Hazen Williams
Citation preview
SISTEMA DE ABASTECIMIENTO DE AGUA DE ARRIBA HACIA ABAJO
Pmin(m) 3.5 de salida Conversione gal
hest.(m) 6.7 UHsup 110 Qsup 1.75 3.5
Lsalida(m) 17.5 UHprop 114 Qprop 1.782 gpm
Alim. I UHinf 120 Qinf 1.83 1
Alim. II
Alim. III
Alim. IV
Smax(m/m) 0.152380952
Tramo AC Tramo CD
Q(lps) 1.78 Q(lps) 0.85
L(m) 4 Leq(m) 4.8 L(m) 6 Leq(m) 7.2
C 140 PVC C 140 PVC
φ(in) 1.5 φ(in) 1.25
K 0.0004266 K 0.0004266
S(m/Km) 74.55933825 S(m/Km) 46.099647
Hac(m) 0.357884824 Hac(m) 0.3319175
Pc(m) 3.642115176 ok! Pc(m) 3.3101977 error
lt
0.2205
lt/s
3.985
Tramo DG Tramo GH
Q(lps) 0.85 Q(lps) 0.61
L(m) 2.7 Leq(m) 3.24 L(m) 5 Leq(m) 6
C 140 PVC C 140 PVC
φ(in) 1.25 φ(in) 1
K 0.0004266 K 0.0004266
S(m/Km) 46.099647 S(m/Km) 73.935601
Hac(m) 0.1493629 Hac(m) 0.4436136
Pc(m) 5.8608349 ok! Pc(m) 5.4172213 ok!