation where the sheds are turned upside down, even if slightly

WorkingvoltageUp to 24 kV

ReferencestandardsIEC 60137 (eletrical test) - Enel unification chart DY 1806 Cap. 4IEC 60507 (1991): salinity salt fog test (type test)IEC 61109 (1992-03) 5000 hours accelerated ageing test (type test)

Technicaldata

Nominal current

Maximum operation voltage

Frequency withstand voltage

Impulse withstand voltage

Creepage distance

Weight

Commercial code

400 A

24 kV

55 kV

125 kV

780 mm.

3,3 kg.

1G11701998

630 A

24 kV

55 kV

125 kV

780 mm.

4,5 kg.

1G11702400

Mod.1998 Mod.2400

• The highlighted items are included in the supplied Kit

•• The highlighted items can be supplied on request

ComponentsPos.

Top connection fixing screw and nuts

Fixing cap

Silicon bushing

O-Ring gaskit

Aluminium insulator fixing flange

Lower connection fixing screws and nuts

Steelwork holes Lay-Out

1

2

3

4

5

6

7

••

••

Kit

Page 33: Aislador Epoxi Catalogo 2011 ENG

31

Assemblinginstructions- Prepare the holes on the body of the tank as indicated (item7).- Remove the paint, or insulating coat, in the area of fixing holes in order to guarantee a correct earth connection of the bushing.- More over make sure that the surface where the bushing hods is without any type of roughness, or unevenness and it must

be perfectly clean in order to guarantee a perfect tightening-up of the flat gaskets (item4).- Place the bushing (item3) on the tank after having positioned the gasket (item4).- Place the aluminium flange (item5) inside the tank and tighten the six fixing screws (item6) together with the relevant

washers with a tightening force value of 9÷11 Nm. The tighting of the screws must be done crosswise.- The lower connection to the M10 threaded hole must be fixed with a tightening force value of 30÷35 Nm.

Mod. 1998 Mod. 2400

Color RAL 7030 Color RAL 7030

Steelwork holes Lay-Out

Page 34: Aislador Epoxi Catalogo 2011 ENG

32

Type PRG 36 kVSF6 - Air silicon rubber bushing

GeneralcharacteristicsThe PRG bushings can be used as medium voltage inlet for SF6 insulated devices such as switchgears suitable for outdoor applications. The external side is made by silicon rubber with internal core made by epoxy resin. The body guarantee solidity to the complex and perfect seal of SF6 gas filled in the inner part of electrical device.Is equipped with galvanized copper conductor and it is supplied completed with:- Top fixing cap made by galvanized brass brass;- Top connection fixing screw & nuts made by galvanized brass;- O-Ring gasket made by EPDM for SF6 gas seal;- Upon request, aluminium flange, screw & nuts for assembling of the bushing on the metallic frame.

ApplicationFor outdoor application and connection with bare electrical wire. The PRG bushing can be assembled in any position with the exception of the situation where the sheds are turned upside down, even if slightly

WorkingvoltageUp to 36 kV

ReferencestandardsIEC 60137 (eletrical test) — Enel unification chart DY 1806 Cap. 4IEC 60507 (1991): salinity salt fog test (type test)IEC 61109 (1992-03) 5000 hours accelerated ageing test (type test)

Datitecnici

Nominal current

Maximum operation voltage

Frequency withstand voltage

Impulse withstand voltage

Creepage distance

Weight

Commercial code

630 A

36 kV

75 kV

170 kV

1050 mm.

5,1 kg.

1G11703600

Mod.3600

ComponentsPos.

Top connection fixing screw and nuts

Fixing cap

Silicon bushing

O-Ring gaskit

Aluminium insulator fixing flange

Lower connection fixing screws and nuts

Steelwork holes Lay-Out

1

2

3

4

5

6

7

••

••

Kit

• The highlighted items are included in the supplied Kit

•• The highlighted items can be supplied on request

with internal core made by epoxy resin

Page 35: Aislador Epoxi Catalogo 2011 ENG

33

Assemblinginstruction– Prepare the holes on the body of the tank as indicated

(item7).– Remove the paint, or insulating coat, in the area of fixing

holes in order to guarantee a correct earth connection of the bushing.

– Moreover make sure that the surface where the bushing holds is without any type of roughness, or unevenness and it must be perfectly clean in order to guarantee a perfect tightening-up of the flat gaskets (item4).

– Place the bushing (item3) on the tank after having positioned the gasket (item4).

– Place the aluminium flange (item5) inside the tank and tighten the six fixing screws (item6) together with the relevant washers with a tightening force value of 9÷11 Nm. The tighting of the screws must be done crosswise.

- The lower connection to the M10 threaded hole must be fixed with a tightening force value of 30÷35 Nm.

Mod. 3636

Steelwork holes Lay-Out Color RAL 7030

Page 36: Aislador Epoxi Catalogo 2011 ENG

34

Type PGS 24-36 kVSF6 - Air silicon rubber bushing

GeneralcharacteristicsAThe PGS bushings can be used as a fixed part for medium voltage input on SF6 gas or oil insulated machines. It is provided with a coupling interface according to DIN 47636 standard that allows a connection with the relevant movable connectors. It is forbidden to use the bushing in outdoor applications without the relevant movable connectors or without the silicon rubber protection (B).

A+BThe PGS bushing with the silicon rubber protection can be utilized outdoor for connections with bare electrical wire. The PGS can be assembled in any position except for the situation where the sheds of silicon rubber protection are turned upside down, even if slightly.

WorkingvoltageUp to 36 kV

ReferencestandardsIEC 60137 (electrical tests)IEC 60507 (1991): Salinity salt fog test (type test)IEC 61109 (1992-03) C: 5000 hours accelerated ageing test (type test)

Technicaldata

Normal current

Maximum operation voltage

Frequency whitstand voltage

Impulse whitstand voltage

Creepage dustance

Weight

Color

Commercial code

630 A

24 kV

55 kV

125 kV

2,4 kg.

RAL 3013

1G11701990

630 A

36 kV

75 kV

170 kV

2,9 kg.

RAL 3013

1G11701996

630 A

24 kV

55 kV

125 kV

780 mm.

4,1 kg.

RAL 7030

1G11702000

630 A

36 kV

75 kV

170 kV

1050 mm.

5,1 kg.

RAL 7030

1G11703000

A1990 A1996 A1990+B2000

A1996+B3000

ComponentsPos.

Top connection fixing screw and nuts

Fixing cap

Silicon bushing

Plastic protective cover

Grease poket

Connection intarface DIN 47636

Epoxy resin bushing

O-Ring gaskit

Steelwork holes Lay-Out

Aluminium insulator fixing flange

Lower connection fixing screws and nuts

• The highlighted items are included in the supplied Kit

•• The highlighted items can be supplied on request

1

2

3

4

5

6

7

8

9

10

11

••

••

Kit

Page 37: Aislador Epoxi Catalogo 2011 ENG

35

AssemblinginstructionPGS bushing (Fig.1and2):– Drill the holes on the body of the tank as indicated (9).– Remove the paint, or insulating coat, in the area of the

fixing fastener holes in order to guarantee a correct earth connection of the bushing.

– Moreover make sure that the surface where the bushing holds is without any type of roughness, or unevenness and it must be perfectly clean in order to guarantee a perfect tightness of the flat gaskets.

– Place the bushing (7) on the metal structure after having positioned the gasket (8). Place the aluminium flange (10) inside the tank and tighten the six fixing screws (11) together with the relevant washers with a tightening force value of 9÷11 Nm. The tighting of the screws must be done crosswise. The lower connection to the M10 threaded hole must be fixed with a tightening force value of 30÷35 Nm.

Silicon rubber protection (Fig.3and4):– Remove the plastic protective cover (4) from the bushing.

The plastic protective cover must be fitted and pressed right down on the bushing always when:

– the bushing is not connected to the movable connector;– the bushing does not have silicon rubber protection. This prevents faults caused by dirty or incidental scratching

of the interface (6).– Clean with alcohol the interface (6) and the area of contact

with the silicon rubber protection (3).– After the complete evaporation of the solvent, spread

evenly over the connection interface (6) the grease contained in the enclosed pocket (5).

– Pull the silicon rubber protection (3) on the bushing (7) and screw down tightly until maximum torque is obtained (90÷100 Nm). This can be done with the aid of a 20 mm spanner used on the top cap (2). The silicon rubber protection is correctly clamped if the bushing is totally covered with it.

– Turn the silicon rubber protection slightly to the left and to the right to distribuite grease evenly over the connection interface (6).

Fig. 1

Fig. 2

Fig. 3

Fig. 4

L -

68,5

mm

- M

od.

1990

- 2

4 kV

L -

108,

5 m

m -

Mod

. 19

96 -

36

kVH

- 2

90 m

m -

Mod

. 20

00 -

24

kVH

- 3

56 m

m -

Mod

. 30

00 -

36

kV

Page 38: Aislador Epoxi Catalogo 2011 ENG

36

Type BSLComposite insulators for line switches

GeneralcharacteristicsThe composite insulators type BSL are suitable to be used in MV line switches. These insulators are realized with a fiberglass and epoxy resin core and aluminium end fittings and covered by silicon rubber. This material gives best performances for an outdoor use: abrasion resistance against UV rays, in environements with very high pollution level and with high salinity concentration. Silicon is unbreakable and hidrophobic. It is not necessary to plan any maintenance operation, even in particularly difficult environement conditions.

ApplicationOutdoor line switches.

ReferencestandardsIEC 60815

Identiification

Drawing Drawing

A

Drawing

D

Drawing

mm.

110

80

115

145

333

393

423

543

663

873

873

673

643

860

kV N N mm. N° kg.

D1

2501

2502

2503

2504

2505

2506

2507

2508

2509

34341

Fig.

1

2

Dry impulsewithstand

voltage (BIL)

Theoricaltensilestress

Theoricalcompressive

stress

75 kV

95 kV

125 kV

170 kV

250 kV

325 kV

325 kV

250 kV

170 kV

325 kV

10000 12000

Fins

Minimumcreepagedistance

6

8

9

13

17

24

18

13

10

10+9

450

600

675

975

1275

1800

1935

1400

1120

weight

0,5

0,6

0,72

0,93

1,15

1,45

2,1

1,55

1,15

2,4

EletricaldataDimensionalcharacteristics Mechanicaldata Technicaldata

Page 39: Aislador Epoxi Catalogo 2011 ENG

37

Fig. 1 Fig. 2

Page 40: Aislador Epoxi Catalogo 2011 ENG

38

Page 41: Aislador Epoxi Catalogo 2011 ENG

39

Products for SF6 insulated switchgear

INV - PPC/PPT - PPS - PTS/IPC - IPF - INV 40

PPC - PPT - PPE 42

PTC 44

PTS 46

PRI 48

Page 42: Aislador Epoxi Catalogo 2011 ENG

40

Type INV - PPC/PPT - PPS - PTSIPC - IPF - INVFuse holder, bushings and accessories for SF6 insulated devices

INVDrawing: 1745 - 1736Epoxy resin fuse holder completed with lower and central contacts for fuse and silicon gasket for bushings assembling.

PPC/PPTDrawing: 3236 - 3220SF6 gas tight type, it is equipped with innen coupling typeEN 50180-50181 (DIN 47637).

PPSDrawing: 1945 - 1521No SF6 tight type, it is equipped with external coupling type EN 50180-50181(DIN 47636) and connection for L.V. reading.

PTSDrawing: 1921SF6 gas tight type, it is equipped with external coupling type EN 50180-50181(DIN 47636) DIN 47636 and connection for L.V. reading.

IPCDrawing: 1830Wire-test SF6 gas tight bushing completed with O-Ring type gasket.

IPFDrawing: 1730Fuse holder SF6 gas tight support bushings completed with O-Ring type gasket.

INVDrawing: 1760Fuse holder cover completed of upper contact, mechanism for fuse and silicon gasket for fuse holder coupling.

ApplicationFor indoor use, vertical and horizontal installation.

PPC/PPT3236/3220

PPS1945/1521

PTS1921

IPC1830

INV1760

INV1745/1736

IPF1730

Page 43: Aislador Epoxi Catalogo 2011 ENG

41

Silicon rubber extension for bushing typeIPC - Drawing: 1840

Fig. 4

Bushing type IPCDrawing: 1830

Identification

TypeFig.

1A

1B

2

3A

3B

4

Drawing Maximum operating voltage

24 kV

36 kV

24 kV

24 kV

24 kV

200 A

200 A

250 A

250 A

500 A

125 kV

170 kV

125 kV

125 kV

125 kV

55 kV

75 kV

55 kV

55 kV

55 kV

14

15

1

1,1

1,78

1

Nominal current Lightning impulsevoltage whitstand

Dry power frequencyvoltage whitstand Weight

1745 - 1760

1736 - 1760

1730

1945

1521

1830

Electricaldata kg.

INV

IPF

PPS

IPC

Fuse holder type INV 24 kVDrawing: 1745A = 592 mm.B = 90 mm.

36 kVDrawing: 1736A = 687 mm.B = 185 mm.

with cover drawing n. 1760

Fig. 1AFig. 1B

Bushing type IPF - Drawing: 1730

Fig. 2

Bushing type PPS - Drawing: 1945

Fig. 3A

Bushing type PPS - Drawing: 1521

Fig. 3B

Page 44: Aislador Epoxi Catalogo 2011 ENG

42

Type PPC - PPT - PPEBushing with internal plug connection

GeneralcharacteristicsThe PPC, PPT and PPE epoxy resin bushings can be used as medium voltage inlet connections for oil or SF6 insulated device, such as transformers or switchgears.They are equipped with internal coupling type DIN 47637 to be coupled with relevant mobile connectors.The PPC-DC 400-630 A bushing is equipped with a connection for the reading of L.V. by a light signal box.

ApplicationIndoor installation at max working temperature of 85º C

ReferencestandardsIEC 60137

Identification

PPC 20/250

PPC-DC 30/630

PPT 20/250

PPT 30/630

PPE 20/1250

Fig.

1

2

3

3236

3206

3220

3195

3227

24 kV

24-36 kV

24 kV

24-36 kV

24 kV

250 A

400-630 A

250 A

400-630 A

1250 A

125 kV

170 kV

125 kV

170 kV

125 kV

55 kV

75 kV

55 kV

75 kV

55 kV

DIN 47637 / ENEL DJ 1115

DIN 47637 / ENEL DJ 1113

DIN 47637 / ENEL DJ 1115

DIN 47637 / ENEL DJ 1113

DIN 47637 / ENEL DJ 1153

2,4

2,5

1,9

2

5,8

Electricaldata Referencestandards kg.

drawing nr. 3236

PPC20/250

drawing nr. 3206

PPC-DC30/630

Type DrawingMaximumoperating voltage

Nominalcurrent

Lightningimpulsevoltage

whitstand

Dry power frequency

voltage whitstand

Coupling type Weight

Page 45: Aislador Epoxi Catalogo 2011 ENG

43

drawing nr. 3220

PPT20/250

drawing nr. 3195

PPT30/630

drawing nr. 3227

PPE20/1250

Color RAL 3013

TechnicaldataPos.

Mobile connector fastening

Fastening insulator insert

Earth socket or outlet of the capacitive potential divider

Threaded central conductor

Epoxy resin insulated part

Connection socket

Electrical field deflector

Coupling type DIN 47637

Equipotential screen

Gasket O-ring

Gasket O-ring

Insulator fixing flange

Insulator screws and nuts

Screws plastic pretective cover

Coupling plastic pretective cover

Insulated insert

Screw M5

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

PPC/DC30/6330

PPC20/250

PPT20/250

PPT30/630

PPE20/1250

•The highlighted items are included in the supplied kit.

Page 46: Aislador Epoxi Catalogo 2011 ENG

44

Type PTCBushing with external plug connection

GeneralcharacteristicsThe PTC bushings can be used as a fixed part in medium voltage inlet for oil or SF6 insulated devices, such as transformers or switchgears.They are equipped with a connection for the reading of low voltage by a light signal box.

ApplicationFor indoor application, suitable for vertical or horizontal installation.

Workingvoltage24 - 36 kV

ReferencestandardsIEC 60137 (electrical tests)DIN 47636/HN 52-S-61 (coupling interface)

Identification

PTC 24/250

PTC 24/250-RCorto

PTC 36/400

PTC 24/400-RCorto

PTC 36/630

PTC 24/630-RCorto

Fig. A H

1

2

105

60

105

60

105

60

184

140

228

183

230

184,5

1922I-6284-02

1930I-7113-02

1933I-6274-02

1935NI-959

1923I-6250-2

1936I-7094-04

24 kV

24 kV

36 kV

24 kV

36 kV

24 kV

250 A

250 A

400 A

400 A

630 A

630 A

125 kV

125 kV

170 kV

125 kV

170 kV

125 kV

55 kV

55 kV

75 kV

55 kV

75 kV

55 kV

DIN 47636HN 52-S-61

DIN 47636HN 52-S-61

EN 50180HN 52-S-61

EN 50181HN 52-S-61

EN 50181DIN 47636

EN 50181DIN 47636

Slidingcontact •

Slidingcontact •

Slidingcontact •

Slidingcontact •

M16

M16

M8

M8

M10

M10

M10

M10

1,3

1,1

2,3

1,9

2,3

1,9

Electricaldata Standards C M kg.

•Werecommendtheuseofflange

Type DrawingMaximumoperationvoltage

Nominalcurrent

Lightningimpulsevoltage

whitstand

Dry power frequency

voltage whitstand

Couplingtype

Connetiontype

Thrededhole Weight

Page 47: Aislador Epoxi Catalogo 2011 ENG

45

Fig. 1

250A

Fig. 2

400-630A

ComponentsPos.

Lower connection

Epoxy resin insulated part

O-Ring gasket

Coupling interface DIN 47636

Copper bar

Insulator fixing flange

Fastening insulator screws

Plastic protective cover

All items are included in the supplied kit

1

2

3

4

5

6

7

8

Page 48: Aislador Epoxi Catalogo 2011 ENG

46

Type PTSBushing with external plug connection

GeneralcharacteristicsThe PTS bushings can be used as a fixed part in medium voltage inlet for oil or SF6 insulated devices, such as transformers or switchgears .They are equipped with a copper conductor and is supplied completed with O-ring gasket, aluminium flange and screws and nuts for assembling operations on the metallic tank.

ApplicationFor indoor application, suitable for vertical or horizontal installation.

Workingvoltage24-36 kV

ReferencestandardsIEC 60137 (eletrical test) EN 50180-50181 (DIN 47636 / HN 52-S-61) coupling interface.

Identification

PTS 24/250

PTS 24/630

PTS 36/400

PTS 36/630

PTS 24/630

1921

1925 M

1942

1925

1929

Fig.

1

2

3

24

36

24

kV

250

630

400

630

630

A

125 kV

170 kV

125 kV

55 kV

75 kV

55 kV

Lamellare

M16x29 mm.

Lamellare

M16x29 mm.

M16x29 mm.

mm. (min.)

M8

M12

M8

M12

M12

222

239

266,5

269

234

mm. (± 1)

150

120

150

150

120

mm.

1,4

2,2

2,4

2,4

3,2

kg.

Electricaldata C M H L

Type DrawingMaximumoperationvoltage

Nominalcurrent

Lightningimpulsevoltage

whitstand

Dry power frequency

voltage whitstand

Contacttype

Thrededhole Weight

Page 49: Aislador Epoxi Catalogo 2011 ENG

47

Fig. 1 Fig. 2 Fig. 3

1

2

3

4

5

6

78

9

10

11

ComponentsPos.

Lower connection

Epoxy resin insulated part

Earth socket or outlet of the capacitive potential divider

O-Ring gasket

Coupling interface DIN 47636

Copper bar

Upper connection

Insulator fixing flange

Fastening insulator screws

Mobile connector fastening 25 e 400 A.

Plastic protective cover

All the items are included in the supplied kit

1

2

3

4

5

6

7

8

9

10

11

Page 50: Aislador Epoxi Catalogo 2011 ENG

48

Type PRI 24 kVSF6 - air bushing for indoor use

GeneralcharacteristicsThe PRI bushings can be used as medium voltage inlet for SF6 insulated devices such as switchgears suitable for indoor applications.They are equipped with nichel-plated copper conductor and it is supplied completed with O-Ring gasket made by EPDM for SF6 gas seal.

ApplicationFor indoor application and connection with bare electrical wire.

WorkingvoltageUp to 24 kV

ReferencestandardsIEC 60137

Commercialcode1G12185024

AssemblinginstructionsBushing insulator PRI.Prepare the holes on the body of the tank as indicated in the steelwork holes Lay-out. Remove the paint, or any insulating coat in the area of fixing holes, in order to guarantee a correct earth connection of the bushing.Moreover, make sure that the surface where the bushing is placed is without any type of roughness or unevenness. It must be completely clean in order to guarantee a perfect tightness.Connect to earth, when not used as capacitive outlet, the M5 thread (A) connected to the equipotential screen.Tighten the 6 fixing screws M6, together with their relevant washers, with a tightening force value of 9 ÷ 11 Nm. The tightening operation must be done crosswise. The lower connection (M10) must be fastened with a tightening force value of 30 ÷ 35 Nm.

Technicaldata

Nominal current

Max operating voltage

Frequency withstand voltage

Impulse withstand voltage

Creepage distance

Weight

630 A

24 kV

55 kV

125 kV

380 mm.

1,95 kg.

Mod.85024

Page 51: Aislador Epoxi Catalogo 2011 ENG

49

Steelwork holes Lay-Out

Page 52: Aislador Epoxi Catalogo 2011 ENG

50

Page 53: Aislador Epoxi Catalogo 2011 ENG

51

Page 54: Aislador Epoxi Catalogo 2011 ENG

52

Note

Page 55: Aislador Epoxi Catalogo 2011 ENG

53

Page 56: Aislador Epoxi Catalogo 2011 ENG

54

VenetaIsolatoriVia Sile 2230022 Ceggia (VE) - ITALYTel.: +39 0444 449311Fax: +39 0444 449381 E-mail : [email protected]

www.comem.com

The data and the illustrations are not binding. We reserve the right to modify the contents of this document on the basis of technical development of the products, without prior notice.