MEMORIA DE CALCULO AC COM CÁLC DE FAN-COIL

Embed Size (px)

Citation preview

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    1/271

    MEMORIA 1

    DOCUMENTO N 1, MEMORIA.

    NDICE GENERAL:

    1.1 MEMORIA DESCRIPTIVA...2

    1.2 CLCULOS... 22

    1.3 ANEJOS.122

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    2/271

    MEMORIA 2

    1.1 MEMORIA DESCRIPTIVA.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    3/271

    MEMORIA 3

    1.1 MEMORIA DESCRIPTIVA.

    NDICE:

    1.1 MEMORIA DESCRIPTIVA5

    1.1.1 OBJETO DEL PROYECTO.5

    1.1.2 DESCRIPCIN DEL EDIFICIO........ 5

    1.1.3 DATOS DE PARTIDA. 6

    1.1.3.1 CONDICIONES EXTERNAS.. 6

    1.1.3.2 CONDICIONES INTERNAS... 6

    1.1.3.3 CARACTERSTICAS CONSTRUCTIVAS7

    1.1.3.4 CONDICIONES DE USO..8

    1.1.3.5 NIVELES DE VENTILACIN..10

    1.1.4 CLCULO DE CARGAS ..11

    1.1.4.2 CLCULO DE CARGAS DE VFRANO.......11

    1.1.5 DISEO DE EQUIPOS...11

    1.1.5.1 DISEO DE FAN COILS........12

    1.1.5.2 DISEO DE CLIMATIZADORES........13

    1.1.5.3 DISEO DE CLIMATIZADORES DE AIRE EXTERIOR........13

    1.1.5.4 DISEO DE CONDUCTOS.......14

    1.1.5.5 DIFUSORES15

    1.1.5.6 DISEO DE REJILLAS15

    1.1.5.7 DISEO DE LOS VENTILADORES...16

    1.1.5.8 DISEO DE TUBERAS. .17

    1.1.5.9 DISEO DE LAS BOMBAS.18

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    4/271

    MEMORIA 4

    1.1.5.10 DISEO DE LA CALDERA.. 19

    1.1.5.11 DISEO DEL EQUIPO REFRIGERADOR.19

    1.1.5.12 DISEO DE ELEMENTOS AUXILIARES..19

    1.1.6 BIBLIOGRAFA21

    1.1.7 COSTE TOTAL DE LA INSTALACIN...21

    1.1 MEMORIA DESCRIPTIVA.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    5/271

    MEMORIA 5

    1.1.1 OBJETO DEL PROYECTO.

    El objeto de este proyecto consiste en la climatizacin de un aeropuerto situado en

    Talavera de la Reina. Para lo cual desarrollaremos a lo largo del mismo las

    condiciones tcnicas y legales a las que debern ajustarse las instalaciones de

    climatizacin de dicho aeropuerto. Cumpliendo el Apndice 07.1 del Reglamento de

    Instalaciones Trmicas de los Edificios, adems de todos los captulos de la RITE,

    con su contenido simplificado y ajustado al tipo de instalacin.

    Las instalaciones a desarrollar comprendern la totalidad de los sistemas de

    refrigeracin y calefaccin necesarios durante todos los das del ao para una

    instalacin de las caractersticas de un aeropuerto.

    1.1.2 DESCRIPCIN DEL EDIFICIO.

    El edificio es un aeropuerto situado en la provincia de Toledo en el lmite con la de

    Madrid, con una superficie a climatizar aproximadamente de 70000 m2. Dicho

    aeropuerto consta de dos plantas situadas a diferentes cotas:

    Una primera planta 0,00 m.: no acondicionada en la que se sitan

    principalmente zonas de almacenamientos, salas de mquinas y cintas para

    transporte de equipaje desde facturacin a los aviones..

    Una segunda planta +5,00 m.: planta acondicionada en la que se centra el

    desarrollo del proyecto. En est planta se encuentran las zonas: Vestbulo de

    entrada, facturacin, equipaje, polica, prensa, zonas comerciales, zonas de

    oficinas y zonas de trnsito.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    6/271

    MEMORIA 6

    1.1.3 DATOS DE PARTIDA.

    1.1.3.1 CONDICIONES EXTERNAS.

    Los valores adoptados como condiciones exteriores de clculo de este proyecto se

    han obtenido de manual CARRIER para la provincia de Madrid dada la situacin del

    aeropuerto y son:

    Altitud: 667 m.

    Latitud: 40 25

    - Condiciones normales de verano: percentil del 95% a las 15 horas solares del

    mes de Julio:

    Temperatura seca: 34 C.

    Temperatura hmeda: 30,1 C

    Variacin diurna: 15

    - Condiciones de invierno:

    Temperatura seca: -3 C

    Temperatura hmeda: - 0,9 C

    1.1.3.2 CONDICIONES INTERNAS.

    Condiciones de verano:

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    7/271

    MEMORIA 7

    Para lograr el bienestar trmico, se aplicar la norma ITE 02.2 sobre condiciones

    interiores, por lo que se tendr en cuenta la norma UNE-EN ISO 7730, en la que se

    determina que la temperatura interior para condiciones de verano deber estar entre

    23 y 25 C. Las condiciones de los diferentes locales para la planta +5,00 m sern,

    considerndose en todos los casos una humedad relativa del 50 %:

    Vestbulo de entrada: 25 1C

    Facturacin: 25 1C

    Zonas de trnsito: 25 1C

    Equipajes: 25 1C

    Zonas de oficinas: 24 1C

    Zonas comerciales: 25 1C

    Condiciones de invierno:

    Las condiciones establecidas para lograr el bienestar trmico en cada uno de los

    locales a climatizar en invierno sern los siguientes, considerando para todos los

    casos una humedad relativa del 50%:

    Vestbulo de entrada: 22 1C

    Facturacin: 22 1C

    Zonas de trnsito: 22 1C

    Equipajes: 22 1C

    Zonas de oficinas: 22 1C

    Zonas comerciales: 22 1C

    1.1.3.3 CARACTERSTICAS CONSTRUCTIVAS.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    8/271

    MEMORIA 8

    Los coeficientes K de transmisin han sido calculados siguiendo lo especificado en

    la norma NBE-CT-79. De esta forma los valores dados para el clculo de nuestro

    proyecto han sido los siguientes:

    - Cristales (F.G.S): 0,48

    - Cristales (K): 2,6 W/m2.C.

    - Muros exteriores (K): 1,45 W/m2.C.

    - Tabiques LNA (K): 1,69 W/m2.C.

    - Tejados (K): 0,63 W/m2.C.

    - Suelos interiores (K): 1,07 W/m2.C.

    - Suelos exteriores (K): 0,63 W/m2.C.

    - Techos LNA (K): 1,07 W/m2.C.

    - Puertas (K): 2 W/m2.C.

    1.1.3.4 CONDICIONES DE USO.

    Niveles de ocupacin:

    Se han considerado los siguientes niveles de ocupacin para los distintos locales de

    la cota +5,00 m.:

    Vestbulo de entrada: 4 m2/persona

    Facturacin: 4 m2/persona

    Zonas de trnstito: 10 m2/persona

    Equipajes: 4 m2/persona

    Zonas de oficinas: 7-10 m2/persona

    Zonas comerciales: 7 m2/persona

    Niveles de actividad considerados:

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    9/271

    MEMORIA 9

    Los niveles de actividad considerados para el clculo de cargas sern los sigueientes:

    Carga sensible:

    Vestbulo de entrada: 70,7 W/persona

    Facturacin: 70,7 W/persona

    Zonas de trnsito: 70,7 W/persona

    Equipajes: 70,7 W/persona

    Zonas de oficinas: 70,7 W/persona

    Zonas comerciales: 70,7 W/persona

    Carga latente:

    Hall de entrada: 68,12 W/persona

    Facturacin: 68,12 W/persona

    Zonas de paso: 68,12 W/persona

    Equipajes: 68,12 W/persona

    Zonas de oficinas: 68,12 W/persona

    Zonas comerciales: 68,12 W/persona

    Cargas elctricas:

    Las cargas elctricas consideradas para el clculo de cargas son las siguientes:

    - Vestbulo de entrada:

    Iluminacin: 20 W/m2.

    Sealtica y monitores: 3 W/m2.

    - Facturacin:

    Iluminacin: 20 W/m2.

    Sealtica y monitores: 3 W/m2.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    10/271

    MEMORIA 10

    - Zonas de trnsito:

    Iluminacin: 20 W/m2

    .

    Sealtica y monitores: 3 W/m2.

    - Equipajes:

    Iluminacin: 20 W/m2.

    Sealtica y monitores: 3 W/m2.

    - Zonas de oficinas:

    Iluminacin: 20 W/m2.

    Cargas elctricas: 20 W/m2.

    - Zonas comerciales:

    Iluminacin: 20 W/m2.

    Cargas elctricas: 20 W/m2.

    1.1.3.5 NIVELES DE VENTILACIN.

    Siguiendo las especificaciones indicadas en la norma UNE se han establecido los

    siguientes niveles de ventilacin:

    Vestbulo de entrada: 10 l/s persona.

    Facturacin: 10 l/s persona.

    Zonas de trnsito: 10 l/s persona.

    Equipajes: 10 l/s persona.

    Zonas de oficinas: 10 l/s persona.

    Zonas comerciales: 10 l/s persona.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    11/271

    MEMORIA 11

    1.1.4 CLCULO DE CARGAS.

    1.1.4.1 CLCULO DE CARGAS DE INVIERNO.

    Con las condiciones exteriores para invierno fijadas en el apartado 1.1.3.1 se ha

    procedido al clculo de las necesidades trmicas de cada una de las zonas del

    aeropuerto.

    En este clculo solo se ha considerado la transmisin en los muros, ya que tanto la

    radiacin, iluminacin y equipos y ocupacin son favorables en invierno, por lo que

    ayudaran en la calefaccin de nuestro local y no han de ser tenidas en cuenta. Los

    locales tendrn una sobrepresin, por lo que la infiltracin no ser tenida en cuenta.

    Se asegura de este modo que en las condiciones ms desfavorables de proyecto, es

    decir cuando arranque el sistema antes de la jornada y an no haya ocupacin, ni

    estn encendidos los equipos, el equipo pueda responder a las necesidades del local

    que sern las indicadas anteriormente para cada uno de los locales.

    1.1.4.2 CLCULO DE LAS CARGAS DE VERANO.

    Para el clculo de las cargas de verano se realizar un clculo reiterativo para estimar

    la hora y el mes ms desfavorables para las condiciones de proyecto seleccionadas,

    en funcin de la orientacin de cada uno de los locales.

    De cada local se calcularn los valores de transmisin en muros, radiacin,

    iluminacin y equipos y ocupacin. Una vez ms la infiltracin no ser tenida en

    cuenta debido a la sobrepresin.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    12/271

    MEMORIA 12

    Se asegurar de este modo que los equipos podrn aportar las necesidades de

    refrigeracin dadas para cada local en las condiciones ms desfavorables de

    proyecto.

    1.1.5 DISEO DE EQUIPOS.

    1.1.5.1 DISEO DE FAN-COILS.

    Se han seleccionado Fan-Coils para cubrir las necesidades trmicas y frigorficas de

    varias oficinas y zonas comerciales. Los equipos seleccionados sern unidades

    verticales con mueble y unidades horizontales ocultas en el falso techo, los distintos

    modelos seleccionados del catlogo para cada uno de los locales sern expuestos en

    el apartado de clculos.

    En ningn caso ser necesario el empleo de glicol en tuberas. Los equipos podrn

    ser de dos tubos o cuatro tubos, en funcin de que locales tengan o no unas

    necesidades trmicas suficientes como para considerar utilizar tuberas para el agua

    caliente de calefaccin.

    El criterio de seleccin de los equipos ha sido realizado mediante el clculo del

    aporte de agua necesario para que puedan hacer frente a las cargas latente y sensible

    de verano y a la carga total de calefaccin en invierno. Cumpliendo con niveles de

    ruido permitidos.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    13/271

    MEMORIA 13

    1.1.5.2 DISEO DE LOS CLIMATIZADORES.

    Se han seleccionado climatizadores para cumplir las necesidades del vestbulo de

    entrada, facturacin, equipaje, y aquellas oficinas y zonas comerciales cuyas

    dimensiones exigen la colocacin de un climatizador.

    La seleccin de climatizadores se ha realizado calculando las potencias necesarias de

    refrigeracin y calefaccin. El punto de impulsin se ha fijado en un intervalo de

    13,5 a 14,5 C, mediante el empleo del diagrama psicromtrico y las condiciones

    externas e internas del edificio se han calculado las potencias de los equipos. Una vez

    conocidas las potencias y fijados los caudales de impulsin, ventilacin y retorno se

    ha seleccionado el equipo mediante un programa de un TROX. Para la temperatura

    de impulsin fijada no ser necesario el empelo de glicol en las tuberas.

    Cada equipo estar compuesto por una batera de fro, una batera de calor, un

    ventilador de impulsin, un ventilador de retorno, dos filtros G4 y F8 segn UNE EN

    779 y tres compuertas, una para expulsar aire al exterior, una segunda compuerta

    para recircular aire de la habitacin y una tercera para tomar aire del exterior.

    1.1.5.3 DISEO DE LOS CLIMATIZADORES DE AIRE EXTERIOR.

    En aquellos locales en los que se ha dispuesto un Fan Coil ser necesario el

    climatizador de aire exterior. Este climatizador se disea para varios locales, siendo

    el caudal de impulsin el mismo que el de ventilacin de cada local.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    14/271

    MEMORIA 14

    El climatizador no contar con un ventilador de retorno por lo que no existir el

    punto de mezcla, las condiciones a las que llega el aire a las bateras son las del

    exterior. El climatizador impulsar durante todo el ao el aire a 22C.

    Este aire de ventilacin se llevar hasta el falso techo lo ms cerca posible del Fan

    Coil. Se realizar una extraccin de todos aquellos locales a los que impulsa aire el

    climatizador de aire exterior, dicha extraccin ser del 80% del caudal de ventilacin

    para cada local.

    Los elementos que componen principalmente el climatizador son: la batera de fro,

    la batera de calor, el ventilador de impulsin, dos filtros G4 y F8 segn UNE EN

    779 y la compuerta para el aire exterior de ventilacin.

    1.1.5.4 DISEO DE CONDUCTOS.

    Los conductos empleados para la climatizacin sern rectangulares, el material

    empleado ser acero galvanizado.

    Como criterio para la seleccin de los conductos necesarios, tanto para la impulsin

    como para retorno, es que la velocidad no ser superior en ningn caso a los 10m/s y

    la prdida de carga por metro lineal de conductos no podr superar los 1,2 Pa/m.

    Para los climatizadores se trabajar siempre a baja velocidad, mientras que en los

    Fan-Coils emplearemos media velocidad.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    15/271

    MEMORIA 15

    1.1.5.5 DIFUSORES.

    Los difusores empleados sern de la serie ADLQ 250-300-400-500-600, los diversos

    tamaos sern en funcin de los caudales de impulsin calculados para las

    necesidades de cada local.

    Como criterio los difusores estarn distribuidos siempre de la forma ms simtrica

    posible en nuestro local.

    1.1.5.6 DISEO DE REJILLAS.

    Las rejillas son las encargadas de permitir retornar el aire desde el local. El modelo

    de rejillas seleccionas son AT, de lamas mviles regulables individualmente, con un

    rango de caudales de 100 a 6000 m3

    /h. El nmero de rejillas necesario para cada

    local vendr dado en funcin del caudal de retorno y el tamao seleccionado para la

    rejilla en cada caso.

    Su disposicin en el local no tiene porque ser simtrica por lo que se dispondr de la

    forma ms conveniente para poder retornar el aire hasta el climatizador o en su caso

    al Fan Coil, en el caso de los Fan Coils la mejor disposicin de est ser justo debajo

    del equipo.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    16/271

    MEMORIA 16

    1.1.5.7 DISEO DE LOS VENTILADORES.

    Tanto el ventilador de impulsin como el de retorno tendr suficiente para vencer la

    prdida de carga que se producirn en los conductos, habr que tener en cuenta

    tambin la perdida que se produce en los difusores y rejillas.

    El ventilador de impulsin se disea teniendo en cuenta el caudal de impulsin al

    local y la prdida de carga que se produce el conducto de impulsin desde el

    climatizador al difusor ms alejado de este.

    El ventilador de retorno se disea teniendo en cuenta el caudal extraccin, que ser la

    suma de los caudales de expulsin y de retorno, y considerando la mayor prdida de

    carga que se produce en el conducto desde la rejilla ms alejada al climatizador.

    Los ventiladores de extraccin se han diseado para aquellos locales que tenemos

    climatizador de aire exterior y Fan Coils, dependern del caudal de extraccin y de la

    prdida de carga que se produce en el conducto desde la rejilla ms alejada al

    ventilador.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    17/271

    MEMORIA 17

    1.1.5.8 DISEO DE TUBERAS.

    Se realizarn dos circuitos cerrados de tuberas independientes, uno para los

    climatizadores y otro para los Fan-Coil, cada uno a su vez con dos circuitos

    independiente de tuberas para la batera de fro y para la batera de calor.

    En el sistema de tuberas de los Fan-Coil, tendremos las siguientes temperaturas:

    Calefaccin:

    Temperatura de entrada del agua 50 C.

    Incremento de temperatura en el agua 5 C.

    Refrigeracin:

    Temperatura de entrada del agua 7 C.

    Incremento de temperatura en el agua 5 C.

    Los Fan-Coil sern de cuatro tubos, en algunos casos el sistema de calefaccin no

    ser necesario.

    En el sistema de tuberas empleado para los climatizadores, los valores de

    temperaturas considerados sern los siguientes:

    Batera de agua fra:

    Temperatura de entrada del agua: 7 C.

    Temperatura de salida del agua: 14 C.

    Batera de agua caliente:

    Temperatura de entrada del agua: 85 C.

    Temperatura de salida del agua: 65 C.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    18/271

    MEMORIA 18

    La regulacin del caudal de entrada a los Fan-Coil se realizar mediante vlvulas de

    tres vas, que nos permitirn el paso de una mayor o menor caudal a nuestro equipo

    en funcin de las necesidades de refrigeracin y trmicas en nuestro local

    dependiendo de los distintos valores de cargas que se puedan dar en las diferentes

    horas del da.

    Los criterios de seleccin para las tuberas sern que la velocidad nunca sea superior

    a 2,1 m/s y que la prdida de carga mxima permitida por metro lineal de tubera ser

    de 25 mm.c.a.

    El material empleado ser acero negro no galvanizado.

    1.1.5.9 DISEO DE LAS BOMBAS.

    Las bombas se han diseado para cada uno de los cuatro circuitos de la instalacin.

    Para los Fan Coils y climatizadores se han considerado los caudales necesarios para

    los circuitos de fro y de calor.

    Las bombas se han diseado considerando la mayor prdida de carga que se produce

    en los circuitos de tuberas, y que se producir desde la batera del Fan Coil o del

    climatizador ms alejada hasta la bomba.

    En total se han dispuesto cuatro bombas, para circuito de fro y circuito de calor de

    Fan Coils y para circuito de fro y circuito de calor de climatizadores.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    19/271

    MEMORIA 19

    1.1.5.10 DISEO DE LA CALDERA.

    La caldera se disear en funcin de las necesidades de calefaccin de los

    climatizadores y de los Fan-Coils.

    La potencia de la caldera ser suficiente para cubrir las necesidades de calefaccin

    del aeropuerto. En total se han seleccionado cuatro calderas, de forma que tres de

    ellas estarn operativas y una permanecer parada. Las calderas se irn alternando en

    su funcionamiento, la caldera parada nos permitir un margen de seguridad ante

    posibles averas o demandas ms altas de la instalacin.

    Las cuatro calderas sern de modelo EUROBLOC-SUPEREX 1.627..

    1.1.5.11 DISEO DEL EQUIPO REFRIGERADOR.

    El equipo de refrigeracin se disear funcin de las necesidades de refrigeracin de

    los climatizadores y Fan Coils. Se ha considerado la potencia total de refrigeracin

    de los equipos y el caudal de agua necesario para la batera de fro de los mismos.

    En total se han seleccionado seis enfriadoras de agua de condensacin por aire de la

    marca Carrier del modelo 30 XA 1702 situadas en la cubierta del edificio

    1.1.5.12 DISEO DE ELEMENTOS AUXILIARES.

    Compuerta cortafuegos:

    En aquellas zonas que sean de seguridad en caso de incendio y estn atravesadas por

    conductos de impulsin o retorno del aire se dispondr de compuertas cortafuegos.

    Vlvulas de interrupcin y regulacin:

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    20/271

    MEMORIA 20

    En todos los Fan Coils, climatizadores, equipos de refrigeracin, calderas y bombas

    se dispondrn de vlvulas de interrupcin y regulacin, que nos permitirn regular el

    caudal necesario que debe pasar por la tubera hasta la batera de fro o de calor del

    equipo. Ests vlvulas vendrn con sistema de memorizacin mecnica de posicin.

    Vlvulas de corte:

    Sern necesarias para todos los equipos disponer de vlvulas de corte. Se dispondrn

    vlvulas de bola para tuberas menores de DN50 y vlvulas de mariposa para tuberas

    mayores de DN65.

    Vlvulas de control:

    La regulacin del caudal necesario en cada momento en las bateras de los Fan-Coils

    y climatizadores se realizar mediante el empleo de vlvulas de tres vas.

    Filtros:

    En todos los equipos ser necesario disponer de filtros para asegurar la limpieza del

    agua del sistema.

    Equipos de medida:

    Para el sistema de tuberas ser necesario disponer de equipos de medida que nos

    permitan conocer el caudal y la temperatura del agua en todo momento, para lo que

    ser necesario disponer de termmetros y manmetros diferenciales en todos los

    equipos.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    21/271

    MEMORIA 21

    1.1.6 BIBLIOGRAFA.

    [CARR03] Manual de aire acondicionado, Autor: Carrier. Editorial:

    MARCOMBO, S.A. [2003].

    Catlogo Fan-Coil de CARRIER.

    Catlogo Climatizadores de TROX.

    Catlogo de difusores y rejillas de TROX.

    Catlogo de bombas de GRUNDFOS.

    Catlogo de enfriadoras de agua de CARRIER.

    Catlogo de calderas de VULCANO-SADECA.

    1.1.7 COSTE TOTAL DE LA INSTALACIN.

    El coste total de nuestra instalacin de climatizacin para el aeropuerto ser de

    2.960.975 .

    Madrid, 22 de junio de 2008

    JAVIER ARIAS ORTIZ

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    22/271

    MEMORIA 22

    1.2 CLCULOS.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    23/271

    MEMORIA 23

    1.2 CLCULOS.NDICE:

    1.2 CLCULOS....................................................................................................25

    1.2.1 CLCULO DE CARGAS........................................................................25

    1.2.1.1 CLCULO DE CARGAS DE VERANO. ........................................25

    1.2.1.1.1 TRANSMISIN..........................................................................25

    1.2.1.1.2 RADIACIN SOLAR. ...............................................................27

    1.2.1.1.3 INTERNAS. ................................................................................27

    1.2.1.1.4 INFILTRACIONES....................................................................29

    1.2.1.1.5 CARGA SENSIBLE Y CARGA LATENTE. ............................ 29

    1.2.1.1.6 RESULTADOS. ..........................................................................29

    1.2.1.2 CLCULO DE PRDIDAS EN INVIERNO...................................32

    1.2.1.2.1 TRANSMISIN EN MUROS Y TECHOS. ..............................33

    1.2.1.2.2 TRANSMISIN EN CRISTALES.............................................33

    1.2.1.2.3 TRANSMISIN EN PARTICIONES........................................33

    1.2.1.2.4 INFILTACIONES. .....................................................................34

    1.2.1.2.5 RESULTADOS. ..........................................................................34

    1.2.1.3 RESULTADOS FINALES. ...............................................................37

    1.2.2 CLCULO DE CAUDALES DE VENTILACIN. ...............................42

    1.2.3 CLCULO DE EQUIPOS.......................................................................47

    1.2.3.1 CLCULO DE CLIMATIZADORES.............................................47

    1.2.3.2 CLCULO DE CLIMATIZADORES DE AIRE PRIMARIO. ......63

    1.2.3.4 DIFUSORES......................................................................................74

    1.2.3.8 TUBERAS. .....................................................................................115

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    24/271

    MEMORIA 24

    1.2.3.9 SELECCIN DE LAS BOMAS. ....................................................118

    1.2.3.10 SELECCIN DE LA CALDERA.................................................120

    1.2.3.11 SELECCIN DEL EQUIPO DE REFRIGERACIN................121

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    25/271

    MEMORIA 25

    1.2 CLCULOS.

    1.2.1 CLCULO DE CARGAS.

    Para el clculo de cargas hemos dividido el aeropuerto en diversas zonas numeradas,

    para las que especificaremos su ocupacin y superficie.

    1.2.1.1 CLCULO DE CARGAS DE VERANO.

    Para el clculo de las cargas de verano tendremos en cuenta los siguientes puntos:

    Transmisin.

    Radiacin solar.

    Internas.

    Infiltraciones.

    1.2.1.1.1 TRANSMISIN.

    El clculo de la transmisin se divide en los siguientes apartados:

    Transmisin en muros y techos:

    La transmisin que se produce en el muro ha sido calculada mediante la siguiente

    frmula:

    eqmuro

    TSKT =

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    26/271

    MEMORIA 26

    Siendo la expresin para el clculo de la temperatura equivalente:

    )( esemm

    a

    eseq ttRRbtaT ++=

    Donde:

    a: factor de correccin.

    est : diferencia equivalente de temperatura a la hora considerada para la pared a la

    sombra.

    emt : diferencia equivalente de temperatura a la hora considerada para la pared

    soleada.

    b: coeficiente que considera el color de la cara exterior de la pared.

    aR : mxima insolacin correspondiente al mes y latitud supuestos, a travs de una

    superficie acristalada vertical u horizontal para la orientacin considerada.

    mR : mxima insolacin en el mes de Julio, a 40 de latitud Norte, a travs de una

    superficie acristalada vertical u horizontal para la orientacin considerada.

    Transmisin en cristales:

    La transmisin en el cristal viene dad por la siguiente expresin:

    )( intTTSKT extcristalcristal =

    Transmisin en particiones:

    Se consideran particiones aquellos locales que no estn acondicionados y para los

    que su temperatura se supone la mitad del incremento de temperatura que se produce

    entre el exterior y el interior.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    27/271

    MEMORIA 27

    2

    )( intTTSKT extLNCParticin

    =

    1.2.1.1.2 RADIACIN SOLAR.

    El clculo de la radiacin solar vendr afectado por la orientacin del local

    considerado y por la hora y mes a la que se realiza dicho clculo. Para asegurar que

    nuestro local puede ser climatizado, an en las peores condiciones de proyecto, se ha

    considerado para la elaboracin del clculo de la radiacin la hora y mes ms

    desfavorables. La obtencin de la hora y el mes ms desfavorables se ha realizado

    para cada local, repitiendo el clculo mediante hojas Excel hasta obtener un mximo

    de radiacin.

    La formula empleada para el clculo de la radiacin:

    ... SGFGSRadiacin cristal =

    Siendo:

    cristalS : la superficie de cristal del local considerado.

    G : la ganancia solar en el cristal.

    F.G.S. : factor de ganancia solar.

    1.2.1.1.3 INTERNAS.

    El valor de la carga interna de pender de la iluminacin, equipos y ocupacin que se

    den el local considerado, por lo que dividimos el clculo en los siguientes apartados:

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    28/271

    MEMORIA 28

    Iluminacin:

    La carga de iluminacin depender de los valores de iluminacin especificados para

    cada local. Una vez conocida la superficie del local considerado el resultado de carga

    de iluminacin se obtiene:

    .arg)()(min 22

    mWacmSWacinIlu =

    Equipos:

    La carga generada por lo equipos depender de los valores considerados para cada

    local en funcin de la zona del aeropuerto. El valor de dicha carga vendr dado de

    esta forma:

    .arg)()( 22

    mWacmSWEquipos =

    Ocupacin:

    En funcin de los valores para los niveles de actividad realizados para cada zona del

    aeropuerto y de la ocupacin considerada podremos calcular los diferentes valores de

    carga sensible y de carga latente.

    .arg)(

    = personaWacocupantesnWC sensiblesensible

    .arg)(

    =persona

    WacocupantesnWC latentelatente

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    29/271

    MEMORIA 29

    1.2.1.1.4 INFILTRACIONES.

    Debido a la sobrepresin que producimos en los locales el valor de las infiltraciones

    ser nulo para todos los locales considerados.

    1.2.1.1.5 CARGA SENSIBLE Y CARGA LATENTE.

    Una vez realizado el clculo de los apartados anteriores podemos obtener los valores

    de carga sensible y carga latente total de nuestro local.

    Siendo la carga sensible total de local la suma de los valores obtenidos para la

    transmisin, en muros, cristales y ventanas, la radiacin producida en los cristales, y

    las cargas internas, tanto de iluminacin, equipos y ocupacin sensible del local.

    El valor de la carga latente vendr dado en funcin nicamente de la ocupacin.

    latenteL CC =

    1.2.1.1.6 RESULTADOS.

    En las siguientes tablas se muestra un resumen de los valores de transmisin,

    radiacin, iluminacin y equipos, carga sensible y carga latente obtenidos para cada

    uno de los locales a climatizar.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    30/271

    MEMORIA 30

    Transmisin

    Zonamuro y

    techo (W)cristales

    (W)particiones

    (W)radiacin

    (W)

    iluminacin

    y equipos(W)

    cargasensible (W)

    carga

    latente(W)

    H1.01 545 0 221 0 487 164 158

    H1.02 0 0 1060 0 2341 658 634

    H1.03 0 0 1060 0 2341 658 634

    H1.04 0 0 698 0 1538 575 554

    H1.05 0 0 740 0 1630 493 475

    H1.06 0 0 809 0 1788 575 554

    H1.07 0 0 881 0 1943 658 634

    H1.08 0 0 363 0 799 247 238

    H1.09 0 0 300 0 664 247 238

    H1.10 0 0 335 0 740 247 238H1.11 0 0 388 0 857 329 317

    H1.12 0 0 388 0 857 329 317

    H1.13 0 0 391 0 862 329 317

    H1.14 0 0 391 0 862 329 317

    H1.15 0 0 667 0 1473 575 554

    H1.16 0 0 2567 0 5663 1644 1584

    H1.17 0 0 812 0 1792 658 634

    H1.18 0 0 188 0 414 164 158

    H1.19 0 0 207 0 458 164 158

    H1.20 0 0 528 0 1164 493 475

    H1.22 0 0 472 0 1043 329 317H1.23 3799 0 3893 0 9127 3864 3723

    H1.24 192 0 547 0 1207 493 475

    H1.25 0 0 414 0 914 411 396

    H1.26 0 0 2479 0 5470 2302 2218

    H1.27 185 0 1186 0 2618 1069 1030

    H1.28 6459 0 9760 0 21538 6330 6099

    H1.29 2244 0 2207 0 5173 1480 1426

    H1.30 2609 0 8067 0 17798 5261 5069

    H1.31 0 0 5630 0 12425 3617 3485

    H1.32 0 0 1700 0 3752 1069 1030

    H1.33 0 0 719 0 1585 493 475

    H1.34 0 0 1472 0 3248 1151 1109

    H1.35 0 0 486 0 1074 411 396

    H1.36 0 0 4686 0 10338 3042 2931

    H1.37 0 0 11777 0 25985 7645 7366

    H2.01 0 0 3105 0 6850 2877 2772

    H2.02 0 0 4079 0 8999 2960 2852

    H2.03 0 0 698 0 1538 493 475

    H2.04 0 0 981 0 2166 740 713

    H2.05 0 0 530 0 1169 411 396

    H2.06 0 0 226 0 497 164 158

    H2.07 0 0 149 0 328 82 79

    H2.08 0 0 216 0 476 164 158H2.09 0 0 226 0 497 164 158

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    31/271

    MEMORIA 31

    H2.10 0 0 198 0 434 164 158

    H2.11 0 0 107 0 234 82 79

    H2.12 0 0 516 0 1140 411 396H2.13 0 0 886 0 1956 740 713

    H2.14 0 0 698 0 1538 575 554

    H2.15 0 0 214 0 469 164 158

    H2.16 0 0 419 0 922 329 317

    H2.17 0 0 737 0 1625 575 554

    H2.18 0 0 698 0 1538 575 554

    H2.19 0 0 1819 0 4011 1315 1267

    H2.20 0 0 4709 0 10391 3782 3644

    H2.21 0 0 698 0 1538 575 554

    H2.22 0 0 2198 0 4847 3535 3406

    H2.23 0 0 416 0 920 329 317H2.24 0 0 765 0 1690 658 634

    H2.25 0 0 698 0 1538 575 554

    H2.26 0 0 10788 0 23804 9947 9584

    H3.01 0 0 8498 0 18749 7892 7604

    H3.02 0 0 8177 0 18041 7563 7287

    H3.03 0 0 698 0 1538 658 634

    H3.04 537 0 1521 0 3358 1233 1188

    H3.05 478 0 1356 0 2991 1069 1030

    H3.06 497 0 533 0 1249 493 475

    H3.07 0 0 435 0 962 329 317

    H3.08 0 0 442 0 973 329 317

    H3.09 0 0 558 0 1232 411 396

    H3.10 0 0 728 0 1606 575 554

    H3.11 0 0 472 0 1042 411 396

    H3.12 0 0 765 0 1690 493 475

    H3.13 0 0 663 0 1463 575 554

    H3.14 0 0 398 0 875 329 317

    H3.15 0 0 381 0 840 329 317

    H3.16 0 0 835 0 1844 658 634

    H3.18 0 0 781 0 1724 658 634

    H3.19 0 0 3453 0 7620 3699 3564

    H3.20 0 0 856 0 1887 658 634

    H3.21 0 0 856 0 1887 658 634H3.22 0 0 151 0 336 82 79

    H3.23 0 0 151 0 336 82 79

    H3.24 0 0 151 0 336 82 79

    H3.25 0 0 105 0 233 82 79

    H3.26 0 0 188 0 414 164 158

    H3.27 0 0 151 0 336 82 79

    H3.28 0 0 151 0 336 82 79

    H3.29 0 0 151 0 336 82 79

    H3.30 0 0 165 0 363 164 158

    H3.31 0 0 288 0 637 247 238

    H3.32 0 0 807 0 1779 658 634H3.33 0 0 495 0 1091 411 396

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    32/271

    MEMORIA 32

    H3.34 0 0 195 0 431 164 158

    H3.35 0 0 300 0 661 247 238

    H3.36 0 0 170 0 376 164 158H3.37 0 0 479 0 1057 329 317

    H3.38 0 0 440 0 970 329 317

    H3.39 0 0 419 0 924 329 317

    H3.40 0 0 353 0 783 247 238

    H3.41 0 0 516 0 1141 411 396

    H3.42 0 0 819 0 1807 493 475

    H3.43 0 0 188 0 414 82 79

    H3.44 0 0 247 0 542 164 158

    H3.45 0 0 442 0 973 329 317

    H3.46 0 0 442 0 973 329 317

    H3.47 0 0 714 0 1577 575 554H3.48 0 0 1958 0 4319 1562 1505

    H3.49 0 0 374 0 829 329 317

    H3.50 0 0 642 0 1418 493 475

    H3.51 0 0 1900 0 4190 1562 1505

    H3.52 0 0 812 0 1792 658 634

    H3.53 0 0 247 0 542 164 158

    H3.54 0 0 226 0 496 164 158

    H3.55 0 0 535 0 1183 411 396

    H3.56 0 0 630 0 1390 493 475

    H3.57 0 0 2544 0 5614 2055 1980

    1.2.1.2 CLCULO DE PRDIDAS EN INVIERNO.

    Para l clculo de las prdidas producidas solo se tendrn en cuentan los valores de

    transmisin, ya que tanto la radiacin como las cargas internas favorecen en

    invierno.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    33/271

    MEMORIA 33

    1.2.1.2.1 TRANSMISIN EN MUROS Y TECHOS.

    La transmisin que se produce en invierno en el muro viene dada por la siguiente

    expresin:

    )( int extmuromuromuro TTSKT =

    Siendo:

    intT : el valor de la temperatura interior del local considerado, y que ser la

    temperatura de confort que queremos obtener en el local. Dicho valor ser de 22 C

    para todas las zonas.

    extT : el valor de la temperatura exterior, 0 C para invierno en Jan.

    1.2.1.2.2 TRANSMISIN EN CRISTALES.

    La transmisin en el cristal viene dada por la siguiente expresin:

    )( int extcristalcristalcristal TTSKT =

    1.2.1.2.3 TRANSMISIN EN PARTICIONES.

    Se consideran particiones aquellos locales que no estn acondicionados y para los

    que su temperatura se supone la mitad del incremento de temperatura que se produce

    entre el interior y el exterior.

    2

    )( int extLNCParticin

    TTSKT

    =

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    34/271

    MEMORIA 34

    1.2.1.2.4 INFILTRACIONES.

    Debido a la sobrepresin no se considerarn infiltraciones en invierno.

    1.2.1.2.5 RESULTADOS.

    En las siguientes tablas se muestran los valores obtenidos para las cargas de invierno,

    para este caso, como se ha especificado anteriormente, solo se tomarn los valores de

    transmisin de nuestro local. Para cada uno de los locales se resumen los valores

    obtenidos por transmisin en muros y techos, cristales y particiones.

    Transmisin

    Zona muro ytecho (W)

    cristales(W)

    particiones(W)

    H1.01 710 0 553

    H1.02 0 0 2663

    H1.03 0 0 2663

    H1.04 0 0 1749

    H1.05 0 0 1853

    H1.06 0 0 2035

    H1.07 0 0 2212

    H1.08 0 0 909

    H1.09 0 0 756H1.10 0 0 842

    H1.11 0 0 974

    H1.12 0 0 974

    H1.13 0 0 981

    H1.14 0 0 981

    H1.15 0 0 1677

    H1.16 0 0 6444

    H1.17 0 0 2040

    H1.18 0 0 470

    H1.19 0 0 521

    H1.20 0 0 1323H1.22 0 0 1186

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    35/271

    MEMORIA 35

    H1.23 5753 0 10386

    H1.24 680 0 1372

    H1.25 0 0 1042H1.26 0 0 6223

    H1.27 656 0 2979

    H1.28 8842 0 24507

    H1.29 2212 0 5886

    H1.30 3017 0 20251

    H1.31 0 0 14137

    H1.32 0 0 4270

    H1.33 0 0 1805

    H1.34 0 0 3695

    H1.35 0 0 1223

    H1.36 0 0 11763H1.37 0 0 29567

    H2.01 0 0 7795

    H2.02 0 0 10240

    H2.03 0 0 1749

    H2.04 0 0 2465

    H2.05 0 0 1330

    H2.06 0 0 565

    H2.07 0 0 374

    H2.08 0 0 542

    H2.09 0 0 565

    H2.10 0 0 493

    H2.11 0 0 267

    H2.12 0 0 1298

    H2.13 0 0 2226

    H2.14 0 0 1749

    H2.15 0 0 535

    H2.16 0 0 1049

    H2.17 0 0 1849

    H2.18 0 0 1749

    H2.19 0 0 4565

    H2.20 0 0 11823

    H2.21 0 0 1749

    H2.22 0 0 5516H2.23 0 0 1047

    H2.24 0 0 1923

    H2.25 0 0 1749

    H2.26 0 0 27086

    H3.01 0 0 21335

    H3.02 0 0 20528

    H3.03 0 0 1749

    H3.04 1902 0 3819

    H3.05 1695 0 3405

    H3.06 1607 0 1421

    H3.07 0 0 1093H3.08 0 0 1107

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    36/271

    MEMORIA 36

    H3.09 0 0 1402

    H3.10 0 0 1826

    H3.11 0 0 1186H3.12 0 0 1923

    H3.13 0 0 1665

    H3.14 0 0 995

    H3.15 0 0 956

    H3.16 0 0 2098

    H3.18 0 0 1960

    H3.19 0 0 8672

    H3.20 0 0 2147

    H3.21 0 0 2147

    H3.22 0 0 381

    H3.23 0 0 381H3.24 0 0 381

    H3.25 0 0 265

    H3.26 0 0 472

    H3.27 0 0 381

    H3.28 0 0 381

    H3.29 0 0 381

    H3.30 0 0 414

    H3.31 0 0 723

    H3.32 0 0 2023

    H3.33 0 0 1242

    H3.34 0 0 491

    H3.35 0 0 751

    H3.36 0 0 428

    H3.37 0 0 1202

    H3.38 0 0 1105

    H3.39 0 0 1051

    H3.40 0 0 891

    H3.41 0 0 1298

    H3.42 0 0 2056

    H3.43 0 0 472

    H3.44 0 0 616

    H3.45 0 0 1107

    H3.46 0 0 1107H3.47 0 0 1793

    H3.48 0 0 4914

    H3.49 0 0 942

    H3.50 0 0 1614

    H3.51 0 0 4767

    H3.52 0 0 2040

    H3.53 0 0 616

    H3.54 0 0 565

    H3.55 0 0 1347

    H3.56 0 0 1581

    H3.57 0 0 6388

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    37/271

    MEMORIA 37

    1.2.1.3 RESULTADOS FINALES.

    Finalmente podemos ver en las siguiente tabla los resultados finales para de las

    cargas de verano e invierno. Para verano se dan los valores de carga sensible y carga

    latente, as como las sumas de las dos. Para invierno se da el valor de la carga total.

    Para cada local se ha especificado la ocupacin, en nmero de personas, y la

    superficie en metros cuadrados.

    Verano Invierno

    Zona Ocup Sup.(m2) C.total(W) C.sensible(W) C.latente(W) C.total(W)

    H1.01 2 17,4 1776 1597 179 1553

    H1.02 4 43,6 3896 3540 356 3371

    H1.03 8 83,6 5286 4572 714 3272

    H1.04 7 54,9 3791 3166 625 2149

    H1.05 6 58,2 3760 3224 536 2278

    H1.06 7 63,9 4199 3574 625 2500

    H1.07 8 69,42 4636 3922 714 2717

    H1.08 3 28,52 1853 1586 267 1117H1.09 3 23,7 1631 1364 267 929

    H1.10 3 26,44 1757 1490 267 1035

    H1.11 4 30,58 2129 1773 356 1198

    H1.12 4 30,58 2129 1773 356 1198

    H1.13 4 30,8 2137 1781 356 1206

    H1.14 4 30,8 2137 1781 356 1206

    H1.15 7 52,61 3685 3060 625 2060

    H1.16 20 202,26 12905 11121 1784 7917

    H1.17 8 64,02 4387 3673 714 2506

    H1.18 2 14,78 1043 864 179 578

    H1.19 2 16,33 1113 934 179 641H1.20 6 41,53 2997 2461 536 1627

    H1.21 1 6,79 494 404 90 266

    H1.22 4 37,24 2434 2078 356 267

    H1.24 6 43,08 3317 2781 536 2522

    H1.25 5 32,67 2407 1960 447 1280

    H1.26 28 195,36 14044 11546 2498 7646

    H1.27 13 93,48 6891 5730 1161 4466

    H1.32 13 134 8506 7345 1161 5246

    H1.33 6 56,61 3853 3262 591 2384

    H1.34 14 115,98 7941 6692 1249 4658

    H1.35 5 38,37 2747 2300 447 1621

    H1.37 93 928,06 60637 51479 9158 36828

    H2.03 6 54,91 3609 3073 536 2149

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    38/271

    MEMORIA 38

    H2.04 9 77,35 5181 4378 803 3029

    H2.05 5 41,74 2937 2490 447 1800

    H2.06 2 17,73 1256 1077 179 808H2.07 1 11,72 796 706 90 573

    H2.08 2 17,01 1222 1043 179 779

    H2.09 2 17,73 1256 1077 179 808

    H2.10 2 15,49 1152 973 179 720

    H2.11 1 8,36 633 543 90 447

    H2.12 5 40,71 2852 2405 447 1708

    H2.13 9 69,85 5064 4261 803 3066

    H2.14 7 54,91 3903 3278 625 1243

    H2.15 2 16,8 1219 1040 179 784

    H2.16 4 32,9 2323 1965 358 1415

    H2.17 7 58,1 4161 3536 625 2603H2.18 7 54,9 3903 3278 625 2315

    H2.21 7 54,9 3791 3166 625 2149

    H2.23 4 32,8 2233 1875 358 1286

    H2.24 8 60,4 4448 3733 715 2695

    H2.25 7 54,9 3903 3278 625 2315

    H3.01 96 669,6 48395 39830 8565 26587

    H3.02 92 644,3 46478 38270 8208 25552

    H3.03 8 54,9 4086 3371 715 2315

    H3.11 5 37,2 2701 2254 447 1584

    H3.12 6 60,4 4083 3547 536 2695

    H3.13 7 52,2 3780 3155 625 2212

    H3.14 4 31,3 2248 1890 358 1349

    H3.15 4 30,0 2189 1831 358 1300

    H3.16 8 65,8 4587 3872 715 2743

    H3.17 4 30,0 2189 1831 358 1300

    H3.18 8 61,6 4390 3675 715 2574

    H3.19 45 272,2 20764 16749 4015 10821

    H3.20 8 67,4 4630 3915 715 2764

    H3.21 8 67,4 4630 3915 715 2764

    H3.37 4 37,3 2686 2328 358 1809

    H3.38 4 34,6 2429 2071 358 1523

    H3.39 4 33,0 2467 2109 358 1623

    H3.40 3 27,9 1938 1671 267 1260H3.41 5 49,7 2889 2442 447 1760

    H3.42 6 64,5 4161 3625 536 2645

    H3.43 1 14,8 946 856 90 706

    H3.44 2 19,4 1337 1158 179 884

    H3.45 4 34,7 2406 2048 358 1486

    H3.46 4 34,7 2406 2048 358 1486

    H3.47 7 154,3 3966 3341 625 2370

    H3.48 19 29,6 10750 9055 1695 6334

    H3.49 4 29,6 2197 1839 358 1323

    H3.50 6 50,6 3497 2961 536 2109

    H3.51 19 149,6 10540 8845 1695 6450H3.52 8 64,0 4474 3759 715 2631

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    39/271

    MEMORIA 39

    H3.53 2 19,4 1337 1158 179 884

    H3.54 2 17,7 1349 1170 179 945

    H3.55 5 42,2 2927 2480 447 1780H3.56 6 49,6 3481 2945 536 2109

    H3.57 25 200,5 13845 11615 2230 8015

    Vestbulo de entrada:

    La zonas Vestbulo corresponde con zonas que dan a las fachada norte

    respectivamente del edificio, hemos considerado una zona de influencia desde la

    fachada de cinco metros.

    Verano Invierno

    Zona Ocup Sup.(m2) C.total(W) C.sensible(W) C.latente(W) C.total(W)

    Vestbulo 1.1 160 639,7 80309 66036 14273 23821

    Vestbulo 2.1 339 1354,7 140507 110266 30241 69035

    Vestbulo 2.2 412 1648,3 179565 142812 36753 83998

    Vestbulo 3.1 149 596,9 60342 47050 13292 27686

    Comercios:

    Verano Invierno

    Zona Ocup Sup.(m2) C.total(W) C.sensible(W) C.latente(W) C.total(W)

    H1.31 44 443,7 28333 24408 3925 17370

    H1.36 37 369,2 24102 20459 3643 14617

    H2.01 35 244,7 17575 14453 3122 9578

    H2.20 46 371,1 25738 21634 4104 15067

    H2.20 37 296,0 20585 16942 3643 11586

    H2.26 121 850,1 61411 50616 10795 33945

    Equipaje:

    Verano Invierno

    Zona Ocup Sup.(m2) C.total(W) C.sensible(W) C.latente(W) C.total(W)

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    40/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    41/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    42/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    43/271

    MEMORIA 43

    Zona Ocupacin Qv(l/s) Qv(m3/h)H1.01 2 20 72

    H1.02 4 40 144

    H1.03 8 80 288

    H1.04 7 70 252

    H1.05 6 60 216

    H1.06 7 70 252

    H1.07 8 80 288

    H1.08 3 30 108

    H1.09 3 30 108

    H1.10 3 30 108

    H1.11 4 40 144H1.12 4 40 144

    H1.13 4 40 144

    H1.14 4 40 144

    H1.15 7 70 252

    H1.16 20 200 720

    H1.17 8 80 288

    H1.18 2 20 72

    H1.19 2 20 72

    H1.20 6 60 216

    H1.21 1 10 36

    H1.22 4 40 144H1.24 6 60 216

    H1.25 5 50 180

    H1.26 28 280 1008

    H1.27 13 130 468

    H1.32 13 130 468

    H1.33 6 60 216

    H1.34 14 140 504

    H1.35 5 50 180

    H1.37 93 930 3348

    H2.03 6 60 216

    H2.04 9 90 324H2.05 5 50 180

    H2.06 2 20 72

    H2.07 1 10 36

    H2.08 2 20 72

    H2.09 2 20 72

    H2.10 2 20 72

    H2.11 1 10 36

    H2.12 5 50 180

    H2.13 9 90 324

    H2.14 7 70 252

    H2.15 2 20 72

    H2.16 4 40 144

    H2.17 7 70 252

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    44/271

    MEMORIA 44

    H2.18 7 70 252

    H2.21 7 70 252

    H2.23 4 40 144H2.24 8 80 288

    H2.25 7 70 252

    H3.01 96 960 3456

    H3.02 92 920 3312

    H3.03 8 80 288

    H3.11 5 50 180

    H3.12 6 60 216

    H3.13 7 70 252

    H3.14 4 40 144

    H3.15 4 40 144

    H3.16 8 80 288H3.17 4 40 144

    H3.18 8 80 288

    H3.19 45 450 1620

    H3.20 8 80 288

    H3.21 8 80 288

    H3.37 4 40 144

    H3.38 4 40 144

    H3.39 4 40 144

    H3.40 3 30 108

    H3.41 5 50 180

    H3.42 6 60 216

    H3.43 1 10 36

    H3.44 2 20 72

    H3.45 4 40 144

    H3.46 4 40 144

    H3.47 7 70 252

    H3.48 19 190 684

    H3.49 4 40 144

    H3.50 6 60 216

    H3.51 19 190 684

    H3.52 8 80 288

    H3.53 2 20 72

    H3.54 2 20 72H3.55 5 50 180

    H3.56 6 60 216

    H3.57 25 250 900

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    45/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    46/271

    MEMORIA 46

    Trnsito:

    Zona Ocupacin Qv(l/s) Qv(m3/h)Trnsito 124 1240 4464

    Recogida de equipajes:

    Zona Ocupacin Qv(l/s) Qv(m3/h)Sector 1.1 2206 22060 79416

    Sector 2.1 2356 23560 84816

    Sector 2.2 2860 28600 102960

    Sector 3.1 1302 13020 46872

    Polica Municipal:

    Zona Ocupacin Qv(l/s) Qv(m3/h)H3.04 15 150 540

    H3.05 13 130 468

    H3.06 6 60 216

    H3.07 4 40 144

    H3.08 4 40 144

    H3.09 5 50 180

    H3.10 7 70 252

    Polica Nacional:

    Zona Ocupacin Qv(l/s) Qv(m3/h)H3.22 1 10 36

    H3.23 1 10 36

    H3.24 1 10 36

    H3.25 1 10 36

    H3.26 2 20 72

    H3.27 1 10 36

    H3.28 1 10 36

    H3.29 1 10 36

    H3.30 2 20 72

    H3.31 3 30 108

    H3.32 8 80 288

    H3.33 5 50 180

    H3.34 2 20 72

    H3.35 3 30 108

    H3.36 2 20 72

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    47/271

    MEMORIA 47

    1.2.3 CLCULO DE EQUIPOS.

    En funcin de las necesidades frigorficas y calorficas de cada local estimaremos el

    empleo de Fan-Coils o de climatizadores para conseguir las condiciones de confort

    de nuestro local. De este modo las habitaciones con cargas menores como puedas ser

    oficinas de pequea superficie se han empleado Fan-Coils, mientras que para zonas

    de gran superficie se han empleado climatizadores.

    1.2.3.1 CLCULO DE CLIMATIZADORES.

    Clculo para verano:

    Caudal de impulsin.

    En primer lugar para poder conocer las condiciones del punto de impulsin que

    requiere nuestro local es necesario calcular el factor de carga sensible de nuestro

    local mediante la siguiente frmula:

    LS

    S

    CC

    CFCS

    +=

    Conocido este factor y haciendo uso del diagrama psicromtrico, se traza la recta que

    une el factor de carga sensible con las condiciones de confort de nuestro local, es

    decir 24 C y 50% de humedad relativa para verano.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    48/271

    MEMORIA 48

    El punto de impulsin de nuestro local de encuentra en esta recta. En primer lugar

    podramos considerar el punto de impulsin como la interseccin de la recta de carga

    con las condiciones de saturacin, pero en nuestro caso, para la mayor parte de los

    climatizadores se obtenan valores del punto de impulsin inferiores a 13 C, esto

    puede suponer temperaturas muy bajas en el agua de refrigeracin de la batera de

    fro. Temperaturas tan bajas pueden suponer el empleo de glicol, lo que encarecera

    nuestra instalacin.

    Por esta razn para nuestro clculo se ha partido, como hiptesis, de considerar una

    temperatura de impulsin que est entre 13,5 C y 14,5 C. Para la temperatura seca

    fijada y con la recta de carga podemos obtener las condiciones del punto de

    impulsin:

    Ts: Temperatura seca (C).

    HR: Humedad relativa (%).

    H: Humedad especfica (g/kg de aire).

    De este modo el valor del caudal de impulsin ser:

    )(01,3

    )(23,1

    ihiL

    ihiS

    HHQC

    TTQC

    =

    =

    Despejando de una de las frmulas obtenemos el valor del caudal de impulsin:

    )(23,1

    )()/(

    ih

    S

    iTT

    WCslQ

    =

    Punto de salida de la batera.

    Se ha considerado un recalentamiento de 1,5 C, por lo que la temperatura a la salida

    de la batera (TSB) sera:

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    49/271

    MEMORIA 49

    5,1= iSB TT

    De este modo y con la misma humedad especfica que la del punto de impulsin

    podemos conocer las condiciones a la salida de la batera:

    Ts: Temperatura seca (C).

    HR: Humedad relativa (%).

    H: Humedad especfica (g/kg de aire).

    Balance de caudales.

    Conocido el caudal de ventilacin (Qv) y el valor del caudal de impulsin (Qi), el

    caudal de retorno (Qr) a la habitacin se obtiene como:

    vir QQQ =

    El caudal de extraccin se ha calculado mediante la siguiente expresin:

    6,3

    )(6,0)/(

    3mV

    slQ localExtraccin =

    Punto de mezcla.

    El aire impulsado a los locales ser resultado de la mezcla de aire que retornamos a

    nuestro local y el aire de ventilacin.

    Las condiciones de temperatura del aire sern diferentes, por un lado el caudal que

    retornamos de nuestro local estar a la temperatura de dicho local, considerando que

    tenemos un recalentamiento del aire en el ventilador de retorno de 1C, el punto de

    retorno ser de 25 C.

    Mientras que las condiciones del caudal de ventilacin sern las del exterior

    consideradas.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    50/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    51/271

    MEMORIA 51

    Condiciones de impulsin.

    Conocida la carga de invierno para nuestro local y con las condiciones de confort de

    invierno, 22C y humedad relativa del 50%, podemos obtener el valor de la

    temperatura de impulsin.

    )(23,1hiiT TTQC =

    Despejando de la formula obtenemos la temperatura de impulsin:

    h

    i

    Ti T

    QCT +

    =23,1

    Punto de mezcla.

    El aire impulsado para invierno es, como en verano, la suma de los caudales de

    retorno y ventilacin.

    Para este caso el caudal de retorno se considera a la temperatura de nuestro local, es

    decir 22 C. Mientras que las condiciones del caudal de ventilacin sern las del

    exterior consideradas.

    El punto de mezcla se obtendr despejando de las siguientes ecuaciones:

    extvhrmi

    extvhrmi

    HQHQHQ

    TQTQTQ

    +=

    +=

    Humectacin con vapor.

    En el caso de que la humedad relativa del punto de impulsin fuera inferior a un

    40%, sera necesario aadir vapor al aire.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    52/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    53/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    54/271

    MEMORIA 54

    Climatizadores para zona de equipaje:

    Para esta zona se utilizarn cuatro climatizadores iguales ya que se han

    dimensionado las zonas para que la carga a combatir sea la misma.

    Zona Tm(C) Hm(gr_ag/Kg_as) Tsb(C) Hsb(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)

    1.1 27,9 12,84 13 9,2 14,5 9,2

    Climatizadores para aduana:

    Tenemos dos zonas de aduanas pero slo utilizaremos un climatizador ya que en la

    otra zona dispondremos de un Fan-Coil para combatir la carga.

    Zona Tm(C) Hm(gr_ag/Kg_as) Tsb(C) Hsb(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)

    H2.02 27,14 12,13 13 9,45 14,5 9,45

    Climatizador para la zona VIP:

    Zona Tm(C) Hm(gr_ag/Kg_as) Tsb(C) Hsb(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)H1.28/29-

    VIP 25,79 10,88 13 9,62 14,5 9,62

    Climatizador para la sala de prensa:

    Zona Tm(C) Hm(gr_ag/Kg_as) Tsb(C) Hsb(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)

    H1.30 26,79 11,8 13 9,56 14,5 9,56

    Climatizador para la zona de trnsito:

    Zona Tm(C) Hm(gr_ag/Kg_as) Tsb(C) Hsb(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    55/271

    MEMORIA 55

    Trnsito 27,3 12,27 13 9,4 14,5 9,4

    Climatizador para sala de equipaje:

    Zona Tm(C) Hm(gr_ag/Kg_as) Tsb(C) Hsb(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)

    H2.2 28,84 13,71 13 8,9 14,5 8,9

    Para el clculo de calefaccin, el punto de impulsin y el de salida de batera se

    consideran el mismo. El recalentamiento del aire que se produce en el ventilador de

    impulsin se considera una ganancia y por seguridad no se tiene en cuenta. En las

    siguientes tablas resumimos para cada zona los valores del punto de impulsin y del

    punto de mezcla obtenidos con las expresiones indicadas en este apartado.

    Climatizadores para grandes estancias:

    Zona Tm(C) Hm(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)

    H1.16 17,37 7,85 28,76 7,85

    H1.37 16,64 7,69 28,8 7,69

    H3.01 14,85 7,24 28,34 7,24

    H3.02 14,87 7,24 28,34 7,24

    Climatizadores para zonas comerciales:

    Zona Tm(C) Hm(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)

    H1.31 16,65 7,69 28,76 7,69

    H1.36 16,63 7,68 28,79 7,68

    H2.01 14,81 7,23 28,3 7,23

    H2.20 16,47 7,62 28,56 7,62

    H2.26 15,85 7,47 28,37 7,47

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    56/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    57/271

    MEMORIA 57

    Climatizador para la zona de trnsito:

    Zona Tm(C) Hm(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)

    Trnsito 16,51 7,63 28,36 7,63

    Climatizador para sala de equipaje:

    Zona Tm(C) Hm(gr_ag/Kg_as) Ti(C) Hi(gr_ag/Kg_as)

    H2.22 12,81 6,7 27,48 6,7

    Balance de caudales.

    El balance de caudales obtenido para cada uno de los locales se expresa en las

    siguientes tablas. El caudal de extraccin ser el caudal que retornamos desde el

    local al climatizador, el caudal de retorno es aquel que extrado del local mezclamos

    con el aire exterior y una vez tratado volvemos a impulsar de nuevo al local, el

    caudal de expulsin es el aire que retornamos del local y expulsamos al exterior, el

    caudal de ventilacin es el calculado en el apartado 1.2.2 y el caudal de impulsin se

    ha calculado segn lo indicado en este apartado.

    Grandes estancias:

    Zona Extraccin(l/s) Retorno(l/s) Expulsin(l/s) Ventilacin(l/s) Impulsin(l/s)

    H1.16 817 752 66 200 952

    H1.37 3787 3476 312 930 4406

    H3.01 2963 2449 514 960 3409

    H3.02 2846 2356 491 920 3276

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    58/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    59/271

    MEMORIA 59

    Zona VIP:

    Zona Extraccin(l/s) Retorno(l/s) Expulsin(l/s) Ventilacin(l/s) Impulsin(l/s)

    H1.28/29 5239 4986 253 470 5456

    Sala de prensa:

    Zona Extraccin(l/s) Retorno(l/s) Expulsin(l/s) Ventilacin(l/s) Impulsin(l/s)

    H1.30 2869 2653 217 640 3293

    Zona de trnsito:

    Zona Extraccin(l/s) Retorno(l/s) Expulsin(l/s) Ventilacin(l/s) Impulsin(l/s)

    Trnsito 4305 3726 579 1240 4966

    Sala de equipaje:

    Zona Extraccin(l/s) Retorno(l/s) Expulsin(l/s) Ventilacin(l/s) Impulsin(l/s)

    H2.22 914 600 315 430 1030

    Potencia de refrigeracin.

    En las siguientes tablas mostramos los valores de potencia sensible, potencia latente

    y la total, que ser el resultado de las suma de ambas potencias. En la ltima columna

    se expresa el caudal de agua necesario en la batera de fro.

    Grandes estancias:

    Zona P.Sensible(W) P.Latente(W) P.Total(W) Q.agua(l/s)

    H1.16 16313 6923 23236 0,791

    H1.37 75558 33051 108609 3,695

    H3.01 61181 58758 119939 3,212

    H3.02 58758 31844 90602 3,082

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    60/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    61/271

    MEMORIA 61

    Zona VIP:

    Zona P.Sensible(W) P.Latente(W) P.Total(W) Q.agua(l/s)

    H1.28/29 85858 20551 106409 3,62

    Sala de prensa:

    Zona P.Sensible(W) P.Latente(W) P.Total(W) Q.agua(l/s)

    H1.30 55845 22152 77997 2,653

    Zona de trnsito:

    Zona P.Sensible(W) P.Latente(W) P.Total(W) Q.agua(l/s)

    Trnsito 87333 42919 130252 4,431

    Sala de equipaje:

    Zona P.Sensible(W) P.Latente(W) P.Total(W) Q.agua(l/s)

    H2.22-equipaje 20060 14883 34943 1,189

    Potencia de calefaccin.

    Los valores obtenidos para la potencia necesaria en la batera de calor se resumen en

    las siguientes tablas para cada una de las zonas, en la ltima columna se indica el

    caudal de agua necesario en la batera de calefaccin.

    Grandes estancias:

    Zona P.Total(W) Q.agua(l/s)

    H1.16 13329 0,159

    H1.37 65884 0,785

    H3.01 56580 0,674H3.02 54295 0,647

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    62/271

    MEMORIA 62

    Zonas comerciales:

    Zona P.Total(W) Q.agua(l/s)

    H1.31 31117 0,371

    H1.36 26177 0,312

    H2.26 66688 0,794

    H2.01 20513 0,245

    H2.20 49113 0,585

    Vestbulo de entrada:

    Zona P.Total(W) Q.agua(l/s)

    Vestbulo1.1 73809 0,879

    Vestibulo 3.1 74237 0,884

    Vestibulo 2.1 160769 1,914

    Vestibulo 2.2 195486 2,328

    Sala de tripulaciones:

    Zona P.Total(W) Q.agua(l/s)

    H1.23 22322 0,266

    Zona de equipaje:

    Zona P.Total(W) Q.agua(l/s)

    Sector 1.1 227945 2,71

    Aduana:

    Zona P.Total(W) Q.agua(l/s)

    H2.02 22322 0,266

    Zona VIP:

    Zona P.Total(W) Q.agua(l/s)

    H1.28/29 65605 0,782

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    63/271

    MEMORIA 63

    Sala de prensa:

    Zona P.Total(W) Q.agua(l/s)

    H1.30 48582 0,579

    Zona de trnsito:

    Zona P.Total(W) Q.agua(l/s)

    Trnsito 72396 0,862

    Sala de equipaje:

    Zona P.Total(W) Q.agua(l/s)

    H2.22 18579 0,222

    1.2.3.2 CLCULO DE CLIMATIZADORES DE AIRE PRIMARIO.

    Para aquellas zonas de oficinas y comerciales en las que vamos a emplear Fan Coil

    ser necesario contar con un equipo que pueda aportar el aire de ventilacin

    necesario para el local. En aquellos locales en los que hemos puesto unidades

    horizontales con mueble y que tienen amplias ventanas que dan al interior de las

    grandes zonas del hall de entrada y zona de equipajes, no ser necesario impulsar aire

    de ventilacin. Se han calculado cinco climatizadores que impulsarn el aire a todos

    los locales en los que se han empleado unidades verticales ocultas de Fan Coils.

    Estos climatizadores no tendrn ventilador de retorno, todo el aire que se extraiga del

    local ser por tanto expulsado al exterior. A continuacin exponemos como se ha

    realizado el clculo de estos equipos.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    64/271

    MEMORIA 64

    Potencia de refrigeracin:

    En este caso no tenemos punto de mezcla ya que hemos eliminado el ventilador de

    retorno y todo el aire que impulsamos a la habitacin procede del exterior. El punto

    por tanto antes de entrar a la batera de fro ser de 34 C, es decir las condiciones

    externas que tenemos para verano en Madrid. Como queremos que la temperatura del

    punto de impulsin sea para todo el ao de 22 C, la temperatura a la salida en la

    batera de fro ser de 20,5 C, considerando un incremento de temperatura de 1,5 C

    en el ventilador de impulsin.

    El caudal que tenemos que considerar es el de ventilacin calculado en el apartado

    1.2.2 y ser el resultado de la suma de todos los caudales de ventilacin de los

    locales que vamos a tratar con el mismo climatizador.

    La potencia latente ser nula ya que si miramos en el diagrama psicromtrico, al

    movernos desde las condiciones exteriores hasta 22 C no le da tiempo a condensar al

    aire.

    La potencia se obtiene de la siguiente expresin:

    LST

    L

    VS

    PPP

    P

    QP

    +=

    =

    =

    0

    )5,12236(23,1

    Para el clculo del caudal de agua necesario en la batera de fro del climatizador de

    aire exterior se considerar la potencia total de refrigeracin. La temperatura de

    entrada del agua (Te) ser de 7 C, mientras que la temperatura de salida del agua

    (Ts) ser de 14 C. El caudal se obtiene despejando de la siguiente expresin:

    )()/(2,4)( TeTsslQkWPT =

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    65/271

    MEMORIA 65

    Potencia de calefaccin:

    Para el clculo de la potencia necesaria para la batera de calor tampoco existe punto

    de mezcla, ya que no retornamos el aire de la habitacin. Por tanto la temperatura

    antes de la entrada a la batera es la del exterior, que para Madrid en invierno son -3

    C. la temperatura de impulsin ser de nuevo 22 C y coincidir con la temperatura

    a la salida de la batera, ya que el incremento de temperatura que se produce en el

    ventilador favorece a combatir la carga y no se considera por seguridad.

    Los caudales de ventilacin ser la suma de todos los caudales de ventilacin de los

    locales a tratar con el mismo climatizador.

    La potencia se obtiene de la siguiente expresin:

    )022(23,1 = VQP

    Para el clculo del caudal de agua necesario en la batera de calor del climatizador de

    aire exterior se considerar la potencia de calefaccin. La temperatura de entrada del

    agua (Te) ser de 85 C, mientras que la temperatura de salida del agua (Ts) ser de

    65 C. El caudal se obtiene despejando de la siguiente expresin:

    )()/(2,4)( TsTeslQkWP =

    Resultados.

    Para el balance de caudales, al no considerar ventilador de retorno el caudal de

    retorno ser nulo. Sin embargo si ser necesario disponer de un ventilador que ir

    separado del climatizador y que servir para realizar la extraccin de aire del local, el

    caudal de extraccin ser un 80 por ciento del caudal de ventilacin. Para este caso

    los caudales de ventilacin y de impulsin son el mismo. A continuacin exponemos

    una tabla con los resultados:

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    66/271

    MEMORIA 66

    Equipo Extraccin(l/s) Retorno(l/s)

    Expulsin(l/s)

    Ventilacin(l/s)

    Impulsin(l/s)

    Equipo 0.1 640 0 640 800 800Equipo 0.2 1376 0 1376 1720 1720

    Equipo 0.3 1288 0 1288 1610 1610

    Equipo 0.4 896 0 896 1120 1120

    La potencia que necesitamos para la batera de fro y el caudal de agua necesario para

    la misma se expone en la siguiente tabla:

    Equipo P.Sensible(W) P.Latente(W) P.Total(W)Equipo 0.1 10332 0 10332

    Equipo 0.2 22214 0 22214

    Equipo 0.3 20794 0 20794

    Equipo 0.4 14465 0 14465

    La potencia necesaria para la batera de calor y el caudal de agua necesaria para la

    misma se expone en la siguiente tabla:

    Equipo P.Total(W) Q.Agua(l/s)Equipo 0.4 30308 0,361

    Equipo 0.1 21648 0,258

    Equipo 0.2 46544 0,555

    Equipo 0.3 43567 0,519

    1.2.3.3 CLCULO DE FAN COILS.

    Las oficinas y zonas comerciales del aeropuerto en la que no se ha empleado un

    climatizador ser necesario la utilizacin de Fan-Coil para combatir la carga del

    local.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    67/271

    MEMORIA 67

    Seleccin de los equipos:

    Para realizar su seleccin se ha comprobado que los modelos elegidos pueden

    cumplir con las necesidades tanto de verano como de invierno que requiere nuestro

    local.

    En algunas oficinas, que situados en el interior del aeropuerto, es decir que sus muros

    no dan al exterior, la carga de invierno se ha considerado despreciable. En funcin de

    que consideremos o no la carga de invierno los modelos sern de cuatro tubos o de

    dos tubos.

    Para pequeas oficinas, en su mayora ocupadas por una nica persona, se han

    dispuesto unidades verticales con mueble, mientras que en oficinas ms grandes y

    locales comerciales se han empleado unidades horizontales ocultas.

    Los modelos seleccionados de catlogo han sido los siguientes:

    42N 16-25-33-43-50

    42JW 005-009-016

    Las unidades verticales con mueble y parte de las unidades horizontales ocultas

    pertenecen al modelo 42N, cuya capacidad frigorfica y calorfica nominal ser

    menor que para los modelos 42JW. Todos las unidades del modelo 42JW ser

    unidades horizontales ocultas.

    Para los modelos 42N las capacidades frigorficas y calorficas sern las siguientes:

    Capacidad frigorfica nominal 1,4 7,3 kW

    Capacidad calorfica nominal 2,0 9,8 kW

    Para los modelos 42JW las capacidades frigorficas y calorficas sern las siguientes:

    Capacidad frigorfica nominal 3 16 kW

    Capacidad calorfica nominal 4 18,5 kW

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    68/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    69/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    70/271

    MEMORIA 70

    Polica Nacional:

    Zona modelo Fan-Coil

    H3.22 42N 25 Unidad vertical con mueble(4tubos)H3.23 42N 25 Unidad vertical con mueble(4tubos)H3.24 42N 25 Unidad vertical con mueble(4tubos)H3.25 42N 25 Unidad vertical con mueble(4tubos)H3.26 42N 25 Unidad vertical con mueble(4tubos)H3.27 42N 25 Unidad vertical con mueble(4tubos)H3.28 42N 25 Unidad vertical con mueble(4tubos)H3.29 42N 25 Unidad vertical con mueble(4tubos)H3.30 42N 25 Unidad vertical con mueble(4tubos)H3.31 42N 33 Unidad vertical con mueble(4tubos)H3.32 42JW 009 unidad horizontal oculta(4tubos)H3.33 42N 43 unidad horizontal oculta(4tubos)H3.34 42N 25 Unidad vertical con mueble(4tubos)H3.35 42N 33 Unidad vertical con mueble(4tubos)H3.36 42N 25 Unidad vertical con mueble(4tubos)

    Caractersticas de los Fan-Coils:

    Los equipos se han seleccionado un ventilador centrfugo y que trabaja a velocidad

    media. Para el modo de refrigeracin la temperatura de entrada del agua ser de 7 C

    y para calefaccin de 50 C, en ambos casos el incremento de temperatura ser de 5

    C. En ningn caso ser necesario el empleo de glicol en la instalacin.

    Para el clculo del caudal de agua necesario en las bateras de fro y de calor de los

    equipos se considerar la potencia total frigorfica y la potencia de calefaccin. La

    temperatura de entrada del agua (Te) ser de 7 C en verano y 50 en invierno,

    mientras que la temperatura de salida del agua (Ts) ser de 12 C en verano y 45 en

    invierno. Los caudales para verano e invierno se obtienen despejando de las

    siguientes expresiones:

    )()/(2,4)(

    )()/(2,4)(

    TsTeslQkWPInvierno

    TeTsslQkWPVerano

    =

    =

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    71/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    72/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    73/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    74/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    75/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    76/271

    MEMORIA 76

    H1.17 ADLQ 4 400 400 5H1.20 ADLQ 4 400 400 5

    H1.26 ADLQ 4 400 400 5H1.32 ADLQ 4 400 400 5H1.33 ADLQ 4 400 400 5H1.34 ADLQ 4 400 400 5H1.35 ADLQ 2 400 400 5H2.03 ADLQ 4 400 400 5H2.04 ADLQ 4 400 400 5H2.05 ADLQ 2 400 400 5H2.12 ADLQ 2 400 400 5H2.17 ADLQ 2 400 400 5H2.18 ADLQ 4 400 400 5

    H2.19-aduana ADLQ 4 600 500 12H2.21 ADLQ 4 400 400 5H2.25 ADLQ 4 400 400 5H3.03 ADLQ 4 400 400 5

    H3.04-policia ADLQ 6 400 400 5H3.05-policia ADLQ 4 600 500 12H3.06-policia ADLQ 4 400 400 5H3.09-policia ADLQ 4 400 400 5H3.10-policia ADLQ 4 400 400 5

    H3.11 ADLQ 2 400 400 5H3.13 ADLQ 4 400 400 5H3.16 ADLQ 4 400 400 5H3.18 ADLQ 4 400 400 5H3.20 ADLQ 4 400 400 5H3.21 ADLQ 4 400 400 5

    H3.32-policianacional ADLQ 4 400 400 5

    H3.33-policianacional ADLQ 2 400 400 5H3.45 ADLQ 4 400 400 5H3.46 ADLQ 4 400 400 5H3.47 ADLQ 6 400 400 5H3.48 ADLQ 4 600 500 12

    H3.50-handling ADLQ 4 400 400 5H3.51 ADLQ 6 400 400 5H3.52 ADLQ 4 400 400 5H3.55 ADLQ 2 400 400 5H3.56 ADLQ 4 400 400 5H3.57 ADLQ 6 400 400 5

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    77/271

    MEMORIA 77

    1.2.3.5 CONDUCTOS DE IMPULSIN.

    Los conductos de impulsin son los que van llevar el aire desde el climatizador hasta

    el local. El conducto lleva el caudal de impulsin calculado para cada climatizador

    en el apartado 1.2.3.1, en el caso de los climatizadores de aire primario el caudal de

    impulsin ser el mismo que el caudal de ventilacin y se han calculado en el

    apartado 1.2.3.2.

    Los conductos se han diseado mediante tablas, para las que conocido el caudal de

    impulsin podemos conocer la velocidad, la prdida de carga por metro lineal en el

    conducto y el dimetro del conducto. Se han diseado para que trabajen a media

    velocidad y teniendo en cuenta que la velocidad nunca sea superior a 10 m/s y para

    que la prdida de carga por metro lineal de conducto no sea superior a 1,2 Pa/m. Una

    vez que tenemos el dimetro del conducto, hemos empleado otra tabla para el clculo

    del conducto rectangular equivalente.

    Para el clculo de la prdida de carga en el conducto que nos permita disear el

    ventilador empleado en el climatizador, hemos empleado un programa de clculo en

    Excel. La prdida de carga se calcula para el tramo ms desfavorable, que ser aquel

    que termine en el punto ms alejado del climatizador.

    En las siguientes tablas damos los valores de caudal, seccin rectangular del

    conducto, dimetro equivalente, longitud del tramo, velocidad, prdida de carga por

    metro lineal y el sumatoria de la prdida de carga dada por el programa de clculo en

    Excel, que considera la prdida que se produce en los codos y por metro lineal de

    conducto.

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    78/271

    MEMORIA 78

    Conducto impulsin 001:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)50123 13923 1500 1000 10 9,29 0,57 53,06

    45123 12534 1500 900 6,29 9,29 0,61 56,89

    40122 11145 1300 900 6,29 9,53 0,69 61,19

    35122 9756 1300 800 6,29 9,39 0,73 65,74

    30122 8367 1100 800 6,29 9,51 0,81 70,8

    25121 6978 1100 700 6,29 9,07 0,81 75,88

    20121 5589 1000 600 6,29 9,32 1 82,16

    15120 4200 800 600 6,29 8,75 0,99 88,37

    10120 2811 750 500 6,29 7,5 0,87 93,81

    5120 1422 500 400 6,29 7,11 1,13 100,91119 33 350 300 3,23 0,32 0,01 100,95

    Perdida de carga en el difusor 5

    Total 106

    Conducto impulsin 002:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)50123 13923 1500 1000 10 9,29 0,57 53,06

    45123 12534 1500 900 6,29 9,29 0,61 56,89

    40122 11145 1300 900 6,29 9,53 0,69 61,19

    35122 9756 1300 800 6,29 9,39 0,73 65,74

    30122 8367 1100 800 6,29 9,51 0,81 70,8

    25121 6978 1100 700 6,29 9,07 0,81 75,88

    20121 5589 1000 600 6,29 9,32 1 82,16

    15120 4200 800 600 6,29 8,75 0,99 88,37

    10120 2811 750 500 6,29 7,5 0,87 93,81

    5120 1422 500 400 6,29 7,11 1,13 100,91

    119 33 350 300 3,23 0,32 0,01 100,95

    Perdida de carga en el difusor 5

    Total 106

    Conducto impulsin 003:

    Seccin

    Q(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)50123 13923 1500 1000 10 9,29 0,57 53,06

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    79/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    80/271

    MEMORIA 80

    20121 5589 1000 600 6,29 9,32 1 82,16

    15120 4200 800 600 6,29 8,75 0,99 88,37

    10120 2811 750 500 6,29 7,5 0,87 93,815120 1422 500 400 6,29 7,11 1,13 100,91

    119 33 350 300 3,23 0,32 0,01 100,95

    Perdida de carga en el difusor 5

    Total 106

    Conducto impulsin 006:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)50123 13923 1500 1000 10 9,29 0,57 53,06

    45123 12534 1500 900 6,29 9,29 0,61 56,89

    40122 11145 1300 900 6,29 9,53 0,69 61,19

    35122 9756 1300 800 6,29 9,39 0,73 65,74

    30122 8367 1100 800 6,29 9,51 0,81 70,8

    25121 6978 1100 700 6,29 9,07 0,81 75,88

    20121 5589 1000 600 6,29 9,32 1 82,16

    15120 4200 800 600 6,29 8,75 0,99 88,37

    10120 2811 750 500 6,29 7,5 0,87 93,81

    5120 1422 500 400 6,29 7,11 1,13 100,91

    119 33 350 300 3,23 0,32 0,01 100,95

    Perdida de carga en el difusor 5

    Total 106

    Conducto impulsin 007:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)50123 13923 1500 1000 10 9,29 0,57 53,06

    45123 12534 1500 900 6,29 9,29 0,61 56,89

    40122 11145 1300 900 6,29 9,53 0,69 61,19

    35122 9756 1300 800 6,29 9,39 0,73 65,74

    30122 8367 1100 800 6,29 9,51 0,81 70,8

    25121 6978 1100 700 6,29 9,07 0,81 75,88

    20121 5589 1000 600 6,29 9,32 1 82,16

    15120 4200 800 600 6,29 8,75 0,99 88,37

    10120 2811 750 500 6,29 7,5 0,87 93,81

    5120 1422 500 400 6,29 7,11 1,13 100,91119 33 350 300 3,23 0,32 0,01 100,95

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    81/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    82/271

    MEMORIA 82

    Perdida de carga en el difusor 5

    Total 106

    Conducto impulsin 010:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)50123 13923 1500 1000 10 9,29 0,57 53,06

    45123 12534 1500 900 6,29 9,29 0,61 56,89

    40122 11145 1300 900 6,29 9,53 0,69 61,19

    35122 9756 1300 800 6,29 9,39 0,73 65,74

    30122 8367 1100 800 6,29 9,51 0,81 70,8

    25121 6978 1100 700 6,29 9,07 0,81 75,88

    20121 5589 1000 600 6,29 9,32 1 82,16

    15120 4200 800 600 6,29 8,75 0,99 88,37

    10120 2811 750 500 6,29 7,5 0,87 93,81

    5120 1422 500 400 6,29 7,11 1,13 100,91

    119 33 350 300 3,23 0,32 0,01 100,95

    Perdida de carga en el difusor 5

    Total 106

    Conducto impulsin 011:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)50123 13923 1500 1000 10 9,29 0,57 53,06

    45123 12534 1500 900 6,29 9,29 0,61 56,89

    40122 11145 1300 900 6,29 9,53 0,69 61,19

    35122 9756 1300 800 6,29 9,39 0,73 65,7430122 8367 1100 800 6,29 9,51 0,81 70,8

    25121 6978 1100 700 6,29 9,07 0,81 75,88

    20121 5589 1000 600 6,29 9,32 1 82,16

    15120 4200 800 600 6,29 8,75 0,99 88,37

    10120 2811 750 500 6,29 7,5 0,87 93,81

    5120 1422 500 400 6,29 7,11 1,13 100,91

    119 33 350 300 3,23 0,32 0,01 100,95

    Perdida de carga en el difusor 5

    Total 106

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    83/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    84/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    85/271

    MEMORIA 85

    20121 5589 1000 600 5,95 9,32 1 80,3

    15120 4200 800 600 5,95 8,75 0,99 86,18

    10120 2811 750 500 5,95 7,5 0,87 91,325120 1422 500 400 5,95 7,11 1,13 98,04

    119 33 350 300 7,43 0,32 0,01 98,11

    Perdida de carga en el difusor 5

    Total 104

    Conducto impulsin 017:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)50123 13923 1500 1000 9,5 9,29 0,57 52,78

    45123 12534 1500 900 5,95 9,29 0,61 56,4

    40122 11145 1300 900 5,95 9,53 0,69 60,47

    35122 9756 1300 800 5,95 9,39 0,73 64,77

    30122 8367 1100 800 5,95 9,51 0,81 69,56

    25121 6978 1100 700 5,95 9,07 0,81 74,37

    20121 5589 1000 600 5,95 9,32 1 80,3

    15120 4200 800 600 5,95 8,75 0,99 86,18

    10120 2811 750 500 5,95 7,5 0,87 91,32

    5120 1422 500 400 5,95 7,11 1,13 98,04

    119 33 350 300 7,43 0,32 0,01 98,11

    Perdida de carga en el difusor 5

    Total 104

    Conducto impulsin 018:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)

    50123 13923 1500 1000 9,5 9,29 0,57 52,7845123 12534 1500 900 5,95 9,29 0,61 56,4

    40122 11145 1300 900 5,95 9,53 0,69 60,47

    35122 9756 1300 800 5,95 9,39 0,73 64,77

    30122 8367 1100 800 5,95 9,51 0,81 69,56

    25121 6978 1100 700 5,95 9,07 0,81 74,37

    20121 5589 1000 600 5,95 9,32 1 80,3

    15120 4200 800 600 5,95 8,75 0,99 86,18

    10120 2811 750 500 5,95 7,5 0,87 91,32

    5120 1422 500 400 5,95 7,11 1,13 98,04

    119 33 350 300 7,43 0,32 0,01 98,11

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    86/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    87/271

    MEMORIA 87

    Conducto impulsin 021:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)

    3428 952 500 350 6,85 5,44 0,75 21,42

    2427 674 400 350 6,85 4,82 0,68 26,03

    1430 397 350 300 6,85 3,79 0,52 29,54

    429 119 300 200 5,95 1,99 0,23 30,9

    Perdida de carga en el difusor 9

    Total 40

    Conducto impulsin 022:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)

    5566 1546 500 350 8,23 8,84 1,98 59,22

    4565 1268 450 350 5,53 8,06 1,79 69,07

    3564 990 450 300 5,53 7,34 1,74 78,65

    2564 712 400 250 5,53 7,12 2,3 91,33

    1563 434 400 200 5,53 5,43 7,84 134,66

    562 156 300 200 5,53 2,6 2 145,7262 17 250 200 3,7 0,34 0,04 145,89

    Perdida de carga en el difusor 5

    Total 151

    Conducto impulsin 023:

    Seccin

    Q(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)19642 5456 900 650 34,32 9,33 1 129,81

    15646 4346 800 600 2,24 9,06 1,06 154,73

    11650 3236 700 500 5,8 9,25 1,34 162,46

    7654 2126 600 400 5,8 8,86 1,56 171,5

    3658 1016 500 300 5,8 6,78 1,27 178,85

    1660 461 400 250 6,73 4,61 0,79 189,99

    Perdida de carga en el difusor 24

    Total 214

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    88/271

    MEMORIA 88

    Conducto impulsin 024:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)11852 3292 750 500 3,11 8,78 1,17 46,05

    7852 2181 650 450 5,88 7,46 1 67,18

    3852 1070 500 350 5,88 6,12 0,94 72,67

    1854 515 400 250 6,73 5,15 0,97 79,18

    Perdida de carga en el difusor 31

    Total 111

    Conducto impulsin 025:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)

    7521 2089 700 400 3,31 7,47 1,05 34,11

    5922 1645 600 400 4,33 6,86 0,96 38,26

    4324 1201 550 350 4,33 6,24 0,93 42,26

    2726 757 500 350 4,33 4,33 0,49 44,38

    1127 313 450 300 4,33 2,32 0,19 45,17

    328 91 400 250 4,85 0,91 0,05 45,6

    Perdida de carga en el difusor 5

    Total 51

    Conducto impulsin 026:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)

    6304 1751 600 400 2,85 7,3 1,08 32,385303 1473 550 400 4,29 6,7 0,96 36,49

    4302 1195 500 350 4,29 6,83 1,15 41,41

    3302 917 450 350 4,29 5,83 0,9 45,26

    2301 639 400 300 4,29 5,33 0,91 49,13

    1300 361 400 250 1,79 3,61 0,51 50,03

    299 83 300 200 3,7 1,39 0,12 50,99

    Perdida de carga en el difusor 5

    Total 56

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    89/271

    MEMORIA 89

    Conducto impulsin 027:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)20344 5651 900 650 10 9,66 1,21 63,38

    16240 4511 900 550 12,58 9,12 1,21 78,53

    12136 3371 800 500 12,58 8,43 1,17 93,25

    8032 2231 700 450 12,58 7,09 0,96 105,27

    3928 1091 500 400 12,6 5,46 0,73 114,46

    1876 521 400 250 3,3 5,21 1,05 125,37

    Perdida de carga en el difusor 31

    Total 157

    Conducto impulsin 028:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)15862 4406 700 650 7,11 9,69 1,23 60,3

    6250 1736 500 450 19,51 7,72 1,22 100,45

    3046 846 450 300 7,12 6,27 1,16 108,65

    1444 401 400 250 2,87 4,01 0,61 114,82

    Perdida de carga en el difusor 24

    Total 139

    Conducto impulsin 029:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)

    33974 9437 1200 800 9 9,84 0,83 60,5830568 8491 1100 800 6,29 9,65 0,83 65,79

    27162 7545 1100 750 6,29 9,15 0,79 70,71

    23757 6599 1100 650 6,29 9,23 0,89 76,27

    20351 5653 900 700 6,29 8,98 0,88 81,78

    16946 4707 800 650 6,29 9,06 1 88,05

    13540 3761 750 550 6,29 9,12 1,18 95,42

    10134 2815 650 550 6,29 7,88 0,96 101,45

    6729 1869 600 450 6,29 6,93 0,9 107,1

    3323 923 500 300 6,29 6,16 1,06 113,75

    1620 450 450 200 3,66 5 1,05 124,45

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    90/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    91/271

    MEMORIA 91

    Perdida de carga en el difusor 24

    Total 112

    Conducto impulsin 033:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)11884 3301 700 550 27,09 8,58 1,09 150,68

    9479 2633 700 500 3,68 7,53 0,91 154

    7074 1965 650 400 10,83 7,56 1,07 165,54

    4670 1297 600 350 10,83 6,18 0,84 174,53

    2265 629 500 350 10,83 3,6 0,32 177,94

    1062 295 400 200 2,87 3,69 0,56 183,28

    Perdida de carga en el difusor 12

    Total 196

    Conducto impulsin 034:

    SeccinQ(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)44000 12222 1400 900 9 9,7 0,69 57,94

    39600 11000 1300 850 6,29 9,96 0,78 62,81

    35201 9778 1200 850 6,29 9,59 0,75 67,53

    30802 8556 1100 800 6,29 9,73 0,84 72,81

    26403 7334 1000 750 6,29 9,78 0,94 78,6722004 6112 900 700 6,29 9,71 1,02 85,06

    17604 4890 850 650 6,29 8,86 0,93 90,88

    13205 3668 800 600 6,29 7,65 0,77 95,69

    8806 2446 750 500 6,29 6,53 5,03 127,3

    4407 1224 600 400 6,29 5,1 3,85 151,46

    8 2 400 200 3,13 0,03 0,01 151,46

    Perdida de carga en el difusor 5

    Total 157

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    92/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    93/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    94/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    95/271

    MEMORIA 95

    2268 630 450 300 33,17 4,67 0,6 112,35

    1440 400 400 250 19,5 4 0,52 126,79

    540 150 250 150 17,74 4 0,85 146,23324 90 200 150 47,5 3 0,53 178,45

    144 40 200 125 4,45 1,6 0,17 179,19

    72 20 150 125 5,98 1,07 0,09 180,01

    Conducto impulsin equipo 0.4:

    Seccin

    Q(m3/h) Q(l/s) A B L(m) V(m/s) AP/m(Pa/m) AP(Pa)4752 1320 500 350 11,45 7,55 1,39 31,52

    4464 1240 500 350 6,62 7,09 1,24 39,66

    4356 1210 500 350 3,34 6,92 1,18 43,59

    3600 1000 450 350 31,55 6,35 1,06 88,04

    3456 960 450 350 5,72 6,1 0,98 93,64

    3312 920 450 350 6,32 5,85 0,91 99,35

    3060 850 450 350 25,06 5,4 0,78 118,89

    2988 830 450 300 44,27 6,15 1,12 178,47

    2592 720 450 300 24,52 5,34 0,86 207,17

    1584 440 350 250 15,53 5,03 0,99 222,51

    1332 370 300 250 2,59 4,94 1,04 231,891116 310 300 250 48,35 4,14 0,75 282,05

    900 250 300 250 5,33 3,34 0,5 284,7

    828 230 300 200 5,49 3,84 0,76 292,89

    1.2.3.6 REJILLAS DE RETORNO.

    El modelo de rejillas seleccionadas para extraer el aire del local son la serie AT, con

    un rango de caudales de 100 a 6000 m3/h. La colocacin de las rejillas se har de

    forma que el conducto de retorno tenga la menor perdida de carga posible, las rejillas

    no tendrn que estar distribuidas de forma simtrica en el local.

    Para cada local cuya carga se combate con un climatizador se han seleccionado un

    nmero de rejillas en funcin del caudal de extraccin, las rejillas seleccionadas para

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    96/271

    MEMORIA 96

    la extraccin del aire con sus caractersticas, tamao, caudal de aire, prdida de carga

    y nivel de potencia sonora se indican en la siguiente tabla.

    Zona Modelo n Rejillas Q(m3/h) H L P(A)

    H1.16 AT 3 1000 325 525 4

    H1.37 AT 7 2000 325 825 6

    H3.01 AT 5 2200 325 825 8

    H3.02 AT 5 2200 325 825 8

    Trnsito AT 10 1600 325 625 7

    H1.31 AT 5 1400 325 625 5

    H1.36 AT 5 1200 325 525 6

    H2.26 AT 5 2800 425 625 10

    H2.01 AT 4 1000 325 525 4

    H2.20- AT 5 2200 325 825 8

    H2.02 AT 5 1000 325 525 4H2.22 AT 3 1100 325 525 5

    H1.23 AT 5 1000 325 525 4

    Vestbulo1.1 AT 10 2000 325 825 6

    Vestibulo 3.1 AT 7 2000 325 825 6

    Vestibulo 2.1 AT 20 1600 325 625 7

    Vestibulo 2.2 AT 20 2000 325 825 6

    H1.28/29 AT 10 2000 325 825 6

    H1.30 AT 10 1100 325 525 5

    Sector 1.1 AT 20 2250 425 625 8

    Sector 1.2 AT 20 2250 425 625 8

    Sector 1.3 AT 20 2250 425 625 8

    Sector 1.4 AT 20 2250 425 625 8

    En los locales que estn climatizados por Fan Coil hemos colocado una rejilla en el

    falso techo, lo ms cerca posible del equipo, para que el Fan Coil pueda tomar el aire

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    97/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    98/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    99/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    100/271

    MEMORIA 100

    4335 1204 500 400 488 6,44 0,84 0,84 158,17

    2085 579 300 300 328 6,86 1,53 1,53 176,02

    Perdida de carga en la rejilla de retorno (Pa) 5

    Total 181

    Conducto retorno 002:

    SeccinQ(m3/h) Q(l/s) A B (m) L(m) V(m/s) P/m(Pa/m) P(Pa)44835 12454 1400 900 1.220 4,35 10,66 0,72 65,6

    22335 6204 1200 650 954 10,43 8,68 0,66 93,14

    20085 5579 1100 600 878 9,87 9,22 0,81 101,12

    17835 4954 1100 600 878 10,59 8,19 0,65 107,95

    15585 4329 1000 500 762 9,55 9,5 1,02 117,64

    13335 3704 800 500 687 9,52 10 1,27 129,71

    11085 3079 800 500 687 8,27 8,31 0,9 137,09

    8835 2454 600 500 598 8,92 8,74 1,17 147,45

    6585 1829 600 450 567 7,25 0,87 0,87 152,91

    4335 1204 500 400 488 6,44 0,84 0,84 158,17

    2085 579 300 300 328 6,86 1,53 1,53 176,02

    Perdida de carga en la rejilla de retorno (Pa) 5

    Total 181

    Conducto retorno 003:

    SeccinQ(m3/h) Q(l/s) A B (m) L(m) V(m/s) P/m(Pa/m) P(Pa)44835 12454 1400 900 1.220 4,35 10,66 0,72 65,6

    22335 6204 1200 650 954 10,43 8,68 0,66 93,1420085 5579 1100 600 878 9,87 9,22 0,81 101,12

    17835 4954 1100 600 878 10,59 8,19 0,65 107,95

    15585 4329 1000 500 762 9,55 9,5 1,02 117,64

    13335 3704 800 500 687 9,52 10 1,27 129,71

    11085 3079 800 500 687 8,27 8,31 0,9 137,09

    8835 2454 600 500 598 8,92 8,74 1,17 147,45

    6585 1829 600 450 567 7,25 0,87 0,87 152,91

    4335 1204 500 400 488 6,44 0,84 0,84 158,17

    2085 579 300 300 328 6,86 1,53 1,53 176,02

    Perdida de carga en la rejilla de retorno (Pa) 5

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    101/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    102/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    103/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    104/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    105/271

  • 7/22/2019 MEMORIA DE CALCULO AC COM CLC DE FAN-COIL

    106/271

    MEMORIA 106

    Perdida de carga en la rejilla de retorno (Pa) 5

    Total 181

    Conducto retorno 015:

    SeccinQ(m3/h) Q(l/s) A B (m) L(m) V(m/s) P/m(Pa/m) P(Pa)44835 12454 1400 900 1.220 4,35 10,66 0,72 6