8/14/2019 F-12 F225 GES-6103F
1/1
TIMEIN
SECONDS
GES-6103F
GES-6103F
10
20
30
40
50
60
70
8090
100
200
300
400
500
600
700800900
1000
98
7
6
5
4
3
2
.9
.8
.7
.6
.5
.4
.3
.2
.1
.09
.08
.07
.06
.05
.04
.03
.02
.01
1
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 108 9 20 30 40 50 60 70 8090
100
200
300
400
500
600
700
800
900
1000
125-250 A
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090100
200
300
400
500
600
700
800
900
1000
MULTIPLES OF CURRENT RATING
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090100
200
300
400
500
600
700
800
900
1000
75-110 A
125-250 A
TIMEIN
SECONDS
200
300
400
500
600
700
800900
1000
.01
.02
.03
.04
.05
.06
.07
.08
.09
.1
.2
.3
.4
.5
.6
.7
.8
.91
2
3
4
5
6
78
910
20
30
40
50
60
70
8090
100
.5
75-110 A
.6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090
100
200
300
400
500
600
700
800
900
1000
Shift index forlong-time delayonly.
Temp. 0 10-50 60
Magnetic Trip Setting Ranges
Trip Unit Setting (amps) Ampacity LO HI
70 600 900 80 700 1000 90 600 900 100 600 1250 110 660 1250 125 600 1250 150 700 1500 175 800 1750 200 900 2000 225 1000 2250 250 1000 2250
Range tolerance is 80-130% of setting.
ApplicationDeterminesEnd of Curve
HI MagneticSetting
Magnetic pickup levels shown forreference. Specific settings andtolerances shown in table above.
Ambient compensated. For ambientsabove 50 C and below 10 C, shiftthe unity index for long-time delay(thermal) portion of curve to desiredambient.
Maximum TotalClearing Time
Maximum TotalClearing Time
Minimum TotalClearing Time
Minimum TotalClearing Time
LO MagneticSetting
LO MagneticSetting
LO MagneticSetting
HI MagneticSetting
HI MagneticSetting
125, 150, 175,200, 225 & 250A
70 & 80 A
90 & 110 A
100 A
01.04
Current Ratings70, 80, 90, 100, 110, 125, 150, 175,200, 225, 250 Amperes
Voltage Ratings600 Vac, 250 Vdc
Frequency Ratings50/60 Hertz
Molded-Case Circuit BreakerF 225 Line
Types TFJ, TFK, THFKAmbient CompensatedLong-Time Delay and InstantaneousTime-Current Curves
Curves show ambient-compensated circuit breaker inopen air, 10-50C, wired with conductors of correspondingrating, no prior load. For all other ambients, use rating shiftindex at top of sheet.
GE Consumer & Industrial -Electrical Distribution
AdjustmentsLong-time delay thermal trip: not adjustable.
Instantaneous magnetic trip: continuouslyadjustable, factory set on HI.Blocks show trip range at marked points oninstantaneous dials.
Note1: Operation above 60 Hertz and 50C mayrequire thermal and interrupting derating of the circuitbreaker. Refer to Selection and Application Manual.
GES-6103F