    1/1

    TIMEIN

    SECONDS

    GES-6103F

    GES-6103F

    10

    20

    30

    40

    50

    60

    70

    8090

    100

    200

    300

    400

    500

    600

    700800900

    1000

    98

    7

    6

    5

    4

    3

    2

    .9

    .8

    .7

    .6

    .5

    .4

    .3

    .2

    .1

    .09

    .08

    .07

    .06

    .05

    .04

    .03

    .02

    .01

    1

    .5 .6 .7 .8 .9 1 2 3 4 5 6 7 108 9 20 30 40 50 60 70 8090

    100

    200

    300

    400

    500

    600

    700

    800

    900

    1000

    125-250 A

    .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090100

    200

    300

    400

    500

    600

    700

    800

    900

    1000

    MULTIPLES OF CURRENT RATING

    .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090100

    200

    300

    400

    500

    600

    700

    800

    900

    1000

    75-110 A

    125-250 A

    TIMEIN

    SECONDS

    200

    300

    400

    500

    600

    700

    800900

    1000

    .01

    .02

    .03

    .04

    .05

    .06

    .07

    .08

    .09

    .1

    .2

    .3

    .4

    .5

    .6

    .7

    .8

    .91

    2

    3

    4

    5

    6

    78

    910

    20

    30

    40

    50

    60

    70

    8090

    100

    .5

    75-110 A

    .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090

    100

    200

    300

    400

    500

    600

    700

    800

    900

    1000

    Shift index forlong-time delayonly.

    Temp. 0 10-50 60

    Magnetic Trip Setting Ranges

    Trip Unit Setting (amps) Ampacity LO HI

    70 600 900 80 700 1000 90 600 900 100 600 1250 110 660 1250 125 600 1250 150 700 1500 175 800 1750 200 900 2000 225 1000 2250 250 1000 2250

    Range tolerance is 80-130% of setting.

    ApplicationDeterminesEnd of Curve

    HI MagneticSetting

    Magnetic pickup levels shown forreference. Specific settings andtolerances shown in table above.

    Ambient compensated. For ambientsabove 50 C and below 10 C, shiftthe unity index for long-time delay(thermal) portion of curve to desiredambient.

    Maximum TotalClearing Time

    Maximum TotalClearing Time

    Minimum TotalClearing Time

    Minimum TotalClearing Time

    LO MagneticSetting

    LO MagneticSetting

    LO MagneticSetting

    HI MagneticSetting

    HI MagneticSetting

    125, 150, 175,200, 225 & 250A

    70 & 80 A

    90 & 110 A

    100 A

    01.04

    Current Ratings70, 80, 90, 100, 110, 125, 150, 175,200, 225, 250 Amperes

    Voltage Ratings600 Vac, 250 Vdc

    Frequency Ratings50/60 Hertz

    Molded-Case Circuit BreakerF 225 Line

    Types TFJ, TFK, THFKAmbient CompensatedLong-Time Delay and InstantaneousTime-Current Curves

    Curves show ambient-compensated circuit breaker inopen air, 10-50C, wired with conductors of correspondingrating, no prior load. For all other ambients, use rating shiftindex at top of sheet.

    GE Consumer & Industrial -Electrical Distribution

    AdjustmentsLong-time delay thermal trip: not adjustable.

    Instantaneous magnetic trip: continuouslyadjustable, factory set on HI.Blocks show trip range at marked points oninstantaneous dials.

    Note1: Operation above 60 Hertz and 50C mayrequire thermal and interrupting derating of the circuitbreaker. Refer to Selection and Application Manual.

    GES-6103F