Sanz Rodrigo 2012

Embed Size (px)

Citation preview

  • 8/20/2019 Sanz Rodrigo 2012

    1/18

    Wind engineering in the integrated design of princess Elisabeth Antarctic base

     Javier Sanz Rodrigo*, Jeroen van Beeck, Jean-Marie Buchlin

    von Karman Institute for Fluid Dynamics (VKI), Chaussée de Waterloo 72, B-1640 Rhode-St-Genèse, Belgium

    a r t i c l e i n f o

     Article history:

    Received 15 October 2011

    Received in revised form

    19 December 2011

    Accepted 29 December 2011

    Keywords:

    Antarctica

    Integrated design

    Wind engineering

    Snowdrift

    Wind loading

    Sand erosion

    a b s t r a c t

    The Belgian Antarctic Base Princess Elisabeth is based on an elevated building on top of sloping terrain

    and connected to an under-snow garage. The integrated design of the base was supported by wind

    engineering testing that looked into building aerodynamics (pressure taps) and snowdrift management.Wind tunnel modeling using sand erosion technique allowed ef cient evaluation of the snow erosion

    and deposition around different building-block shapes during the conceptual design phase. Parametric

    testing shows that the positioning of the main building on the ridge has a signicant impact on wind

    loading and snow erosion and deposition. Important reductions in wind loading and snow deposition

    can be obtained by elevating the building and reducing the windward cantilever. The positioning of the

    garage roof can further decrease the wind loading by acting as a diffuser in the back of the building. This

    study shows that, not only for safety and cost reduction but also for the integration of renewable

    energies, important benets in the design of a building can be achieved if wind engineering is considered

    since the conceptual phase of the integrated building design process.

     2012 Elsevier Ltd. All rights reserved.

    1. Introduction

    The concern about Climate Change has signicantly increased

    the interest of scientic research in Antarctica. Coinciding with the

    International Polar Year (IPY) 2007e2008, three European research

    bases were designed and have recently been deployed in Antarc-

    tica: Halley VI (United Kingdom), Newmayer III (Germany) and

    Princess Elisabeth (Belgium).

    The new stations put in evidence the primary role that the

    environmental conditions play on their design, especially when

    higher levels of sustainability and energy ef ciency are pursued, as

    it is the case for the Princess Elisabeth   “Zero Emission”   research

    station.

    The integrated design process, implemented in the case of the

    Princess Elisabeth base, aims at making best use of the ambient

    conditions in the design of energy ef cient buildings with the leastimpact on the environment throughout their lifetime. The use of 

    renewable energies in Antarctica as primary energy source

    provides more autonomy, minimizing the fuel consumption with

    the corresponding savings in logistics, CO2 emissionsand risks of oil

    spill contamination.

    The extreme weather conditions make Antarctic construction

    the forefront of Bioclimatic Architecture, with katabatic winds up to

    70 m s1 that induce important structural loading; snow drifting

    that can produce annual build-ups as high as 1.5 m, making

    accessibility dif cult and increasing maintenance works; temper-

    atures as lowas 60  C that induce important heat losses; and very

    low humidity that increases the risk of   re. Furthermore, the

    Antarctic environment constitutes an excellent test bench for the

    demonstration of renewable energies and energy ef ciency

    technology.

    All in all, it is evident that building design in Antarctica

    requires careful consideration of the environment in order to  nd

    safe and cost-effective solutions with the least impact on the

    environment, a key aspect of the Antarctic-Environmental

    Protocol (1991).

    1.1. Philosophy of a zero emission station

    The Princess Elisabeth Antarctic research station is situated

    approximately 1 km North of Utsteinen Nunatak, on a small and

    relatively  at granite ridge (71570S 23200E, 1390 m a.s.l.), 173 km

    inland from the former Roi Baudouin base and 55 km from former

     Japanese Asuka station. The new station occupies the empty space,

    in the 20e30 East sector, left by the closing of Asuka station in

    1992. The nearest permanent stations are Syowa (Japan), 684 km to

    the west, and the Novolazarevskaya (Russia), 431 km to the east.

    The nearest coast is some 190 km north.

    *  Corresponding author. National Renewable Energy Centre of Spain (CENER),

    C/Ciudad de la Innovación 7, 31621 Sarriguren, Spain. Tel.:   þ34 948 25 28 00;

    fax: þ34 948 27 07 74.

    E-mail address:  [email protected] (J. Sanz Rodrigo).

    Contents lists available at SciVerse ScienceDirect

    Building and Environment

    j o u r n a l h o m e p a g e :   w w w . e l s e v i e r . c om / l o c a t e / b u i l d e n v

    0360-1323/$  e   see front matter    2012 Elsevier Ltd. All rights reserved.

    doi:10.1016/j.buildenv.2011.12.023

    Building and Environment 52 (2012) 1e18

    mailto:[email protected]://www.sciencedirect.com/science/journal/03601323http://www.elsevier.com/locate/buildenvhttp://dx.doi.org/10.1016/j.buildenv.2011.12.023http://dx.doi.org/10.1016/j.buildenv.2011.12.023http://dx.doi.org/10.1016/j.buildenv.2011.12.023http://dx.doi.org/10.1016/j.buildenv.2011.12.023http://dx.doi.org/10.1016/j.buildenv.2011.12.023http://dx.doi.org/10.1016/j.buildenv.2011.12.023http://www.elsevier.com/locate/buildenvhttp://www.sciencedirect.com/science/journal/03601323mailto:[email protected]

  • 8/20/2019 Sanz Rodrigo 2012

    2/18

    The selected site is very convenient as it provides stable ground

    for anchoring. The station design makes best use of terrain condi-

    tions for the integration of the building following a hybrid design.

    The main building, above ground-level and anchored onto snow-

    free rock area is connected, with a weather protected bridge, to

    an adjacent garage/storage building, constructed under the snow

    surface (Fig. 1). The summer station is designed for optimal use by

    12 people with a surface area (living, technical, research, storage) of 

    800 m2. An extension, based on heated shelters, make it possible to

    accommodate another 8 to 18 people.

    The system design of the station is based on sustainable tech-

    nology and high-energy ef ciency, with full-year monitoring and

    remote sensing capability. The station aims at being zero-

    emissions, making use of renewable energy as the primary

    energy source and integrating passive building design in

    a comprehensive energy management regime, thereby minimizing

    the use of fossil fuels. The power budget of the station is composed

    of 48% of wind power from nine wind turbines, 20% of solar

    photovoltaic from 380 m2 of solar panels and 12% solar thermal

    with 22 m2 of solar panels.

    The internal layout of the main building is designed with

    concentric layers around a central technical core, which holds the

    control systems, the water treatment unit and the batteries forenergy storage. Around the technical core, the kitchen and laundry

    rooms and the sleeping and living rooms are distributed. A

    substantial contribution to the zero-emissions target is met by

    having very good insulation, with a stainless steel outer skin and 7

    insulation layers in the walls and triple glazed windows. Passive

    heating is also an important energy saver because it recycles the

    heat produced inside the building.

    The interested reader should refer to the Comprehensive Envi-

    ronmental Evaluation CEE report [1] fora broader description of the

    scope of the base and its design particularities. A dedicated website

    (http://www.antarcticstation.org) is also available for the follow up

    of the station activities.

    1.2. The integrated building design process

    The Princess Elisabeth base was designed by the International

    Polar Foundation (IPF). An integrated building design approach was

    followed whereby multiple design disciplines were assembled

    from the beginning of the project to obtain a highly synergic design

    that allows optimizing the performance and ef ciency of the

    building. This kind of approach is the state of the art in building

    design and it is being adopted in singular buildings or building

    complexes where high levels of energy ef ciency and sustainability

    are pursued.

    A key to successful integrated building design is the early

    participation of experts from different specialties: civil engi-

    neering, architecture, interior and landscape design, energy and

    wind engineering, etc. The early collaboration among them

    allows  nding opportunities at conceptual level that can produce

    a very signicant impact in the  nal performance and cost of the

    design.

    In the Antarctic integrated building design process, wind engi-

    neering (wind and snowdrift assessment) and energy ef ciency

    lead decisions about the optimal positioning, orientation and shape

    of the building. The integration of renewable energies and opera-

    tional aspects like the positioning of entrances, emergency exits or

    snow collection facilities (for water consumption) are also deter-

    mined after careful assessment of the environmental conditions of 

    the building envelop.

    The aerodynamic design of Princess Elisabeth station had three

    phases: the conceptual design phase, the building envelop design

    and the optimization phase. In the conceptual phase, the designers

    had to decide about the optimum building typology by trading off basic design parameters on a number of building-block concepts.

    Once the basic typology was selected, the building envelope was

    shaped and positioned on the ridge considering both internal

    constraints (internal layout and system integration) and external

    environmental aspects. From the wind engineering point of view,

    snowdrift control and wind loading had to be tested in order to

    assess the aerodynamic performance of different building proto-

    types and ridge integration alternatives. Finally, an optimization

    phase looked at more detailed elements of the building like, for

    instance, localized forces on the corners of the building or the

    integration of the under-snow garage.

    1.3. Wind engineering strategy

    Wind engineering constitutes a crucial aspect in the design of 

    modern Antarctic bases [3]. Not only for safety and cost reduction

    but also for the integration of renewable energies, important

    benets in the design of a building can be achieved if wind engi-

    neering is part of the integrated building design process since the

    very beginning.

    Fig. 1.   Sketch of the building and its integration in the ridge.

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e182

    http://www.antarcticstation.org/http://www.antarcticstation.org/

  • 8/20/2019 Sanz Rodrigo 2012

    3/18

    All modern buildings have undergone aerodynamic studies at

    different stages of their design. Delpech et al.   [4]   simulated the

    snowdrift around Concordia station using real snow in a climatic

    wind tunnel. Waechter and Williams [5] used water ume and CFD

    modeling of snowdrifts to support the design of a new building for

    the Amundsen Scott base at the South Pole. Beyers and Harms  [6]

    made  eld tests of snow accumulation in the vicinity of SANAE IV 

    station using a reduced scale model of the building. Leitl et al. [7]

    performed wind tunnel simulations of Neumayer III station on

    snowdrift and wind loading. The design of the new Halley VI station

    has also been supported with CFD simulations (not published).

    The wind engineering aspects of Princess Elisabeth station were

    tested at the von Karman Institute L1-B wind tunnel with support

    from numerical CFD models at different stages of the design. This

    paper will only deal with the experimental part. Information about

    the numerical aspects can be found in Ref.  [2].

    Snowdrift modeling in wind tunnel is a dif cult task due to the

    inherent impossibility to maintain similarity of all the driving

    forces. It is also very costly and time consuming as it takes several

    hours to develop signicant build-ups. As a result, it was not

    feasible to use this technique in the very demanding conceptual

    design phase, where many building congurations had to be tested

    in a very limited amount of time. Instead, the sand erosion tech-nique proved to be a cost-effective solution to evaluate the wind

    conditions at ground-level and, at the same time, identify snow

    accumulation and erosion regions. The application of this technique

    to snowdrift assessment is published on this paper forthe rst time.

    The sand erosion technique allowed the evaluation of six

    different building-block concepts with several ridge integration

    strategies. Prismatic blocks were used in order to offer the best

    perspective for a systematic comparison of the different design

    concepts. Two block concepts offered similar aerodynamic perfor-

    mance: a square-based one-storey building or a rectangular-based

    two-storey building aligned with the wind direction.

    After a site visit during Belare-2005 expedition, IPF selected the

    location on the ridge offering the best conditions for anchoring and

    accessibility. It also turned out that a one-storey building would bepreferable for a better compatibility with the internal layout of the

    building, which would be based on a concentric architecture

    around a technical core reserved for the system installations. The

    square-based model had better compatibility with this concentric

    concept than the rectangular-based concept. Hence, it constituted

    the reference for the building envelop design phase in which the

    square building would be shaped and positioned to obtain better

    aerodynamic performance.

    The reference building-block was instrumented with pressure

    taps to measure wind loading at different building-ridge integra-

    tions. A parametric study showed that the height of the building

    legs and the positioning across the ridge were sensitive parameters

    for both aerodynamics and snowdrift control.

    While elevating the main building with legs solves the problemof snow accumulation, it might generate problems of snow erosion

    around the under-snow garage. Hence, dune visualization tests

    were performed to check the impact of the snow erosion generated

    by the building on the integrity of garage.

    Several evolutions of the envelop design were tested until the

    adoption of a nal one, whose aerodynamic performance was again

    tested with pressure taps to assess the  nal loads and to optimize

    the  nal positioning on the ridge. During this phase, wind tunnel

    testing also revealed some aerodynamic aspects of the garage roof,

    which could be used as a diffuser to modify the wind loading on the

    building.

    These wind tunnel testing phases will be summarized in this

    paper. The test case shows how wind engineering can aid the

    integrated building design process and the bene

    ts of considering

    these aspects from an early stage.The originality of the test case can

    be focused on the study of the inuence of the   ow under the

    building on the aerodynamic aspects of the building. Elevated

    buildings on pillars are the typical design solution in snow regions

    to cope with snowdrifts but they are typically placed in at terrain.

    Having sloping terrain under the building makes the building

    aerodynamics less predictable. It is shown in the paper that by

    carefully positioning the building on top of the ridge important

    reductions in wind loading and snowdrift can be obtained.

    2. Experimental setup

     2.1. Wind tunnel site and ABL model

    A model of the southern part of the ridge topography at a scale

    1:100 was built and installed at the 2.8 m diameter turning table of 

    the VKI L1-B atmospheric boundary layer wind tunnel (Fig. 2, left).

    The wind tunnel is of the close-circuit type, equipped with two

    contrarotating fans of 580 kW that forces wind speeds up to

    6 0 m s1. The rectangular wind engineering test section is 2 m high,

    3 m wideand20 m longwith a roughedoor to allow the growth of 

    a turbulent boundary layer similar to the lower part of the atmo-

    spheric boundary layer (ABL).

    The site topography is made of 3 mm thick wooden layers

    smoothed up with high denition plaster within the steps. Of 

    course, the model represents both the ridge and the snow surface

    as it was found in Antarctica. Once the building is situated on top of 

    the ridge, the snow surface behind it will change under the action

    of the erosion and deposition generated by the building.

    Since no Coriolis forces and thermal stratication can be

    reproduced, the test section is suitable for the characterization of 

    the surface boundary layer in neutral conditions. This is suitable for

    the purposes of this investigation since we are interested in

    snowdrift and wind loading at high wind speeds in the  rst 20 m

    above the ground. At low wind speeds the Antarctic boundary layer

    is characterized by stable stratication due to a quasi-permanent

    temperature inversion due to radiative cooling.The incoming surface boundary layer is modeled in the wind

    tunnel using a 20 m rough  oor that reproduces the logarithmic

    wind prole according to Monin Obukhov theory:

    U   ¼  u*k

    ln

     z 

     z 0

      (1)

    where  u*   ¼ ffiffiffiffiffiffiffis=r

    p   is the friction velocity,   s is the shear stress,  r is

    the air density,   k  ¼  0.4 is the von Karman constant, and  z 0  is the

    roughness length. Beyers and Harms [6] also used this logarithmic

    prole to  t measurements in the vicinity of SANAE IV station. The

    effective roughness height above snow covered terrain is propor-

    tional to the saltation layer thickness, which varies with the square

    of the friction velocity.

     z 0;eff   ¼   C 1u2*

    2 g   (2)

    where g  ¼  9.8 m s2 is the acceleration of gravity and the constant

    C 1  depends on the snow properties. Beyers and Harms  [3] present

    values from different authors ranging from 0.035 to 0.12. The

    effective roughness is low for wet snow and high for fresh snow

    cover after snowfall. At SANAE IV they found a value of 0.0035 over

    wet snow for friction velocities above 0.4 m s1. The effective

    roughness height was between 2.8$105 m and 1.8$104 m for

    friction velocities ranging from 0.4 to 1 m s1 respectively. For dry

    uncompacted snow the saltation layer and roughness height will be

    higher. Considering the upper limit of   C 1   for high effective

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e18   3

  • 8/20/2019 Sanz Rodrigo 2012

    4/18

    roughness conditions, the values of  z 0  can range between 104 m

    and 6$103 m for the same range of friction velocities. Therefore,

    the variability of the effective roughness length can be quite large,

    although always very low, as it depends on the snow properties and

    the friction velocity.

    The sensitivity associated to the ABL is assessed by testing two

    ABL classes: Class I or   ‘smooth ABL ’ ( z 0 ¼  2$104 m, 7% turbulence

    intensity at building height, in full-scale units), close to the ex-

    pected site conditions, and Class IV or   ‘rough ABL ’ ( z 0 ¼  0.4 m, 20%

    turbulence intensity at building height, in full-scale units), typical

    of the urban environment. The class I boundary layer is obtained by

    removing the roughness elements of the class IV boundary layer.

    The urban boundary layer is of course an unrealistic extreme casefor Antarctica but it is interesting to check the sensitivity of the

    building aerodynamics to the incoming wind prole since the

    incoming ABL is not known a priori. Nevertheless, it is expected

    that snow erosion and deposition will be dominated by the

    disturbance generated by the building rather than by the incoming

    ow conditions.

     2.2. Wind climate from onsite AWS data

    An automatic weather station (AWS) was placed at the south-

    ernmost edge of the ridge since December 2004. During the winter

    2005, a station malfunction resulted in loss of measurements

    between the 2nd of July and the 14th of August. Nevertheless, the

    annual data availability is suf cient to assess the local wind climatethroughout the year 2005, with an annual 4-m mean velocity of 

    5.9 m s1 and a prevailing wind direction sector from E to SSE. The

    most energetic wind direction is E with 90% of the energy

    content (Fig. 3). A CFD simulation of the mean  ow from this wind

    direction results in the 4-m high speed-up contour map of  Fig. 2

    (right) with respect to the AWS mean velocity. It is observed that

    the building area in top of the ridge has 20% higher wind speeds

    than the ones observed at the AWS position.

    The estimatedmean velocity is ratherlow due to the presence of 

    nearby Utsteinen and the Sor Rondane Mountains to the S-SE, that

    shelter from the intense katabatic winds of the region. Wind speed

    measured at Asuka Station between 1986 and 1991, 60 km north-

    east, were twice as high due to a more exposed site to the katabatic

    winds.

    Even though the mean wind speed is not high, the site is char-

    acterized by the presence of intense wind storms, especially during

    the winter season. This is revealed by an annual velocity distribu-

    tion with a long tail characterized by a Weibull shape factor of 1.35.

     2.3. Snowdrift assessment: sand erosion tests

    The presence of strong winds in Antarctica is responsible for the

    transport of large quantities of snow in the form of snowdrifts,

    producing a variety of operational problems around buildings and

    structures.

    It is normal practice in Polar Regions to use elevated buildings as

    they can passively remove the snow through the window passingunder the building. Almost all modern stations use this basic

    principle in their design. Some of them like Halley V, where the

    snow accumulation rate is 1.5 m per year, even include jackable legs

    to adapt to the progressively higher snow level.

    The size of the building generated snowdrifts will depend,

    among other factors, on the height of the pillars and the orientation

    of the building against the wind. General guidelines about snow-

    drifts around prismatic buildings on   at terrain can be found in

    Refs.   [8,9]. Elevated buildings present smaller snowdrifts by

    increasing the height or the length of the building in the direction

    of the wind. On the contrary, increasing the width perpendicular to

    the wind direction increases the size of the snowdrifts. Kwok et al.

    [10] studied the optimum spacing between groups of buildings in

    order to minimize snowdrift. Kwok and Smedley [11] studied theeffect of the corner geometry and the wind incidence on the

    snowdrift size. A very signicant reduction in snowdrift is obtained

    by chamfering or rounding the corners with respect to a sharp-

    edged building model. Hence, the chamfer should be as large as

    the internal layout allows. Irrespectively of the corner geometry

    they also recommended to align the building with the main wind

    direction and use longer pillar heights to reduce the volume of the

    snowdrift. Chamfering the corners is also a well known technique

    to decrease wind loading on the building facades.

    In the case of Princess Elisabeth base, the presence of the ridge

    sticking out of the snow surface constitutes a particular situation in

    which the wind speed-up generated between the building and the

    ridge can be used to enhance the snow removal ef ciency of the

    building, allowingfor theuse of shorter pillars.The same principleis

    Fig. 2.   Topographic model of the ridge at a scale 1/100 in the L1-B wind tunnel (left) and Eastern speed-up contours at 4 m with respect to the AWS velocity (right).

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e184

  • 8/20/2019 Sanz Rodrigo 2012

    5/18

    used in the new AmundseneScott base in the South Pole, where the

    bottom edge of the building facing the wind is shaped like an airfoil

    to accelerate the  ow and increase the erosive action on the snow.

    The snow drifting process is described in detail in Ref.  [12]. The

    requirements for wind tunnel modeling of snowdrifts around

    obstacles can be found from different authors [9,13e

    15]. Geometricsimilitude of snowdrifts is fullled if the model and prototype windelds are similar because the snowdrift development is driven by

    the wind shear stress. Hence, standard wind engineering require-

    ments can be adopted to obtain   ow similarity   [16]. Apart from

    scaling the topography and building geometry and the ABL prole,

    In the case of bluff body aerodynamics it is standard practice to

    assume  ow similarity when a fully turbulent regime is attained,

    which is achieved with Re  >  104.

    Testing the snowdrift development rate requires length exper-

    iments at low wind speeds in order to avoid too much Froude

    distortion [9]. Since the interest of the design process was rather on

    the comparison of different building typologies, in the conceptual

    and envelope design phases, than on the prediction of the amount

    of snow build up, partial snowdrift modeling was adopted. Thealternative model is based on the sand erosion or scour technique,

    which is used in wind engineering studies related to the assess-

    ment of the wind comfort around buildings   [17e19], i.e. the

    prediction of the occurrence of high level winds at ground (i.e.

    pedestrian) level in the urban environment.

    The test procedure is straightforward. A thin layer of sand

    (w3 mm) is spread all over the  oor of the test section. A uniform

    freestream velocity is set in the wind tunnel for a certain time

    (1 min) such that a quasi-steady erosion contour is obtained. This

    contour indicates lines where the friction velocity reaches the

    threshold for saltation. By increasing the freestream velocity in

    progressive steps (from 5 to 13 m s1 in steps of 0.5 m s1),

    a family of contours is obtained, each one associated to a particular

    value of the freestream velocity and the same value of the local

    (threshold) friction velocity. A picture is taken from the top at the

    end of each time step and a contour detection algorithm extracts

    the contours that are gridded to obtain a contour map of erosion

    wind speeds.

    Even though some advances have been made in the quanti-

    cation of the sand erosion tests as a measurement of the shearstress  [20,21], the technique is still mostly used as a visualization

    tool in order to spot areas with high or low skin friction. Livesey

    et al. [18] compared thewind speeds inferred from the sand erosion

    technique with those measured with a hot-lm anemometer. He

    found that the sand erosion measurement, rather than the mean

    speed, was related to the gust speed, dened as the mean plus one

    standard deviation. Nevertheless, the wind speeds inferred had

    considerably large variability. As a result, it was concluded that the

    technique was suitable to identify areas of high relative winds and,

    as such it shall be used in comparative studies. This capability will

    be used in the present context to infer the action of the building on

    the snow surface around it by comparison with the situation

    without the building and, as a result, distinguish areas of snow

    deposition and erosion. Therefore, the sand erosion technique isperformed in two steps:  rst without the building (reference case)

    and then with the building model at the position and orientation of 

    interest.

    Being the erosion contours related to a gust factor  [18]   the

    contours never reach a steady state shape because they are all the

    time eroded under the action of turbulence gusts. Nevertheless, in

    the rst minute after a change in the freestream velocity, the largest

    changes are produced as a result of the new mean wind speed [21].

    Therefore, the contours recorded during the test are assumed to be

    contributed mostly by the mean wind speed.

    Once the two erosion speed contour maps are obtained, the

    ratio between both will reect an amplication factor,   Ae,

    a measure of the action of the building on the reference or back-

    ground 

    ow 

    led:

    Fig. 3.   AWS wind speed and direction distributions (JJA corresponds to summer season and DJF to winter season).

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e18   5

  • 8/20/2019 Sanz Rodrigo 2012

    6/18

     Ae   ¼  U 0U b

    (4)

    where U 0 is the erosion wind speed from the building-free case and

    U b is the erosion wind speed from the building case. That is, Ae >  1

    implies a relative increase of the wind shear and Ae <  1 a decrease

    of the wind shear. Then, in areas where  Ae is equal or close to 1, the

    building does not change the background surface wind  ow.

    The sand, as the snow, is eroded when the shear stress of thewind acting on the ground exceeds a certain threshold. This

    condition is satised, in the case of the sand employed in this study,

    fora thresholdfrictionvelocity of 0.23 m s1. The contoursobtained

    from the sand erosion patterns delimit the positions at which the

    friction velocity is near the threshold value, separating the erosion

    (friction velocity higher than the threshold) from the deposition

    areas (friction velocities bellow the threshold) for a given velocity.

    According to Anno [14]   “the geometrical similitude of a border line

    between the eroded area and the deposited area constitute the

    most important similitude in the modeling of a snowdrift since the

    snowdrift would be formed as a combination of erosion and

    deposition”. Hence, provided that the  ow similitude parameters

    are satised, the extension of the snow deposition areas will be

    delimited with the contour at which the local friction velocityequals the threshold friction velocity. The scaling of the snowdrift

    areas is directly related to the ratio of friction velocity to threshold

    friction velocity (u*/u*t , ratio between the wind shear stress and the

    particle cohesive forces). Hence, the scale factor between the  eld

    velocity and the wind tunnel velocity is directly the ratio of 

    threshold friction velocities:

    u*   ¼   u*;  WTu*t 

    u*t ;WT;   U   ¼   U WT 

    u*t u*t ;WT

    (5)

    where the subscript WT denotes wind tunnel parameters.

    The threshold friction velocity of the snow in the led is dif cult

    to predict and ranges between 0.1 m s1 for dry uncompacted snow

    and 0.4 m s1 for wind hardened snow [22]. Li and Pomeroy [23]

    found threshold 10 m wind speeds ranging from 7 to 14 m s 1 forwet snow and from 4 to11 m s1 for dry snow using meteorological

    data from 16 stations in western Canada. Beyers and Harms   [6]

    found a threshold 10 m wind speed of 8 m s 1, equivalent to

    a threshold friction velocity of 0.28 m s1, from prole measure-

    ments at SANAE IV base (Droning Maud Land, Antarctica). Mann

    et al. [24] analyzed particle counter prolesof snow at Halley (Coats

    Land, Antarctica) and found threshold friction velocities in the

    range 0.22e0.36 m s1, depending on the time since the last

    blowing snow deposition. Hence it seems that an average value of 

    0.3 m s1 can be assumed for the threshold friction velocity of the

    snow in Antarctica. Since it is 30% higher than that of the sand

    particles used in the sand erosion tests, it means that the   eld

    velocities will be scaled by a factor 1.3 of the wind tunnel velocities

    according to Eq. (5).Of course, the sand erosion technique is a surface visualization

    and does not provide information about the development rate of 

    the height of erosion or deposition. Therefore, the comparisons

    between the different building typologies will be based on the size

    of the areas with   Ae  <   1, as an indicator of the ef ciency of the

    building to accumulate snow. Considering a typical threshold wind

    velocity for snowdrift of 5 m s1 at 4 m in the AWS position, 91% of 

    the snowdrift will come from the sector E-ESE (63%) and SE-SSE

    (28%) sectors. Two prevailing snowdrift directions where selected

    for testing during the design phase: 101 and 145. The  rst one is

    the most energetic and will bring the largest contribution to

    snowdrifts as it is noticed from the snow patterns behind the ridge.

    Fig. 4  shows some examples of photos obtained from erosion

    tests. The wind speed is progressively increased from the top

    (6 m s1) to the bottom (12 m s1). The left column presents the

    building-free test which is used as a reference to compute the

    amplication factor. The middle and right columns show two

    erosion tests for a rectangular building, situated on top of the ridge

    with two orientations: parallel and perpendicular to the incoming

    wind direction (145). The building in both cases is elevated from

    the ground leaving a clearance of one (full-scale) meter between

    the building and the top of the ridge.

    The areas out of the inuence of the building present similar

    erosion patterns to the building-free case. The small differences are

    due to the inherent lack of repeatability of the manual sand

    spreading process. Nevertheless, the reproducibility of the erosion

    tests is quite good, with uncertainties on the erosion velocities

    bellow 0.5 m s1.

    At low erosion velocities, the  rst erosion patterns appear near

    the corners and bellow the building, where the turbulence and

    wind speed-up are the highest. At high velocities, only the sand in

    the best sheltered areas remains. These areas will have good wind

    comfort butwill also build up snow.As expected, when the building

    is oriented perpendicular to the prevailing wind direction, the

    snow accumulation areas are increased both behind and in from of 

    the building. The accumulation in the back is not so problematic if 

    there is some space left between the building and the snowdrift,where the main entrance would be placed. The snowdrift accu-

    mulated in the front is more risky as it will progressively block the

    ow underneath the building creating more build up in the back.

     2.4. Garage integration: dune formation tests

    The surface erosion tests are very helpful in the analysis of the

    wind conditions at surface level but they do not offer much infor-

    mation about the vertical development of erosion or deposition. As

    the elevated building concept seems to have the snow accumula-

    tion problem under control, it was important to assess the effect

    that the building aerodynamics would have on the snow erosion

    around the under-snow garage, situated just behind the main

    building. Aerodynamically speaking the garage roof serves asa platform that avoids the development of too large snow erosion in

    the vicinity of the main building, providing a more stable ground to

    give access to the building from the West.

    To study the garage integration, an 80 cm wide portion of the

    wooden ridge model was removed from the lee side at the location

    of the building. A vertical cut of 8 cm, following the rock prole asit

    was found on the site, gives room for the accommodation of 

    a 45   11  5 cm3 garage. The height between the garage roof and

    the ridge top was kept at 1 m in full scale. The empty space left waslled up with sand plus an additional centimeter to cover the

    garage entirely. This situation constitutes the setup for the dune

    formation visualizations. These testsare done, similar to the surface

    erosion tests, at progressively increasing speeds but now the time

    for each velocity step is extended to 5 min to account for the longerdevelopment of the dune patterns. The edges of the cut have been

    placed suf ciently far away from the action of the building, making

    use of the results from the sand erosion tests. This will ensure that

    the dunes are only driven by the action of the wind and not by the

    presence of extra vorticity from the edges of the cut. Interestingly,

    at the end of the experiments the erosion patterns show a smooth

    transition from the snow bed to the wooden proles at the edges.

    Since these proles are obtained in real scale by erosion and

    deposition generated by the ridge alone, this can be considered as

    a good indication of the similarity of the snow erosion patterns in

    the wind tunnel. In fact, by measuring the snow surface topography

    before and after the construction of the station, Pattyn et al.  [25]

    conrmed that, apart from the immediate vicinity, the building

    has a limited effect on the patterns of snowdrift behind the ridge.

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e186

  • 8/20/2019 Sanz Rodrigo 2012

    7/18

    The sand bed is very erodible, compared with the wind hard-

    ened snow and ice bed, so the results cannot be directly related to

    the  eld conditions. As with the erosion tests, the dune formation

    test can be used to qualitatively compare the relative difference

    between different building congurations.

     2.5. Wind loading assessment: pressure taps tests

    To study the building-ridge integration from the wind loading

    point of view, a model of the reference and  nal building models

    was manufactured with a distribution of pressure taps to map the

    pressure acting on the building skin (Fig. 5).

    The number of pressure taps was limited by the size of the

    evacuation bridge situated in the back of the building, through

    which all the 1 mm diameter tubes had to pass in order to reach

    three scanning valves situated under the wind tunnel. The low

    frequency response of the tubing only allowed the measurement of 

    mean pressures for the characterization the mean wind loading.

    Uematsu and Isyumov [26]  state that, when the characteristic

    dimension of the building is small compared with the turbulence

    integral scale of the incoming winds, the maximum load effects can

    be evaluated using a quasi-steady approach. This is the standard

    practice of many codes, like the Eurocode  [27] or the Japanese AIJ

    [32]   recommendations, which deduce the design load from the

    mean pressure

    eld. It is also convenient when the turbulence

    eld

    Fig. 4.  Example of erosion tests: Building-free test as reference (left column), rectangular building oriented along the incoming wind direction (middle column) and perpendicular

    to the incoming wind (right column). The wind direction (145 ) is indicated with an arrow.

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e18   7

  • 8/20/2019 Sanz Rodrigo 2012

    8/18

    is unknown, as in the present case. The quasi-steady method

    assumes that the pressure   uctuations on the building are fully

    correlated with the velocity   uctuations, i.e. the maximum pres-

    sure will appear at the maximum velocity peak. Then, the designpressure is calculated by multiplying the mean pressure coef cient

    with the peak dynamic pressure calculated with the extreme

    (design) wind velocity. This approach fails when the building

    generated turbulence, at separation regions, contributes signi-

    cantly to the pressure  uctuations. This building generated turbu-

    lence has smaller scales that can be important for small elements

    on the skin of the building. As a result, the quasi-steady approach

    can be safely used to calculate design loads for the main structure

    or for large elements of the building but not for localized small

    elements.

    Tieleman et al. [33] conclude, in their review of the wind tunnel

    requirements for wind loading assessment of low-rise buildings,

    that the incoming wind prole does not inuence the mean pres-

    sure coef 

    cient. It is more important to match the incoming hori-zontal turbulence intensities if one is interested in reproducing well

    the  uctuations of the pressure coef cients. The independence of 

    the mean pressure coef cient with the incoming turbulence was

    also demonstrated in Ref.  [28]. Hence, the uncertainty associated

    with the incoming boundary layer conditions might not be that

    important for the modeling of the mean pressure  eld. Neverthe-

    less two limiting classes of neutral ABL were tested in order to

    verify this hypothesis.

    The mean pressure coef cient is dened according to the

    incoming dynamic pressure at freestream level:

    Cp10   ¼  D p

    1

    2rU 2AWS

    (6)

    where  D p   is the measured mean pressure relative to a common

    undisturbed reference outside the wind tunnel,  r  is the air density

    and   U AWS   is the reference wind speed velocity measured at the

    AWS position. Notice that the AWS is located at a lower elevation

    than the building of around 10 m. The subscript 10 is used in

    accordance with the Eurocode   [27]   to stand for global pressure

    coef cient, to be used for structural design, or local pressure

    coef cient for surfaces greater or equal to 10 m2. The AWS position

    is used as a reference for the wind speed because it can be related

    later with the   eld measurements to obtain the design dynamic

    pressure:

    D p50   ¼   Cp101

    2

    rU 2AWS;50   (7)

    where U AWS,50 is the design velocity estimated using extreme value

    analysis at the AWS position. The mean yearly air density measured

    at the site is 1.13 kg m3.

    The overall forces acting on the building are obtained by inte-gration of the mean pressure coef cients on the building facades.

    The force coef cient along i  axis, CF i, is dened as follows:

    CF i   ¼  F i

    1

    2rU 2AWS Ai

    (8)

    where   Ai  is the frontal area perpendicular to the incoming wind

    direction along the  i  axis.

    3. Conceptual design

    The conceptual design of the base started from the selection of 

    a number of block geometries, with the least detail level, offering

    the best perspective for a systematic comparison of the designprototypes. Six different block concepts were selected for testing

    during the conceptual design phase, all of them with the same

    living area. The differences between them were on the shape of 

    the base (square or rectangular), the number of storeys (one or

    two) and whether the building was integrated on the ridge or

    elevated. Several wind incidences and ridge positions were

    tested.

     3.1. Selection of reference building-block concept 

    Fig. 6   shows three models, made of transparent plexiglas to

    look through, that provided similar performance from the

    snowdrift point of view (two building orientations are tested).

    Two other building concepts integrated on the ridge presentedsnow accumulation areas next to the building, indicating prob-

    lems of accessibility   [3]. It is clearly noticed the impact of the

    building orientation on the winds at surface level. When the

    rectangular two-storey building is placed perpendicular to the

    incoming wind it presents a much larger obstruction to the  ow

    and generates higher speed-ups (erosion areas) and also larger

    areas for snow accumulation in the from and in the back of the

    building. When the frontal area is minimized by aligning the

    building with the wind direction, the snow deposition area is very

    much reduced, as indicated by Kim et al.   [8]   in   at terrain

    conditions.

    The square-based buildings present similar snow accumulation

    areas. The orientation at 45 seems to present fewer problems for

    snow build-up in front of the building.

    Fig. 5.   Reference (left) and  nal (right) building models instrumented with 133 and 159 pressure taps respectively.

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e188

  • 8/20/2019 Sanz Rodrigo 2012

    9/18

    The rectangular model presents the smallest snowdrift area of 

    the three models, when it is aligned with the incoming wind. Inthe other hand, it is also more sensitive to the wind direction

    variability. Therefore it was concluded from these tests that the

    three concepts had similar performance with respect to snow.

    Hence, the selection of the building typology to follow the design

    process could be left to other design criteria. Because of an easier

    construction and a better compatibility with the internal layout

    the elevated square-based and one-storey building model was

    selected.

    A 20     20     5 m3 square-based model, selected in the

    conceptual phase, was modied with 2 m depth chamfered at the

    four vertical edges and 1 m depth chamfer at the top and bottom

    edges, to offer much better performance in reducing snowdrifts, as

    it was observed in Ref.  [11]. This model shall constitute the refer-

    ence for further optimizations of the design.

     3.2. Building-ridge integration

    After Belare-2005 expedition to Antarctica, IPF selected the area

    with the best terrain conditions for the anchoring of the building.

    This area is situated some 40 m north of the previously selected

    area for the erosion tests presented in Fig. 6. The positioning of the

    building on the ridge is constrained by the anchoring conditions on

    the rock, which are more dif cult at the lee side of the ridge due to

    an almost vertical slope. Therefore, the building can be better

    positioned with the back side on top of the ridge and some canti-

    lever upstream.

    Fig. 7 presents a sensitivity analysis of the amplication factor

    versus the integration of the reference building, considering the

    height of the clearance and the position acrossthe ridge. In the top-

    left gure, the building is at a reference position  X 0 and is elevated

    1 m from the top of the ridge. When the building is lifted to 2 m at

    Fig. 6.   Amplication factor contours for models oriented parallel (left) and at an incidence angle (right) to the incoming wind direction from SE  þ  10.

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e18   9

  • 8/20/2019 Sanz Rodrigo 2012

    10/18

    the same position (top-right gure), the deposition area is reduced.

    In the contrary, if the building is moved backwards by just 2.5 m

    (bottom-left   gure), the snow deposition area is signicantlyenhanced. This situation is partly alleviated if the elevation is

    increased to 2 m (bottom-right  gure).

    The positioning of the building across the ridge appears to be an

    important aspect for controlling snow accumulation and erosion. A

    building with larger windward cantilever offers more speed-up

    underneath producing more aggressive erosion behind the

    building. When the building is shifted backwards, the   ow   nds

    more resistance to go under it and deviates more to the sides

    producing less erosion behind the building. In both situations

    elevating the building improves the erosion. It will be explained

    later how the positioning of the building also affects the wind

    loading as both aspects are controlled by the drag of the building-

    ridge conguration.The building at 45 incidence has a   “delta wing” conguration

    generating more vorticity and hence more erosion than the

    building aligned with the incoming wind direction   [3]. This was

    also concluded by Beyers [31] from numerical CFD simulations of 

    the snowdrifts around SANAE IV station.

    The wind loading on the building will be also inuenced by its

    positioning on the ridge. To study the building-ridge integration

    from the wind loading point of view, a model of the reference

    building model was manufactured with 133 pressure taps to map

    the pressure acting on the building facades.

    Fig. 7.   Amplication factor contours for the reference building model. Sensitivity to elevation height and across-ridge positioning.

    Fig. 8.   Mean pressure coef 

    cient at reference position, with 1 m clearance and wind incidences 0

    (left) and 45

    (right). The wind direction is 101

    parallel to the X  axis.

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e1810

  • 8/20/2019 Sanz Rodrigo 2012

    11/18

    Fig. 8   shows the mean pressure coef cient distribution

    throughout the building facades, obtained by linear interpolation

    in the top and bottom faces and by nearest neighbor interpolation

    in the rest, for two wind incidences: 0 and 45. The positioning of 

    the taps is also indicated. The typical pressure build-up in the

    stagnation area of the frontal face is depicted as well as the high

    suction in the separation region at the leading edge of the top

    surface. The latter is much higher for the building oriented at 45

    wind incidence due to the formation of   “delta wing”   vortices,

    similar to the situation of ground-based buildings with   at roofs

    [28].

    The pressure map at the top surface does not vary much with

    the positioning of the building. The high suction generated at the

    leading edge is increased at higher building elevations. This is due

    to the higher surface velocities that create larger suction, as it is the

    case for ground-based buildings [29]. A slight decrease in the top

    surface suction is observed when the building is positioned back-

    wards, probably due to lower local velocities. Large suction areas

    occur very close to the roof edges in the upwind corners and is

    typically alleviated using parapets [30]. Unfortunately this remedy

    will also create snow accumulation on the roof and thus it is not

    a good solution in this case. Due to the sloping terrain, the wind

    approaches the building with a small up-ow angle. Hence, a smallnegative inclination of the roof would decrease the relative up-ow

    angle, reducing the  ow separation area and decreasing the overall

    lift on the rooftop.

    The most interesting results happen in the bottom surface,

    where the  ow interacts with the building and the ridge. Here, it

    can be noticed a positivepressure at the leading edge due tothe up-

    ow generated by the sloping terrain. Then, the pressure turns to

    negative, due to the speed-up generated by a convergent clearance,

    as the  ow approaches the ridge top. At the ridge top the speed-up

    and the suction reaches a maximum value which is then decreased

    by a divergent clearance at the rear of the building.

    Fig. 9 shows the effect of the clearance height on the pressure

    distribution on the bottom surface. The left column shows the

    sensitivity of the pressure distribution to the elevation height,when this one is set to 0, 1 and 2 m. The right column shows the

    sensitivity to the across-ridge positioning of the building, when this

    one is placed 3 m backwards, at the reference position ( X 0) and 3 m

    forward.

    When the building sits in top of the ridge (Fig. 9, top-left) a high

    blockage is created on theow under the building, which generates

    high pressure build-up and a net positive lift force on the building.

    The lift force is two times higher than the one obtained with 1 m

    clearance. Using a clearance of 2 m (Fig. 9, bottom-left) instead of 

    1 m further decreases the lift force. Even though the lift force is

    counteracted with the self weight of the building, a positive aero-

    dynamic lift will lead to vibrations on the structure, so it should be

    avoided. Owing to the ridge slope, the elevated building concept is

    not only a good solution to decrease snow deposition but alsoa more convenient conguration from the aerodynamic point of 

    view.

    The sensitivity of the positioning of the building across the ridge

    is also quite remarkable. The highest suction on the bottom face is

    alwaysgenerated at the ridge top, where theowaccelerates due to

    the contraction of the clearance. The larger the area situated at the

    ridge top the higher the suction on the bottom surface and,

    therefore, the lower the overall lift force on the building.

    4. Building envelope design

    Once the reference concept has been developed, the building

    envelope evolves with the integration of the interior layout and the

    technical systems. At this stage of the process, the internal layout

    becomes the main design driver of both the internal and external

    geometry of the base.

    The aim for a modular base, which would allow easier

    manufacturing and transportation, lead to an octagonal building.

    From the aerodynamic point of view, this geometry could be

    considered as an intermediate case between the square building at

    0 and 45 wind incidence. The integration of solar panels also

    required an inclination of the side walls of 30 for a more ef cient

    energy capture. The accommodation of some units of the system in

    the center of the building required some extra space, which was

    found by adding a second storey that sticks out of the roof. This

    add-on would also be used to give access to the roof and to

    accommodate some more solar panels.

    The new building envelope was tested using sand erosion tests.

    Fig. 10 shows the amplication factor erosion maps obtained for the

    octagonal building with the same congurations of  Fig. 7 for the

    reference building. At rst glance, it is clear that the new geometry

    is much more effective at removing snow.Indeed, the building in its

    back position and with an elevation of 2 m removes almost entirely

    all the deposition area situated behind the building, leaving only

    the two deposition tails delimiting the building wake.

    Theerosion strength is bettervisualizedwith dune tests (Fig.11).

    The visualizations reveal the formation of two dunes delimited atboth sides by erosion streams originated by the interaction of the

    vortex shedding from the edges of the building with the wake of the

    building. The two most external erosion streams are generated by

    the corner vortices generated at the front of the building. The third

    erosion stream, in between thetwo dunes, isattributed tothe vortex

    shedding from the trailing edge of the building, where the   ow

    passing underneath meets the low pressure in the wake. These two

    vortex streams arevery intense at the exit of thebuilding producing

    very intense wind shear that removes the sand on top of the garage

    roof very early in the erosion tests. The intensity of these vortices

    depends again on the speed-up generated under the building and

    hence on the building-ridge positioning.

    The dune formation tests are consistent with the surface erosion

    test: the erosion strength is more important when the building iselevated or is moved forward. Even with the very erodible sand bed

    it seems that the garage integrity is preserved because the erosion

    does not expose the garage too much in the reference building. In

    the other hand, the octagonal building presents much deeper

    snowdrifts. In effect, by reducing the surface in the back of the

    octagonal building the suction created at the ridge top is acting on

    a smaller area and the overall lift force is increased. This V shape at

    the exit of the clearance also enhances the vorticity which is the

    responsible for the strong erosion streams just behind the building.

    To cope with potential erosion problems and lift forces, the back

    of the building was modied back to its original extension, still

    leaving the inclined walls for the solar panels. Dune formation tests

    on this new building envelope are shown in   Fig. 11   (right). It is

    remarkable the important effect of the geometry at the back of thebuilding on the erosion patterns. The larger area on top of the ridge

    attenuates the trailing edge vorticity decreasing the erosion very

    signicantly.

    The new building geometry was considered denitive and no

    mayor changes were done on it. As with the reference building,

    wind loading tests were also conducted to verify the sensitivity of 

    the  nal geometry on the building positioning.

    5. Design optimization and nal assessment

    A model of the  nal building geometry, obtained at the end of 

    the envelope design phase, was instrumented with 159 pressure

    taps in order to assess the  nal wind loading specications (Fig. 5).

    This time, the positioning of the pressure taps wasdeterminedfrom

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e18   11

  • 8/20/2019 Sanz Rodrigo 2012

    12/18

    CFD simulations of the pressure distribution on the skin of the

    building. By using CFD, the uncertainty on the global forces due to

    tap resolution was reduced from 30%, in the reference building

    when CFD simulationswere not available, to 3% in thenal building

    model. The positioning of the taps and the associated uncertainty

    was estimated by comparing the integrated CFD forces obtained

    from all the grid cells of the skin and based only on the cells of the

    tap positions. The garage was also included in the   nal wind

    loading tests. The height between the garage rooftop and the ridge

    was another parameter to be tested.

    Fig. 9.  Mean pressure coef cient in the bottom face of the reference building. Sensitivity to elevation height and across-ridge positioning. The axes grid size is 10 m. Wind direction

    is 101 aligned with the building, from right to left.

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e1812

  • 8/20/2019 Sanz Rodrigo 2012

    13/18

    Fig. 11.  Dune formation tests for the reference building (left), octagonal building (center) and  nal building (right) at  X ¼ X 0 2.5 m and 2 m pillars height. The wind direction is

    101

    , parallel to the building.

    Fig. 10.   Amplication factor contours for octagonal building with inclined walls. Sensitivity to elevation height and across-ridge positioning.

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e18   13

  • 8/20/2019 Sanz Rodrigo 2012

    14/18

    Fig. 12 shows the pressure  eld on the  nal building geometry,

    this time using linear interpolation in all faces because of the better

    repartition of the pressure taps. The 

    nal geometry offers a signif-icant reduction of drag force due to a more aerodynamic shape in

    the front.

    Again, building-ridge integration was studied for the   nal

    geometry. Fig.13 shows the effectof the elevation of the building on

    drag and lift coef cients for different across-ridge positions in the

    reference building and the  nal building, which is always situated

    in the backwards position ( X 0e3 m).

    The sensitivity to the incoming ABL is also studied, with

    measurements using the smooth (snow type) and rough (urban

    type) test section. The effect on the lift and drag forces are indeednot signicant in agreement with similar studies [28,33]. However,

    the nal geometry offers 40% reduction on drag with respect to the

    reference building, due to the aerodynamic frontal shape. The drag

    decreases a further 20e30% as the building moves backwards due

    to the effect of a smaller building-ridge wake.

    The high positive lift force is also signicantly decreased when

    the reference building is shifted backwards due to the larger

    Fig. 12.   Mean pressure coef cient on  nal building model from pressure taps.

    Fig. 13.   Lift (left) and drag (right) coef 

    cients for the reference and 

    nal building models. Effect of clearance height, across-ridge positioning and incoming ABL.

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e1814

  • 8/20/2019 Sanz Rodrigo 2012

    15/18

    suction on the bottom surface. For the same reason, when the

    clearance height is increased, the lift force decreases.

    Therefore, the elevated building is not only a good solution to

    cope with snow accumulation but also a more convenient cong-

    uration, from the structural point of view, in this particular situa-

    tion in which the building is installed in sloping terrain. Above 2 mthe decrease in lift force is not very signicant, so it seems to be

    a good choice for the pillars height, also providing comfortable

    accessibility under the building. The  nal building geometry offers

    higher lift coef cient due to a lower suction under the building.

    Besides, the inclined faces on the sides, most of them under suction,

    also increase the lift.

    Having the back of the building partly on top of the garage roof 

    makes the positioning of the latter another design parameter to

    take into account.  Fig. 14  shows the inuence of the step height

    between the garage roof and the ridge top on the aerodynamic

    coef cients.

    An optimum is noticed around 1 m, with 60% lower lift and 20%

    lower drag than the position with the garage roof leveled at the

    ridge top. With a  xed step of 1 m, tilting the garage roof down bya small angle of 3.5 results in a reduction of 20% in lift and drag. In

    fact, the garage is acting as a diffuser, enhancing the speed-up

    under the building. At 9.5 garage tilt the aerodynamic forces are

    not reduced any further. This angle is close to the mean slope

    observed in the snow surface at the lee side of the ridge, which was

    the surface geometry present during the testing of the reference

    building as the garage was not included.

    Regarding wind direction variability (Fig. 15) it is remarkable

    howlow dependency is of the lift coef cient with wind direction in

    the nal building geometry. Surprisingly, the drag coef cient is the

    lowest, not at 101 when the building has a parallel orientation to

    the wind, but at 135. At 101 the ridge is perpendicular to the

    incoming wind and the frontal area offered by the building-ridge

    ensemble is the largest, producing a larger wake and thereforehigher drag. In the contrary, when the building is aligned with the

    wind direction the highest speed-up is generated under the

    building and the lowest lift is produced. The presence of the tower

    increases the drag in the SE-S sector.

    6. Evaluation of the design in the eld

    Unfortunately there are no   eld measurements that could be

    used for validation of the wind tunnel design. Nevertheless it is

    worth looking at some photos that were taken behind the Princess

    Elisabeth station during the  rst years of operation of the station

    that allow a visualization of the  nal capabilities of the building to

    cope with snowdrifts.

    Fig. 16 shows the situation of the snowdrifts behind the station

    at the arrival of the BELARE 2008e09 season in November 2008.

    The station was built in the previous season and was left inhabited

    during the winter. Therefore, the situation shown in the photo

    reects the state of the snow surface after 7 months of untouched

    snowdrift development. The situation is fairly good with a cleangarage surface and no apparent snowdrift build-up behind the

    building. As expected, the erosion patterns produced by the

    building are not as severe as showed by the volumetric sand

    erosion tests. Overall, the snowdrift aspects seem under control.

    Aiming for more energy independence, during the BELARE

    2008e09 season the station was equipped with an array of solar

    panels that covered the entire surface of the garage roof just

    behind the building. This had important consequences in the

    building aerodynamics as it is clearly noticed in the photos of 

    Fig. 17,   taken one year later, at the beginning of the BELARE

    2009e10.

    The solar panels increase the overall drag of the building and

    reduce the wind speed-up underneath. This reduces the ef ciency

    of the building aerodynamics to passively remove snowdrift. Alsosnow accumulation dunes develop and bury some of the solar

    panels increasing the maintenance works. Interestingly, the

    asymmetric development of the two snowdrift dunes also

    appeared in the wind tunnel tests, where larger accumulations

    were observed in the southern side of the building ( Fig. 11).

    The snowdrifts might be different from year to year

    depending on the interannual variability of the surface wind

    Fig. 14.   Inuence of garage roof positioning. Final building geometry with 2 m clearance height at 101 wind direction.

    Fig.15.  Lift and drag coef cients dependency on wind direction for the reference and

    nal building models.

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e18   15

  • 8/20/2019 Sanz Rodrigo 2012

    16/18

    speed. Since AWS measurements are not available during the

    operational phase of the station, ERA-Interim reanalysis data

    has been used to compute the mean 10 m wind speed in the E-

    SSE snowdrift sector over the wintering unmanned period

    AprileSeptember as a proxy to snowdrift transport. The snow

    transport can be esti mated based on the empirical

    function found during the STABLE2 experiment in Halley (Ant-

    arctica)  [34].

    Fig. 16.  Situation of snowdrifts behind the princess Elisabeth station at the beginning of BELARE 2008e09 season. Courtesy of René Robert,  International Polar Foundation,

    November 2008.

    Fig. 17.  Situation of snowdrifts behind the princess Elisabeth station at the beginning of BELARE 2009e10 season. Courtesy of René Robert,   International Polar Foundation,

    Novemeber 2009.

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e1816

  • 8/20/2019 Sanz Rodrigo 2012

    17/18

    logðQ Þ ¼   0:632U   3:69 (9)where   Q   is the snow mass   ux in g m1 s1 and   U   is the mean

    velocity. The interannual variability of the mean velocity and snow

    transport is provided in Fig. 18 in terms of anomalies, i.e. the ratio of 

    the seasonal mean to the long term seasonal mean 1989e2010.

    It is observed that the snow transport was 14% lower in 2009

    than in 2008 which means that the generation of snow build-ups

    during the 2009 winter season can be attributed to the presence of 

    solar panels rather than to changing climatological conditions.

    Snowdrift build-ups where also found at the beginning of 

    BELARE 2010e11 and 2011e12 seasons. Regardless of the large

    interannual variability between 2009 and 2010 (58% increase) the

    size of the snowdrifts was quite similar which means that the

    cumulated volume reaches a quasi-steady state within the winter

    season. Nevertheless, the main building always remains snow-freeensuring accessibility. The maintenance works for removing the

    snow around the solar panels and garage entrance take a few days

    at the beginning of each season as reported in the station’s website.

    7. Conclusions

    The integrated design of an Antarctic building requires careful

    consideration of the environmental conditions in which it will be

    immersed. The conceptual design requires a rapid prototyping

    process where the sand erosion technique proves useful to assess

    snowdrift and wind conditions around different building concepts.

    Dune formation tests help visualizing the erosion strength of the

    building wake around the under-snow garage. Sand erosion and

    wind loading tests showed the high sensitivity of the aerodynamicsof the building with the positioning on the ridge, all controlled by

    the behavior of the  ow under the building.

    The envelope and optimization design phases were also sup-

    ported with wind tunnel testing and CFD modeling aiding the

    decision making process until the assessment of the  nal design.

    The aerodynamic shape of the   nal building results in 40% drag

    reduction. The overall forces can be further lowered by using the

    garage roof as a diffuser. Increasing the trailing edge area by

    introducing a step between the ridge top and the garage rood

    results in 60% lower lift and 20% lower drag. A small inclination of 

    the roof by 3.5 reduced further lift and drag by 20%.

    After therst years of operation of the Princess Elisabeth base, it

    can be concluded that the station can effectively cope with snow-

    drift, producing no signi

    cant impact in the snow patterns behind

    the ridge as predicted by the wind tunnel sand erosion tests and

    conrmed with measurements of the snow surface topography

    before and after the construction of the building  [25].

    This study constitutes a good example of the advantages of 

    including wind engineering since the beginning of the integrated

    building design process, giving the opportunity to consider the

    most effective use of the environment while achieving important

    structural and maintenance savings by carefully selecting the

    optimum positioning and shape of the building.

    References

    [1] Belgian Science Policy and International Polar Foundation, 2007, Constructionand operation of the New Belgian Research Station, Dronning Maud Land,Antarctica. Final Comprehensive Environmental Evaluation (CEE), May 2007.

    [2] Gorlé C, Sanz Rodrigo J, van Beeck J. Design of Belgian polar base: CFD analysisand validation, ICWE-12 proceedings, Cairns (Australia); July 2007.

    [3] Sanz Rodrigo J. On Antarctic wind engineering, PhD thesis, Université Libre deBruxelles, Belgium; 2011.

    [4] Delpech P, Palier P, Gandemer J. Snowdrifting simulation around Antarcticbuildings. J Wind Eng Ind Aerodyn 1998;74e76:567e76.

    [5] Waechter BF, Williams CJ. Snowdrift design guidance for the New South PoleStation. Proceedings of the 10th international conference on cold regionsengineering. New Hampshire (USA); August 1999.

    [6] Beyers JHM, Harms TM. Outdoors modelling of snowdrift at SANAE IV research station, Antarctica. J Wind Eng Ind Aerodyn 2003;91:551e69.

    [7] Leitl B, Schatzmann M, Baur T, Koening-Langlo G. Physical modeling of snowdrift and wind pressure distribution at the proposed German Antarctic StationNeumayer III. In: Proceedings of OMAE2006, Hamburg (Germany); June 2006.

    [8] Kim DH, Kwok KCS, Smedley DJ, Rhode HF. Modelling of snowdrift aroundprismatic buildings for Antarctic environment. Int J Offshore Polar Eng. ISOPE1992;2(1):73e9.

    [9] Kwok KCS, Kim DH, Smedley DJ, Rohde HF. Snowdrift around buildings forAntarctic environment. J Wind Eng Ind Aerodyn 1992a;41e44:2797e808.

    [10] Kwok KCS, Smedley DJ, Kim DH. Snowdrift Around Groups of AntarcticBuildings, 11th Australasian   uid mechanics conference, University of Tasmania, Hobart, Australia; 1992.

    [11] Kwok KCS, Smedley DJ. Snowdrift around Antarctic buildings   e   effects of corner geometry and wind incidence. Int J Offshore Polar Eng ISOPE 1993;13:61e5.

    [12] Kind RJ. Snow drifting. In: Gray DM, Male DH, editors. Handbook of snow,principles, processes, management and use. Toronto: Pergamon Press; 1981.

    [13] Kind RJ. A critical examination of the requirements for model simulation of wind-induced erosion/deposition phenomena such as snowdrifting. Atmos

    Environ 1976;10:219e

    27.[14] Anno Y. Requirements for modeling of snow drift. Cold Regions Sci Technol

    1984;8:241e52.[15] Haehnel, Lever JH. Scaling snowdrift development rate, In: 52th Eastern snow

    conference, Toronto, Ontario, Canada; 1995.[16] Simiu E, Scanlan RH. Wind effects on structures: an introduction to wind

    engineering. New York: John Wiley and Sons; 1978. p. 468.[17] Beranek WJ, van Koten H. Visual techniques for the determination of wind

    environment. J Wind Eng Ind Aerodyn 1979;4:295e306.[18] Livesey F, Inculet D, Isyumov N, Daveport AG. A scour technique for the

    evaluation of pedestrian winds. J Wind Eng Ind Aerodyn 1990;36:779e89.[19] Dezsö G. On assessment of wind confort with sand erosion. Ph.D. thesis,

    University of Eindhoven, The Netherlands; 2006.[20] Viegas DX, Janerio Borges AR. An erosion technique for the measurement of 

    the shear stress  eld on a  at plate. J Phys E Sci Instrum 1986;19:625e30.[21] van Beeck J, Dezs}o G, Planquart Ph. Microclimate assessment by sand erosion

    and Irwin probes for atmospheric boundary layer wind tunnels. In: Conf. Proc.on physical modelling of   ow and dispersion phenomena, PHYSMOD2009,24e26 Aug. 2009, von Karman Institute for Fluid Dynamics, Sint-Genesius-

    Rode, Belgium, pp. I.3.1e

    I.3.8.[22] Jaedicke C. Drifting snow and snow accumulation in complex arctic terrain.

    Ph.D. thesis, Geographical Institute, University of Bergen; 2001.[23] Li L, Pomeroy JW. Estimates of threshold wind speed for snow transport using

    meteorological data. J Appl Meteorol 1997;36:205e13.[24] Mann GW, Anderson PS, Mobbs SD. Prole measurements of blowing snow at

    Halley, Antarctica. J Geophys Res 2000;105:24491e508.[25]   PattynF, Matsuoka K, BerteJ. Glacio-meteorologicalconditions in the vicinity of 

    the Belgian princess Elisabeth station, Antarctica. AntarcticSci 2010;22:79e85.[26] Uematsu Y, Isyumov N. Wind pressures acting on low-rise buildings. J Wind

    Eng Ind Aerodyn 1999;82:1e25.[27] EN 1991 Eurocode 1 actions on structures, Part 1e4: General actions e  wind

    actions, 2008, European Standard.[28] Bienkiewicz B, Sun Y. Local wind loading on the roof of a low-rise building.

     J Wind Eng Ind Aerodyn 1992;45:11e24.[29] Gerhardt HJ, Kramer C. Effect of building geometry on roof windloading.

     J Wind Eng Ind Aerodyn 1992;41e44:1765e73.[30] Kind RJ. Worst suction near edges of  at rooftops with parapets. J Wind Eng

    Ind Aerodyn 1988;31:251e

    64.

    Fig. 18.  Mean velocity and snow transport anomalies with respect to the long term

    period 1989e2010 considering the wintering unmanned season AprileSeptember and

    the prevailing wind direction E-SSE.

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e18   17

  • 8/20/2019 Sanz Rodrigo 2012

    18/18

    [31] Beyers JHM. Numerical modelling of the snow   ow characteristicssurrounding SANAE IV Research Station, Antarctica. Phd Thesis, South Africa;2004.

    [32] Tamura Y, Ohkuma T, Okada H, Kanda J. Wind loading standards and designcriteria in Japan. J Wind Eng Ind Aerodyn 1999;83:555e66.

    [33] Tieleman HW, Hajj MR, Reinhold TA. Wind tunnel simulation requirements toassess wind loads on low-rise buildings. J Wind Eng Ind Aerodyn 1998;74e76:675e85.

    [34] Dover AJ. Numerical modeling of blowing snow. Ph.D. thesis, Dept. of AppliedMaths, University of Leeds, Leeds, UK; 1993.

     J. Sanz Rodrigo et al. / Building and Environment 52 (2012) 1e1818