DISEÑO DEL REFUERZO PARA VIGAS CONTINUAS DE CIMENTACION ACERO LONGITUDINAL VIGAS CONTINUAS DE CIMENTACION EJE FD-FA 1. Colocar dimensiones de la viga continua 30.0 cm 3 Ø 3/4 '' As Positivo 5.04 cm² Verificar As min y As max 80.0 cm 2 Ø 1/2" Para evitar el pandeo del estribo 8.40 cm² 40.0 cm As Negativo 11.04 cm² Cumple con As min y As max 9 Ø 1/2 '' 190.0 cm 11.04 cm² 2. Colocar Diametro de Barra Longitudinal asumida, Estribo y Momento. REFUERZO POSITIVO REFUERZO NEGATIVO ACERO MINIMO: f`c = 210.00 Kg/cm2 f`c = 210.00 Kg/cm2 ρ min = 0.0024 fy = 4200.00 Kg/cm2 fy = 4200.00 Kg/cm2 As min = 8.40 cm² b = 190.00 cm b = 30.00 cm Ø barra = 3/4 '' h = 120.00 cm h = 120.00 cm As = 2.850 cm² Ø barra = 1/2 '' Ø barra = 1/2 '' Tomamos 3 Ø ### Ø estribo = 3/8 '' Ø estribo = 3/8 '' ACERO MAXIMO recub. = 2.50 cm recub. = 7.50 cm ρmax = 0.0163 d = 115.91 cm d = 110.91 cm As max = 56.57 cm² M = 22.03 Tn-m M = 44.48 Tn-m Ø barra = 3/4 '' a = 0.624 cm a = 8.659 cm As = 2.850 cm² As = 5.04 cm² As = 11.04 cm² Tomamos 20 Ø ### 3. Aceros Negativos y Positivos Finales ACERO POSITIVO ACERO NEGATIVO As Positivo 8.40 cm² As Negativo 11.04 cm² 0.43 Ø barra = 3/4 '' Ø barra = 1/2 '' As = 2.850 cm² As = 1.267 cm² Tomamos 3 Ø 3/4 '' Tomamos 9 Ø 1/2 ''

DISEÑO VIGAS CONTINUAS

Embed Size (px)

Citation preview

Page 1: DISEÑO VIGAS CONTINUAS

DISEÑO DEL REFUERZO PARA VIGAS CONTINUAS DE CIMENTACION

ACERO LONGITUDINALVIGAS CONTINUAS DE CIMENTACION EJE FD-FA1. Colocar dimensiones de la viga continua

30.0 cm3 Ø 3/4 '' As Positivo 5.04 cm² Verificar As min y As max

80.0 cm2 Ø 1/2" Para evitar el pandeo del estribo

8.40 cm²

40.0 cmAs Negativo 11.04 cm² Cumple con As min y As max

9 Ø 1/2 '' 190.0 cm

11.04 cm²

2. Colocar Diametro de Barra Longitudinal asumida, Estribo y Momento.REFUERZO POSITIVO REFUERZO NEGATIVO ACERO MINIMO:

f`c = 210.00 Kg/cm2 f`c = 210.00 Kg/cm2 ρ min = 0.0024fy = 4200.00 Kg/cm2 fy = 4200.00 Kg/cm2 As min = 8.40 cm²b = 190.00 cm b = 30.00 cm Ø barra = 3/4 ''h = 120.00 cm h = 120.00 cm As = 2.850 cm²

Ø barra = 1/2 '' Ø barra = 1/2 '' Tomamos 3 Ø 3/4 ''Ø estribo = 3/8 '' Ø estribo = 3/8 '' ACERO MAXIMO

recub. = 2.50 cm recub. = 7.50 cm ρmax = 0.0163d = 115.91 cm d = 110.91 cm As max = 56.57 cm²

M = 22.03 Tn-m M = 44.48 Tn-m Ø barra = 3/4 ''a = 0.624 cm a = 8.659 cm As = 2.850 cm²

As = 5.04 cm² As = 11.04 cm² Tomamos 20 Ø 3/4 ''

3. Aceros Negativos y Positivos FinalesACERO POSITIVO ACERO NEGATIVOAs Positivo 8.40 cm² As Negativo 11.04 cm² 0.43

Ø barra = 3/4 '' Ø barra = 1/2 ''As = 2.850 cm² As = 1.267 cm²

Tomamos 3 Ø 3/4 '' Tomamos 9 Ø 1/2 ''

Page 2: DISEÑO VIGAS CONTINUAS

ACERO TRANSVERSAL15.000 Tn/m² REFUERZO NEGATIVO22.500 Tn/m² f`c = 210.00 Kg/cm2

Tomando B = 1.00 m □ Ø 3/8 '' @ 0.27 fy = 4200.00 Kg/cm2Mom. Neg = 7.20 Tn-m b = 100.00 cm

30.0 cm h = 40.00 cmØ barra = 1/2 ''

80.0 cm 1/2 '' @ 0.2 Ø estribo = 3/8 ''recub. = 7.50 cm

80.0 cm d = 30.91 cmM = 7.20 Tn-m

40.0 cm a = 1.486 cmAs = 6.31 cm²

190.0 cm Ø barra = 1/2 ''As = 1.267 cm²

22.50 Tn/m @ = 20.00

VERIFICACION POR CORTANTE

Vu = 25.000 Tn A cara de columna Ø.Vc = Vud =

Wu = 1.49 Tn/m 38.344 Tn > 24.541 Tn Ok

recub. = 7.50 cm

Ø barra = 1/2 ''

Ø estribo = 3/8 ''b = 190.00 cmd = 30.91 cm

DISEÑO DE REFUERZO TRANSVERSAL

REFUERZO DENTRO DE LA ZONA DE CONFINAMIENTO

2d = 2.218 mØ estribo = 3/8 ''

La separacion de los estribos debe ser:S ≤ d/4 = 27.73 cm S = 27.00 cm □ Ø 3/8 '' @ 0.27

S ≤ 30.00 cm

REFUERZO FUERA DE LA ZONA DE CONFINAMIENTO

sadm Suelo =s diseño =

Se colocará refuerzo Transversal por confinamiento a una distancia "2d" medida desde la cara del apoyo.

Page 3: DISEÑO VIGAS CONTINUAS

La separacion de los estribos debe ser:S = 55.00 cm □ Ø 3/8 '' @ 0.55

Page 4: DISEÑO VIGAS CONTINUAS

DISEÑO DEL REFUERZO PARA VIGAS CONTINUAS DE CIMENTACION

ACERO LONGITUDINALVIGAS CONTINUAS DE CIMENTACION EJE F10-F61. Colocar dimensiones de la viga continua

25.0 cm3 Ø 3/4 '' As Positivo 7.89 cm² Verificar As min y As max

90.0 cm2 Ø 1/2" Para evitar el pandeo del estribo

8.21 cm²

50.0 cmAs Negativo 12.55 cm² Cumple con As min y As max

5 Ø 3/4 '' 60.0 cm

12.55 cm²

2. Colocar Diametro de Barra Longitudinal asumida, Estribo y Momento.REFUERZO POSITIVO REFUERZO NEGATIVO ACERO MINIMO:

f`c = 210.00 Kg/cm2 f`c = 210.00 Kg/cm2 ρ min = 0.0024fy = 4200.00 Kg/cm2 fy = 4200.00 Kg/cm2 As min = 8.21 cm²b = 60.00 cm b = 25.00 cm Ø barra = 3/4 ''h = 140.00 cm h = 140.00 cm As = 2.850 cm²

Ø barra = 1/2 '' Ø barra = 1/2 '' Tomamos 3 Ø 3/4 ''Ø estribo = 3/8 '' Ø estribo = 3/8 '' ACERO MAXIMO

recub. = 2.50 cm recub. = 7.50 cm ρmax = 0.0163d = 135.91 cm d = 130.91 cm As max = 55.27 cm²

M = 40.08 Tn-m M = 59.29 Tn-m Ø barra = 3/4 ''a = 3.095 cm a = 11.809 cm As = 2.850 cm²

As = 7.89 cm² As = 12.55 cm² Tomamos 20 Ø 3/4 ''

3. Aceros Negativos y Positivos FinalesACERO POSITIVO ACERO NEGATIVOAs Positivo 8.21 cm² As Negativo 12.55 cm² 0.43

Ø barra = 3/4 '' Ø barra = 3/4 ''As = 2.850 cm² As = 2.850 cm²

Tomamos 3 Ø 3/4 '' Tomamos 5 Ø 3/4 ''

Page 5: DISEÑO VIGAS CONTINUAS

ACERO TRANSVERSAL15.000 Tn/m² REFUERZO NEGATIVO22.500 Tn/m² f`c = 210.00 Kg/cm2

Tomando B = 1.00 m □ Ø 3/8 '' @ 0.3 fy = 4200.00 Kg/cm2Mom. Neg = 0.34 Tn-m b = 100.00 cm

25.0 cm h = 50.00 cmØ barra = 1/2 ''

90.0 cm 1/2 '' @ 5.68 Ø estribo = 3/8 ''recub. = 7.50 cm

17.5 cm d = 40.91 cmM = 0.34 Tn-m

50.0 cm a = 0.052 cmAs = 0.22 cm²

60.0 cm Ø barra = 1/2 ''As = 1.267 cm²

22.50 Tn/m @ = 568.00

VERIFICACION POR CORTANTE

Vu = 25.000 Tn A cara de columna Ø.Vc = Vud =

Wu = 1.49 Tn/m 16.026 Tn < 24.392 Tn Aumentar Espesor de Ala

recub. = 7.50 cm

Ø barra = 1/2 ''

Ø estribo = 3/8 ''b = 60.00 cmd = 40.91 cm

DISEÑO DE REFUERZO TRANSVERSAL

REFUERZO DENTRO DE LA ZONA DE CONFINAMIENTO

2d = 2.618 mØ estribo = 3/8 ''

La separacion de los estribos debe ser:S ≤ d/4 = 32.73 cm S = 30.00 cm □ Ø 3/8 '' @ 0.3

S ≤ 30.00 cm

REFUERZO FUERA DE LA ZONA DE CONFINAMIENTO

sadm Suelo =s diseño =

Se colocará refuerzo Transversal por confinamiento a una distancia "2d" medida desde la cara del apoyo.

Page 6: DISEÑO VIGAS CONTINUAS

La separacion de los estribos debe ser:S = 65.00 cm □ Ø 3/8 '' @ 0.65

Page 7: DISEÑO VIGAS CONTINUAS

DISEÑO DEL REFUERZO PARA VIGAS CONTINUAS DE CIMENTACION - CONECTADAS

ACERO LONGITUDINALVIGAS CONTINUAS DE CIMENTACION EJE FB-FC1. Colocar dimensiones de la viga continua

25.0 cm3 Ø 3/4 '' As Positivo 4.28 cm² Verificar As min y As max

90.0 cm2 Ø 1/2" Para evitar el pandeo del estribo

8.21 cm²

50.0 cmAs Negativo 9.70 cm² Cumple con As min y As max

5 Ø 5/8 '' 100.0 cm

9.70 cm²

2. Colocar Diametro de Barra Longitudinal asumida, Estribo y Momento.REFUERZO POSITIVO REFUERZO NEGATIVO ACERO MINIMO:

f`c = 210.00 Kg/cm2 f`c = 210.00 Kg/cm2 ρ min = 0.0024fy = 4200.00 Kg/cm2 fy = 4200.00 Kg/cm2 As min = 8.21 cm²b = 100.00 cm b = 25.00 cm Ø barra = 3/4 ''h = 140.00 cm h = 140.00 cm As = 2.850 cm²

Ø barra = 1/2 '' Ø barra = 1/2 '' Tomamos 3 Ø 3/4 ''Ø estribo = 3/8 '' Ø estribo = 3/8 '' ACERO MAXIMO

recub. = 2.50 cm recub. = 7.50 cm ρmax = 0.0163d = 135.91 cm d = 130.91 cm As max = 55.27 cm²

M = 21.90 Tn-m M = 46.33 Tn-m Ø barra = 3/4 ''a = 1.007 cm a = 9.130 cm As = 2.850 cm²

As = 4.28 cm² As = 9.70 cm² Tomamos 20 Ø 3/4 ''

3. Aceros Negativos y Positivos FinalesACERO POSITIVO ACERO NEGATIVOAs Positivo 8.21 cm² As Negativo 9.70 cm² 0.43

Ø barra = 3/4 '' Ø barra = 5/8 ''As = 2.850 cm² As = 1.979 cm²

Tomamos 3 Ø 3/4 '' Tomamos 5 Ø 5/8 ''

Page 8: DISEÑO VIGAS CONTINUAS

ACERO TRANSVERSAL10.000 Tn/m² REFUERZO NEGATIVO15.000 Tn/m² f`c = 210.00 Kg/cm2

Tomando B = 1.00 m □ Ø 3/8 '' @ 0.3 fy = 4200.00 Kg/cm2Mom. Neg = 1.05 Tn-m b = 100.00 cm

25.0 cm h = 50.00 cmØ barra = 1/2 ''

90.0 cm 1/2 '' @ 1.85 Ø estribo = 3/8 ''recub. = 7.50 cm

37.5 cm d = 40.91 cmM = 1.05 Tn-m

50.0 cm a = 0.161 cmAs = 0.68 cm²

100.0 cm Ø barra = 1/2 ''As = 1.267 cm²

15.00 Tn/m @ = 185.00

VERIFICACION POR CORTANTE

Vu = 25.000 Tn A cara de columna Ø.Vc = Vud =

Wu = 1.49 Tn/m 26.709 Tn > 24.392 Tn Ok

recub. = 7.50 cm

Ø barra = 1/2 ''

Ø estribo = 3/8 ''b = 100.00 cmd = 40.91 cm

DISEÑO DE REFUERZO TRANSVERSAL

REFUERZO DENTRO DE LA ZONA DE CONFINAMIENTO

2d = 2.618 mØ estribo = 3/8 ''

La separacion de los estribos debe ser:S ≤ d/4 = 32.73 cm S = 30.00 cm □ Ø 3/8 '' @ 0.3

S ≤ 30.00 cm

REFUERZO FUERA DE LA ZONA DE CONFINAMIENTO

sadm Suelo =s diseño =

Se colocará refuerzo Transversal por confinamiento a una distancia "2d" medida desde la cara del apoyo.

Page 9: DISEÑO VIGAS CONTINUAS

La separacion de los estribos debe ser:S = 65.00 cm □ Ø 3/8 '' @ 0.65