PARAMETROS DE DISEÑO SISMORRESISTENTE
Zona Sísmica = 2
Factor de Zona Z = 0.30
Factor U = 1.5
Factor de suelo S = 1.4
Periodo Tp = 0.9
Categoría Edificación = A
Coeficiente de Reducción R = 7
Sistema Estructural elegido = Dual
a) PREDIMENSIONAMIENTO DE VIGAS, COLUMNAS Y PLACAS
Para el predimensionamiento de vigas, columnas y placas se ha utilizado las siguientes sobrecargas.
Pasillo : 400 kg/cm2.
Aulas : 300 kg/cm2.
Techos incl. Nieve : 100 kg/cm2.
Peso de Aligerado : 300Kg/cm2. Con h = 0.20 m.
Acabados : 100 kg/cm2.
MEMORIA DE CALCULO ESTRUCTURAL I.E. SECUNDARIO
DISENO SISMORRESISTENTE POR SUPERPOSICION MODAL ESPECTRAL
ELABORADO POR: ING.ELVER CONTRERAS TITO
DISEÑO DE UNA EDIFICACION DE CONCRETO ARMADO DE DOS NIVELES
UBICACION : CUSCO
USO : EDUCACION
f´'c : 210 Kg / cm2
f``y : 4200 Kg / cm2
PARAMETROS DEL SUELO : S3
CUADRO DE VIGAS, COLUMNAS Y PLACAS
VIGA -101 0.25X0.40 C-1 0.25X0.35 PLACA MX1, MX2, MX3, MX4 0.25X0.80
VIGA -102 0.25X0.35 C-2 0.35X0.30 PLACA MY1, MY2 0.25 X1.30
VIGA -103 0.25X0.45 C-3 0.25X0.25
VIGA -104 0.30X0.45/0.60
VIGA -201 0.25X0.35
VIGA -202 0.25X0.30
VIGA -203 0.25X0.35
VIGA -204 0.30X0.45/0.60
b) METRADO DE CARGAS Y DE MASAS
Cant. Peso L(m) A(m) Alto(m) Total
LOSA ALIGERADA
Losa Aligerada e=0.20 cm. 2 300 5.95 3.42 12,209.4 Kg.
Losa Aligerada e=0.20 cm. 4 300 5.95 4.47 31,915.8 Kg.
Losa Aligerada e=0.20 cm. (pasillo) 1 300 24.9 1.55 11,578.5 Kg.
TECHO
Tirante, tornapunta, montante, par, pendolon 6,664 Kg.
Teja andina 1 12.17 26.65 10.7 3,470.34 Kg.
VIGAS
Viga V-101 1 2400 49.44 0.25 0.4 11,865.6 Kg.
Viga V-102 1 2400 52.7 0.25 0.35 11,067 Kg.
Viga V-104 1 2400 11.5 0.3 0.5 4,140 Kg.
Viga V-201 1 2400 49.44 0.25 0.35 10,382.4 Kg.
Viga V-202 1 2400 52.7 0.25 0.3 9,486 Kg.
Viga V-204 1 2400 11.7 0.3 0.5 4,212 Kg.
COLUMNAS
Primer Piso
Columna C-1 15 2400 3 0.25 0.35 9,450 Kg.
Columna C-2 4 2400 3 0.3 0.35 3,024 Kg.
Columna C-3 7 2400 3 0.25 0.25 3,150 Kg.
Segundo Piso
Columna C-1 15 2400 2.9 0.25 0.35 9135 Kg.
Columna C-2 4 2400 2.9 0.3 0.35 2923.2 Kg.
Columna C-3 7 2400 2.9 0.25 0.25 3045 Kg.
ACABADOS
Primer Piso 1 100 25.32 5.95 15065.4 Kg.
1 100 26.65 1.55 4130.75 Kg.
MUROS
Primer Piso
Ejes 9,10,11,13,15 1 1800 23.4 0.2 2.5 21060 Kg.
Eje D, B 1 1800 34.36 0.2 1.32 16327.872 Kg.
Eje D, B 1 1800 10.6 0.2 1.18 4502.88 Kg.
Eje D, B 2 1800 6.84 0.2 1.8 8864.64 Kg.
Eje D, B 2 1800 3.9 0.2 0.7 1965.6 Kg.
Eje A 0 1800 19.5 0.15 1.2 0 Kg.
Segundo Piso
Ejes 9,10,11,13,15 1 1800 23.4 0.2 2.5 21060 Kg.
Eje D, B 1 1800 34.36 0.2 1.32 16327.872 Kg.
Eje D, B 1 1800 10.6 0.2 1.18 4502.88 Kg.
Eje D, B 2 1800 6.84 0.2 1.8 8864.64 Kg.
Eje D, B 2 1800 3.9 0.2 0.7 1965.6 Kg.
Eje A 1 1800 19.5 0.15 1.2 6318 Kg.
PLACAS
Primer Piso
Ejes 9,15 2 2400 1.8 0.2 2.5 4320 Kg.
Ejes D, B 4 2400 1.1 0.2 2.5 5280 Kg.
Segundo Piso
Ejes 9,15 2 2400 1.8 0.2 2.5 4320 Kg.
Ejes D, B 4 2400 1.1 0.2 2.5 5280 Kg.
COLUMNETAS
Columnetas 12 2400 0.15 0.15 1.2 777.6 Kg.
SOBRECARGA
Aulas
Peso de sobrecarga 1° 1 300 25.32 5.95 45196.2 Kg.
Pasillo
Peso de sobrecarga 1° 1 400 26.65 1.55 16523 Kg.
Peso de sobrecarga techo incluido nieve 1 100 26.65 10.7 28515.50 Kg.
Según Reglamento, consideramos el 50% de la carga viva (Centros Educativos)
PESO TOTAL DEL 1°y 2° NIVEL
PRIMER PISO SEGUNDO PISO
ESPECIFICACION (KG) (KG)
LOSA ALIGERADA 55703.7
TECHO 10134.33635
VIGAS 27072.6 24080.4
COLUMNAS 15624 15103.2
ACABADOS 19196.15
MUROS 52720.992 59038.992
PLACAS 9600 9600
COLUMNETAS 777.6
SOBRECARGA 50% 30859.6 14257.75
TOTAL 211,554.64 132,214.68
MASAS
g= 9.81m/s2
P1 = 211.554642 Tn m1 = 21.56520306 Tn-Seg/m
P2 = 132.2146784 Tn m2 = 13.47754112 Tn-Seg/m
INERCIA ROTACIONAL
PISO 1 J1 = 1366.088222 Tn.s2.m.
PISO 2 J2 = 853.7601124 Tn.s2.m.
MATRIZ DE MASA DEL EDIFICIO
c) MODELO PSEUDOTRIDIMENSIONAL SAP 2000-Periodo y Modos
Análisis Dinámico por combinación modal espectral.
2
22.21 0 0 0 0 0
0 13.48 0 0 0 0
0 0 22.21 0 0 0. /
0 0 0 13.48 0 0
0 0 0 0 1406.89 0
0 0 0 0 0 853.76
m Tn S m
ESPECTRO DE DISEÑO DE LA NORMA SISMORRESISTENTE
Proyecto : CONSTRUCCION DE 12 AULAS IE SIMON BOLIVAR e INSTITUTO SUPERIOR PEDAGOGICO POMACANCHI
Z = 0.3 Factor de Zona
U = 1.5 Factor de Uso
S = 1.4 Factor de Suelo
R = 7 Factor de Ductilidad
Tp = 0.9 Periodo predominante del suelo
g = 9.81 Gravedad
T C Sa
0.1 2.500 2.207
0.2 2.500 2.205
0.3 2.500 2.205
0.4 2.500 2.205
0.5 2.500 2.205
0.6 2.500 2.205
0.7 2.500 2.205
0.8 2.500 2.205
0.9 2.500 2.205
1 2.250 1.985
1.1 2.045 1.804
1.2 1.875 1.654
1.3 1.731 1.527
1.4 1.607 1.418
1.5 1.500 1.323
1.6 1.406 1.240
1.7 1.324 1.167
1.8 1.250 1.103
1.9 1.184 1.044
2 1.125 0.992
2.5 0.900 0.794
3 0.750 0.662
5 0.450 0.397
0.000
0.250
0.500
0.750
1.000
1.250
1.500
1.750
2.000
2.250
2.500
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5
Acela
racio
n E
spectr
al
Periodo T(Seg.)
ESPECTRO DE DISEÑO
SaZ U C S
R
CgC 2.5
TP
T
C 2.5 C
TABLE: Modal Participating Mass Ratios
OutputCase StepType StepNum Period UX UY RZ
Text Text Unitless Sec Unitless Unitless Unitless
MODAL Mode 1 0.426513 0.817323 5.396E-07 0.000026
MODAL Mode 2 0.308893 0.000001484 0.798837 0.025403
MODAL Mode 3 0.257983 0.000007486 0.024903 0.830175
MODAL Mode 4 0.110646 0.182597 7.359E-07 0.000009452
MODAL Mode 5 0.082742 0.000001112 0.176191 0.000113
MODAL Mode 6 0.043818 0.00007 0.000068 0.144275
La tabla anterior entrega ordenadamente los periodos por lo cual se puede observar que el periodo
fundamental es 0.42 teniendo una mayor participación e X y que UX es mayor a UY y RZ lo cual indica que el
primer modo de vibrar ocurre en el eje X.
d) RESPUESTA DE ESPECTRO DE DISENO (ZONA 2 CUSCO)
TABLE: Base Reactions
OutputCase CaseType StepType GlobalFX
Text Text Text Ton
SX LinRespSpec Max 65.962
CORTE EN COLUMNAS
TABLE: Joint Reactions
Joint OutputCase CaseType StepType U1 U2 U3 R1 R2 R3
Text Text Text Text Ton Ton Ton Ton-m Ton-m Ton-m
53 SX LinRespSpec Max 1.0415 0.0264 3.0193 0.0465 1.95369 0.0015
54 SX LinRespSpec Max 1.4129 0.0215 0.4062 0.03559 2.32224 0.0015
55 SX LinRespSpec Max 1.2486 0.0144 1.6612 0.02249 2.15933 0.0015
56 SX LinRespSpec Max 1.1272 0.0106 0.0162 0.01824 2.03875 0.0015
57 SX LinRespSpec Max 0.873 0.0322 1.2372 0.05533 1.78598 0.0015
63 SX LinRespSpec Max 0.9182 0.0052 0.0109 0.00799 1.57355 0.00081
76 SX LinRespSpec Max 0.5717 0.0238 0.0124 0.03788 1.48741 0.0015
77 SX LinRespSpec Max 0.5493 0.0137 0.0432 0.0218 1.4649 0.0015
78 SX LinRespSpec Max 0.5326 0.0122 0.0012 0.01981 1.44798 0.0015
80 SX LinRespSpec Max 1.0501 0.0381 3.0096 0.05817 1.96734 0.0015
81 SX LinRespSpec Max 1.4225 0.0239 0.4263 0.03802 2.33688 0.0015
82 SX LinRespSpec Max 1.2687 0.0147 1.563 0.0228 2.18433 0.0015
83 SX LinRespSpec Max 1.1592 0.0127 0.0142 0.02032 2.07565 0.0015
84 SX LinRespSpec Max 0.8956 0.0429 1.3076 0.06589 1.81356 0.0015
87 SX LinRespSpec Max 0.7493 0.0133 1.9679 0.02074 1.40581 0.00081
88 SX LinRespSpec Max 1.0154 0.0098 0.3759 0.01504 1.66995 0.00081
89 SX LinRespSpec Max 0.9496 0.0079 0.4588 0.01088 1.60474 0.00081
93 SX LinRespSpec Max 0.6933 0.0174 1.4058 0.02591 1.35014 0.00081
831 SX LinRespSpec Max 0.8071 0.000764 0.0331 0.00121 1.46325 0.00081
832 SX LinRespSpec Max 0.8304 0.0095 0.2567 0.01518 1.48644 0.00081
TOTAL 19.1162
CORTE EN MUROS
TABLE: Section Cut Forces
SectionCut OutputCase CaseType StepType F1 F2 F3 M1 M2 M3
Text Text Text Text Ton Ton Ton Ton-m Ton-m Ton-m
SCUT1 SX LinRespSpec Max 11.8923 0.0005458 0.0927 0.00164 5.17406 0.00614
SCUT10 SX LinRespSpec Max 0.6874 1.1716 0.0201 1.15604 2.06214 0.01097
SCUT2 SX LinRespSpec Max 11.9146 0.006 0.2114 0.01799 5.1506 0.0061
SCUT5 SX LinRespSpec Max 12.1535 0.0005238 0.0832 0.00157 5.03528 0.00618
SCUT6 SX LinRespSpec Max 12.1811 0.007 0.2209 0.02106 5.00964 0.00622
SCUT9 SX LinRespSpec Max 0.6707 1.0672 0.0598 1.10675 2.01207 0.0102
49.4996
FUERZAS CORTANTES Extracción de esfuerzos en los elementos. Las reacciones en la base del edificio son: PARA EL SISMO EN X: CORTE BASAL
SEGUNDO NIVEL. CORTE EN COLUMNAS SEGUNDO NIVEL
TABLE: Element Forces - Frames
Frame Station OutputCase CaseType StepType P V2 V3 T M2 M3
Text m Text Text Text Ton Ton Ton Ton-m Ton-m Ton-m
76 0.2 SX LinRespSpec Max 1.2167 1.5171 0.0182 0.00075 0.02828 1.93281
78 0.2 SX LinRespSpec Max 0.1902 2.4558 0.0059 0.00075 0.01133 3.07277
80 0.2 SX LinRespSpec Max 0.665 2.0535 0.0066 0.00075 0.00664 2.57908
82 0.2 SX LinRespSpec Max 0.0048 1.7672 0.003 0.00075 0.00505 2.22299
84 0.2 SX LinRespSpec Max 0.4928 1.1028 0.011 0.00075 0.01997 1.42521
110 0.2 SX LinRespSpec Max 1.2118 1.5218 0.016 0.00075 0.01881 1.93624
112 0.2 SX LinRespSpec Max 0.1953 2.4544 0.0083 0.00075 0.01213 3.07216
114 0.2 SX LinRespSpec Max 0.6273 2.0793 0.0054 0.00075 0.00721 2.61119
116 0.2 SX LinRespSpec Max 0.0044 1.8212 0.0055 0.00075 0.00685 2.29007
118 0.2 SX LinRespSpec Max 0.5183 1.1441 0.0207 0.00075 0.0239 1.47251
124 0.175 SX LinRespSpec Max 0.7793 1.0773 0.005 0.0004 0.00682 1.39325
126 0.175 SX LinRespSpec Max 0.1473 1.7062 0.0039 0.0004 0.00505 2.18658
128 0.175 SX LinRespSpec Max 0.1673 1.5539 0.0074 0.0004 0.00869 1.99312
108 0.175 SX LinRespSpec Max 0.0125 1.1887 0.0011 0.0004 0.00142 1.5447
120 0.175 SX LinRespSpec Max 0.1011 1.2437 0.0036 0.0004 0.0048 1.61408
136 0.175 SX LinRespSpec Max 0.5667 0.9479 0.0103 0.0004 0.0125 1.22877
18 0.175 SX LinRespSpec Max 0.0066 1.4847 0.0028 0.0004 0.00354 1.90351
27.1196 CORTE EN MUROS SEGUNDO NIVEL
TABLE: Section Cut Forces
SectionCut OutputCase CaseType StepType F1 F2 F3 M1 M2 M3
Text Text Text Text Ton Ton Ton Ton-m Ton-m Ton-m
SCUT11 SX LinRespSpec Max 1.0591 0.3731 0.0278 0.00985 0.63446 0.00496
SCUT12 SX LinRespSpec Max 0.9637 0.3881 0.0102 0.01104 0.48539 0.00708
SCUT3 SX LinRespSpec Max 2.5848 0.0022 0.0372 0.00276 1.25114 0.00289
SCUT4 SX LinRespSpec Max 2.6371 0.0074 0.0968 0.01064 1.34813 0.00274
SCUT7 SX LinRespSpec Max 2.738 0.003 0.0333 0.00402 1.52239 0.0029
SCUT8 SX LinRespSpec Max 2.798 0.0096 0.102 0.01362 1.62933 0.003
12.7807 Se puede apreciar que para un sismo en X los muros en Y1, Y2, no tienen importancia estructural, lo cual es razonable ya que el sismo se proyecta en forma perpendicular al eje de principal inercia. Las columnas tiene un aporte del 28% de la carga. Es claro que el muro en X1, X2, X5, X6 Tienen un aporte de 72% de la carga según los resultados de SAP2000. Cabe señalar que desde el punto de vista de la estructuración cumple con la norma E030 de estructuras. Donde se indica aceptable el tipo de sistema estructural adoptado para el caso SISTEMA DUAL para edificaciones de la categoría A.
PARA EL SISMO EN Y:
TABLE: Base Reactions
OutputCase CaseType StepType GlobalFX GlobalFY
Text Text Text Ton Ton
SY LinRespSpec Max 0.1053 64.9127 CORTE BASAL CORTE EN COLUMNAS
TABLE: Joint Reactions
Joint OutputCase CaseType StepType U1 U2 U3 R1 R2 R3
Text Text Text Text Ton Ton Ton Ton-m Ton-m Ton-m
53 SY LinRespSpec Max 0.0364 0.7312 1.5644 1.50824 0.07024 0.01501
54 SY LinRespSpec Max 0.0515 0.7552 1.8409 1.5724 0.08518 0.01501
55 SY LinRespSpec Max 0.0449 0.7908 1.9184 1.65045 0.07869 0.01501
56 SY LinRespSpec Max 0.0412 0.8836 2.2694 1.86157 0.07505 0.01501
57 SY LinRespSpec Max 0.031 0.9903 2.1671 2.09624 0.06492 0.01501
63 SY LinRespSpec Max 0.0328 0.5562 4.0076 0.91356 0.05684 0.00809
76 SY LinRespSpec Max 0.0029 1.0045 0.265 1.81908 0.01094 0.01501
77 SY LinRespSpec Max 0.0027 1.0507 0.276 1.90757 0.01068 0.01501
78 SY LinRespSpec Max 0.0026 1.1789 0.3146 2.15349 0.01056 0.01501
80 SY LinRespSpec Max 0.0198 1.016 1.762 1.78973 0.03782 0.01501
81 SY LinRespSpec Max 0.028 1.059 1.6489 1.87256 0.04591 0.01501
82 SY LinRespSpec Max 0.0255 1.1078 1.7674 1.96353 0.04342 0.01501
83 SY LinRespSpec Max 0.0235 1.244 2.0455 2.21734 0.04145 0.01501
84 SY LinRespSpec Max 0.0162 1.4013 2.7255 2.5017 0.03424 0.01501
87 SY LinRespSpec Max 0.0272 0.4493 3.0809 0.73357 0.05133 0.00809
88 SY LinRespSpec Max 0.037 0.4725 3.2207 0.77135 0.06098 0.00809
89 SY LinRespSpec Max 0.0339 0.4941 3.4227 0.80842 0.05797 0.00809
93 SY LinRespSpec Max 0.0255 0.626 4.5103 1.0301 0.04962 0.00809
831 SY LinRespSpec Max 0.033 0.4856 2.6762 0.82123 0.05706 0.00809
832 SY LinRespSpec Max 0.0338 0.5464 3.1006 0.92717 0.05785 0.00809
16.8434 CORTE EN MUROS
TABLE: Section Cut Forces
SectionCut OutputCase CaseType StepType F1 F2 F3 M1 M2 M3
Text Text Text Text Ton Ton Ton Ton-m Ton-m Ton-m
SCUT1 SY LinRespSpec Max 0.3205 0.0683 1.1539 0.20486 0.33652 0.05707
SCUT10 SY LinRespSpec Max 0.0105 27.2092 0.365 15.50216 0.0316 0.09227
SCUT2 SY LinRespSpec Max 0.3212 0.0766 1.3409 0.22972 0.33494 0.05715
SCUT5 SY LinRespSpec Max 0.2088 0.1288 1.5293 0.38654 0.09872 0.05787
SCUT6 SY LinRespSpec Max 0.2095 0.1332 1.7638 0.3997 0.09714 0.05797
SCUT9 SY LinRespSpec Max 0.0104 21.1021 0.2494 10.03858 0.0313 0.09278
48.7182
SEGUNDO NIVEL CORTE EN COLUMNAS SEGUNDO NIVEL
TABLE: Element Forces - Frames
Frame Station OutputCase CaseType StepType P V2 V3 T M2 M3
Text m Text Text Text Ton Ton Ton Ton-m Ton-m Ton-m
18 0.175 SY LinRespSpec Max 1.5625 0.0635 0.9034 0.01499 1.15963 0.08196
76 0.2 SY LinRespSpec Max 0.5909 0.0764 0.7621 0.0278 0.96765 0.09793
78 0.2 SY LinRespSpec Max 0.7112 0.1151 0.7988 0.0278 1.01458 0.14465
80 0.2 SY LinRespSpec Max 0.7447 0.0984 0.8486 0.0278 1.08417 0.12445
82 0.2 SY LinRespSpec Max 0.8909 0.0899 0.9939 0.0278 1.28303 0.1138
84 0.2 SY LinRespSpec Max 0.8368 0.0633 1.1988 0.0278 1.54701 0.08178
108 0.175 SY LinRespSpec Max 1.0216 0.0657 0.7475 0.01499 0.96067 0.08402
110 0.2 SY LinRespSpec Max 0.6795 0.0353 1.4197 0.0278 1.78656 0.04473
112 0.2 SY LinRespSpec Max 0.6234 0.0549 1.5006 0.0278 1.88879 0.06892
114 0.2 SY LinRespSpec Max 0.6733 0.049 1.5817 0.0278 1.99771 0.06152
116 0.2 SY LinRespSpec Max 0.7889 0.0442 1.8353 0.0278 2.32932 0.05567
118 0.2 SY LinRespSpec Max 1.0704 0.0262 2.1692 0.0278 2.74982 0.03361
120 0.175 SY LinRespSpec Max 1.1912 0.0675 0.8712 0.01499 1.12109 0.08637
124 0.175 SY LinRespSpec Max 1.1776 0.0507 0.6857 0.01499 0.87995 0.06564
126 0.175 SY LinRespSpec Max 1.2333 0.0738 0.7315 0.01499 0.93879 0.09482
128 0.175 SY LinRespSpec Max 1.3192 0.0662 0.7752 0.01499 0.9947 0.0854
136 0.175 SY LinRespSpec Max 1.7608 0.0466 1.0482 0.01499 1.34715 0.06049
1.0867 18.8714 CORTE EN MUROS SEGUNDOI NIVEL
TABLE: Section Cut Forces
SectionCut OutputCase CaseType StepType F1 F2 F3 M1 M2 M3
Text Text Text Text Ton Ton Ton Ton-m Ton-m Ton-m
SCUT11 SY LinRespSpec Max 0.0157 4.1295 0.0932 1.11254 0.00849 0.18281
SCUT12 SY LinRespSpec Max 0.0152 6.7158 0.1405 1.71923 0.00781 0.18119
SCUT3 SY LinRespSpec Max 0.1977 1.3339 0.5532 1.83903 0.09979 0.10698
SCUT4 SY LinRespSpec Max 0.1997 1.5596 0.6457 2.14287 0.10285 0.10772
SCUT5 SY LinRespSpec Max 0.2088 0.1288 1.5293 0.38654 0.09872 0.05787
SCUT6 SY LinRespSpec Max 0.2095 0.1332 1.7638 0.3997 0.09714 0.05797
14.0008 Se puede apreciar que para un sismo en Y los muros en X1, X2, X5, X6, no tienen importancia estructural, lo cual es razonable ya que el sismo se proyecta en forma perpendicular al eje de principal inercia. Las columnas tiene un aporte del 25% de la carga. Es claro que el muro en X1, X2, X5, X6 Tienen un aporte de 75% de la carga según los resultados de SAP2000. Cabe señalar que desde el punto de vista de la estructuración cumple con la norma E030 de estructuras. Donde se indica aceptable el tipo de sistema estructural adoptado para el caso SISTEMA DUAL para edificaciones de la categoría A.
TABLE: Joint Displacements
Joint OutputCase CaseType StepType U1 U2 R3 delta U1 delta U2 delta R3 D/he
Text Text Text Text m m Radians m m Radians
piso 2 SX LinRespSpec Max 0.013344 0.000013 0.000006608 0.008086 0.000007258 1.732E-06 0.00278828
piso 1 SX LinRespSpec Max 0.005258 0.000005742 0.000004876 0.005258 0.000005742 4.876E-06 0.00175267
TABLE: Joint Displacements
Joint OutputCase CaseType StepType U1 U2 R3 delta U1 delta U2 delta R3 D/he
Text Text Text Text m m Radians m m Radians
piso 2 SY LinRespSpec Max 0.000016 0.006825 0.000136 0.004083 0.000087 0.000087 0.00140793
piso 1 SY LinRespSpec Max 4.5E-06 0.002742 0.000049 0.002742 0.000049 0.000049 0.000914
e) CONTROL DE DESPLAZAMIENTOS.
La tabla modificada que entrega SAP2000 es:
Para el sismo en X.
Los desplazamientos mayores ocurren en el eje X ya que las fuerzas están aplicadas en el eje X. El D/he para todos los pisos cumple con la norma E030 ya que son menores 0.007.
Para el sismo en Y.
Los desplazamientos mayores ocurren en el eje Y ya que las fuerzas están aplicadas en el eje Y. El D/he para todos los pisos cumple con la norma E030 ya que son menores 0.007. f) COMBINACIONES DE CARGA ORIENTADAS PARA EL DISENO.
1. 1.5D+1.8L1
2. 1.5D+1.8L2
3. 1.5D+1.8L3
4. 1.5D+1.8L1+1.8L2+1.8L3
5. 1.25(D+L1)+SX
6. 1.25(D+L1)+SY
7. 1.25(D+L2)+SX
8. 1.25(D+L2)+SY
9. 1.25(D+L3)+SX
10. 1.25(D+L3)+SY
11. 1.25(D+L1+L2+L3)+SX
12. 1.25(D+L1+L2+L3)+SY
13. 0.9D+SX
14. 0.9D+SY
ESTADOS DE CARGA
DISENO EN CONCRETO ARMADO