CARGAS DE SERVICIO EN CADA PISO DE LA EDIFICACION CARGA SISMICA- 1ER PISO DESCRIPCION BASE( X) ALTURA(Y ) LARGO(Z ) PESO UNITARIO CANTIDAD TOTAL LOSA 5.00 8.00 1 420 5 10500 MUROS 5.00 8.00 1 100 5 2500 ACABADOS 5.00 8.00 1 100 5 2500 S/C 5.00 8.00 1 350 0.50 875 VIGA X-X 0.25 0.50 24.00 2400 4.5 32400 VIGA Y-Y 0.35 0.65 28.00 2400 4.5 68796 COLUMNA CENTRAL 0.6 0.75 3 2400 8 25920 COLUMNA LATERAL 0.55 0.60 3 2400 8 19008 COLUMNA ESQUINERA 0.5 0.6 3 2400 3 6480 16897 9 CARGA SISMICA- 2DO PISO DESCRIPCION BASE( X) ALTURA(Y ) LARGO(Z ) PESO UNITARIO CANTIDAD TOTAL LOSA 5.00 8.00 1 420 4 8400 MUROS 5.00 8.00 1 100 4 2000 ACABADOS 5.00 8.00 1 100 4 2000 S/C 5.00 8.00 1 350 0.5 875 VIGA X-X 0.25 0.5 24.00 2400 4.5 32400 VIGA Y-Y 0.35 0.65 28.00 2400 4.5 68796 COLUMNA CENTRAL 0.60 0.75 3 2400 8 25920 COLUMNA LATERAL 0.55 0.6 3 2400 8 19008 COLUMNA ESQUINERA 0.50 0.6 3 2400 3 6480 16587 9

Cortante Basal

Embed Size (px)

DESCRIPTION

Concreto Armado, Cortante basal de estación de bomberos de 5 niveles

Citation preview

Page 1: Cortante Basal

CARGAS DE SERVICIO EN CADA PISO DE LA EDIFICACION

CARGA SISMICA- 1ER PISODESCRIPCION BASE(X) ALTURA(Y) LARGO(Z) PESO UNITARIO CANTIDAD TOTAL

LOSA 5.00 8.00 1 420 5 10500MUROS 5.00 8.00 1 100 5 2500

ACABADOS 5.00 8.00 1 100 5 2500S/C 5.00 8.00 1 350 0.50 875

VIGA X-X 0.25 0.50 24.00 2400 4.5 32400VIGA Y-Y 0.35 0.65 28.00 2400 4.5 68796

COLUMNA CENTRAL 0.6 0.75 3 2400 8 25920COLUMNA LATERAL 0.55 0.60 3 2400 8 19008

COLUMNA ESQUINERA 0.5 0.6 3 2400 3 6480168979

CARGA SISMICA- 2DO PISODESCRIPCION BASE(X) ALTURA(Y) LARGO(Z) PESO UNITARIO CANTIDAD TOTALLOSA 5.00 8.00 1 420 4 8400MUROS 5.00 8.00 1 100 4 2000ACABADOS 5.00 8.00 1 100 4 2000S/C 5.00 8.00 1 350 0.5 875VIGA X-X 0.25 0.5 24.00 2400 4.5 32400VIGA Y-Y 0.35 0.65 28.00 2400 4.5 68796COLUMNA CENTRAL 0.60 0.75 3 2400 8 25920COLUMNA LATERAL 0.55 0.6 3 2400 8 19008COLUMNA ESQUINERA 0.50 0.6 3 2400 3 6480 165879

CARGA SISMICA- 3ER PISO

Page 2: Cortante Basal

DESCRIPCION BASE(X) ALTURA(Y) LARGO(Z) PESO UNITARIO CANTIDAD TOTALLOSA 5.00 8.00 1 420 3 6300MUROS 5.00 8.00 1 100 3 1500ACABADOS 5.00 8.00 1 100 3 1500S/C 5.00 8.00 1 350 0.5 875VIGA X-X 0.25 0.5 24.00 2400 4.5 32400VIGA Y-Y 0.35 0.65 28.00 2400 4.5 68796COLUMNA CENTRAL 0.60 0.75 3 2400 8 25920COLUMNA LATERAL 0.55 0.6 3 2400 8 19008COLUMNA ESQUINERA 0.50 0.6 3 2400 3 6480 162779

CARGA SISMICA- 4TO PISODESCRIPCION BASE(X) ALTURA(Y) LARGO(Z) PESO UNITARIO CANTIDAD TOTALLOSA 5.00 8.00 1 420 2 4200MUROS 5.00 8.00 1 100 2 1000ACABADOS 5.00 8.00 1 100 2 1000S/C 5.00 8.00 1 350 0.5 875VIGA X-X 0.25 0.5 24.00 2400 4.5 32400VIGA Y-Y 0.35 0.65 28.00 2400 4.5 68796COLUMNA CENTRAL 0.60 0.75 3 2400 8 25920COLUMNA LATERAL 0.55 0.6 3 2400 8 19008COLUMNA ESQUINERA 0.50 0.6 3 2400 3 6480 159679

CARGA SISMICA- 5TO PISODESCRIPCION BASE(X) ALTURA(Y) LARGO(Z) PESO UNITARIO CANTIDAD TOTALLOSA 5.00 8.00 1 420 1 2100MUROS 5.00 8.00 1 100 1 500ACABADOS 5.00 8.00 1 100 1 500S/C 5.00 8.00 1 350 0.5 875VIGA X-X 0.25 0.5 24.00 2400 4.5 32400VIGA Y-Y 0.35 0.65 28.00 2400 4.5 68796COLUMNA CENTRAL 0.60 0.75 3 2400 8 25920COLUMNA LATERAL 0.55 0.6 3 2400 8 19008COLUMNA ESQUINERA 0.50 0.6 3 2400 3 6480 156579

PESO TOTAL: 813 895 Kg

CALCULO DE LA CORTANTE BASAL

Page 3: Cortante Basal

ANALISIS ESTÁTICO:

Fórmula

FACTOR DE ZONA

CATEGORIA DE EDIFICIOS

ZONA Z CATEGORIA DESCRIPCION FACTOR U

3 0.4 A EDIFICACIONES ESENCIALES 1.5

2 0.3 B EDIFICACIONES IMPORTANTES 1.3

1 0.15 C EDIFICCIONES COMUNES 1.0

PARAMETROS DEL SUELO

TIPO DESCRIPCION Tp (s) S

S1 Suelo rígido 0.4 1.0

S2 Suelo intermedio 0.6 1.2

S3 Suelo flexible 0.9 1.4

V= Z .U .C . SR

. P

Page 4: Cortante Basal

Factor de Amplificación Sísmica ( C ):

Fórmula

Periodo Fundamental:

CT 35CT 45CT 60

Fuerza cortante en la base:

Fórmula

Datos:

Z= 0.15 R= 8U= 1.5 hn= 15

C =2.5(TpT

) ; C ≤ 2.5T=

hnCT

V=¿ ZUCSR

. P ; CR

SISTEMAS ESTRUCTURA

L

SITEMA ESTRUCTURAL COEFICIENTE DE REDUCCION

( R )

CONCRETO Pórticos de concreto armado

8

Page 5: Cortante Basal

C= 2.5 Ct= 35S= 1.4 P= 813895.0

0 Tp= 0.9

Tenemos que:

V = 80117.79 Kg

Revisando que cumpla el factor amplificación sísmica:

T = 0.43

C = 5.25 < 2.5 ----- NO CUMPLE

C = 2.5

Verificando que CR≥0.125 :

0.312 ≥ 0.125 ----- SI CUMPLE

NIVEL Pi(kg) Hi(m) PiHi(kg) PiHi/∑PiHi (PiHi/∑PiHi)x V(tn)

5 68796.00 15.00 1031940.00 0.50 39.8594 25920.00 12.00 311040.00 0.15 12.0143 19008.00 9.00 171072.00 0.08 6.6082 6480.00 3.00 19440.00 0.01 0.7511 168979.00 3.20 540732.80 0.26 20.886

TOTAL PiHi 2074224.80 V= 40.259