Model FB-SHorizontal
Steam Boiler
60 - 400 BHP
7/23/2019 CALDEROS HORIZONTALES
2/8
Operating Principal
The FB-S is a traditional three-pass horizontalfiretube boiler. The first pass flows through thefurnace from front to back. The furnace iscorrugated to maximize efficiency while alsominimizing thermal stress.
The second and third passes travel through heavy
duty seamless tubes. Flue gasses travel first fromthe combustion furnace to the front chamberforming the second pass. The gases then flow
through the third pass tubes to the back of theboiler stack and out the exhaust vent, locatedconveniently in the back of the boiler.
Featuresa few of the
Compact design minimizes Footprint
Seamless tubes 15% thicker than
competitors
Corrugated Furnace
Large Water Content
Generous Heating Surface
Three year pressure vessel warranty
7/23/2019 CALDEROS HORIZONTALES
3/8
Fulton boilers are used in a variety ofapplications throughout the industry. Food,plastic and chemical processing as well aspharmaceutical and bio-fuel production are
only a few of the many existing applicationsusing Fulton.
Large scale laundry applications rely on FultonFB-S boilers every day to provide a steadysupply of steam, which is critical for theirbusiness.
Fulton horizontal boilers can often be found in
many large building heat applications - such asschools and government buildings - where areliable source of heat is crucial.
Applicationsa wide range of
Bio-Fuel
Laundry
Building Heat
7/23/2019 CALDEROS HORIZONTALES
4/8
C
D
A
B
E
A
B
C
D
Rear stack connection for easy venting.
Multiple banks of heavy gauge seamlessboiler tubes used in the second and thirdflue pass ensure durability.
Water-backed design eliminates heavyrefractory on rear door while increasingefficiency and reducing radiant heat loss.
Large water volume and generous steamchamber ensure low sensitivity to load
change and pressure vessel stability.
The combustion chamber is locatedbelow the water level and with enoughclearance from the bottom of the boiler toallow for optimal water circulation. Thelow placement of the combustionchamber provides an additional buffer
between the furnace and the water level,providing higher quality steam.
7/23/2019 CALDEROS HORIZONTALES
5/8
Insidetake a look
F
EF
The large diameter corrugatedcombustion chamber provides a generous
heating surface area. This enhances heattransfer while reducing heat flux.
In addition to reinforcing the overallstrength of the combustion chamber, thecorrugation also increases the longevity ofthe pressure vessel. This is due to asubstantial reduction in thermal and
mechanical fatigue caused by cyclicalexpansion and contraction.
The large surface area of the burnerinitially reduces exit temperatures through
enhanced radiation and convection.Radiant heat losses from the gas chamberare then minimized by heavy insulation onthe front door. This also helps to reducethe temperature of the front door.
The gas chamber is air insulated to reduceheat exchange loss. Though it is not a partof the pressure vessel, it does play acrucial role in the boiler design.
Fully modulated oil, gas
or combination burner.(open protocol)
7/23/2019 CALDEROS HORIZONTALES
6/8
Specifications
Models FB-S 60 100 150 200 250 300 400BHP 60 100 150 200 250 300 400
Max Operating Pressure * PSI 150 150 150 150 150 150 150
BAR 10.3 10.3 10.3 10.3 10.3 10.3 10.3
Steam Output LBS/HR 2,204 3,306 4,409 6,612 8,816 9,918 13,224
KG/HR 1,000 1,500 2,000 2,999 3,999 4,499 5,998
Approximate Fuel UsageLight Oil ** GPH 19 28 37 56 75 84 112
LPH 72 106 140 212 284 318 424Natural Gas ** FT3/HR 2,705 4,058 5,378 8,122 10,806 11,936 15,715
M3/HR 77 115 153 230 306 338 445
ConnectionsSafety Relief Valve IN 2 2 2 2 2 2.5 3
MM 51 51 51 51 51 64 76
Steam Outlet (150 lb flange) IN 2 2.5 3 4 4 4 5
MM 51 64 76 102 102 102 127
Feedwater inlet IN 1.25 1.25 1.25 1.25 1.5 1.5 2
MM 32 32 32 32 38 38 51
Blowdown IN 1.5 1.5 1.5 2 2 1.5 2
MM 38 38 38 51 51 38 51
Water Column Blowdown IN 0.5 0.5 0.5 0.5 0.5 0.5 0.5
MM 13 13 13 13 13 13 13
Stack Diameter IN 12 14 16 18 20 20 24
MM 305 356 381 457 508 508 610
PowerBurner Motor (Oil) BHP 2 3 7.5 15 15 15 20
KW 1.5 2.2 4.5 7.5 7.5 7.5 15
Burner Motor (Gas) BHP 2 3 7.5 15 20 20 20
KW 1.5 2.2 4.5 7.5 15 15 15
* Please consult factory for alternate operating pressures.
** Please consult factory for additional fuel options.
Specifications and Dimensions are approximate. Consult factory for model specific electrical requirements.
We reserve the right to change specifications and/or dimensions without notice.
Detailstechnical
7/23/2019 CALDEROS HORIZONTALES
7/8
Dimensions
Models FB-S 60 100 150 200 250 300 400BHP 60 100 150 200 250 300 400
A. Boiler Length (w/o burner) IN 131 143 161 188 195 236 218
MM 3,327 3,632 4,089 4,775 4,953 5,994 5,537
B. Boiler Length (w/ burner) IN 173 185 207 234 246 286 270
MM 4,394 4,699 5,258 5,944 6,248 7,264 6,858
C. Boiler Width (w/ trim) IN 67 70 83 86 86 86 106
MM 1,702 1,788 2,108 2,184 2,184 2,184 2,692
D. Boiler Height (w/ trim) IN 77 80 92 98 100 100 118
MM 1,956 2,032 2,337 2,489 2,540 2,540 2,997
E. Door Opening IN 32 34 36 36 43 43 46
MM 813 837 914 914 1,092 1,092 1,168
Approximate WeightsShipping Weight LB 9,460 11,330 14,300 20,240 25,564 28,786 38,126
KG 4,291 5,139 6,486 9,181 11,596 13,057 17,294
Operating Weight LB 14,972 17,827 22,006 31,032 38,783 44,207 56,407
KG 6,791 8,086 9,982 14,076 17,592 20,052 25,586
Water Content GAL 661 779 924 1,294 1,585 1,849 2,192
LITERS 2,500 2,950 3,500 4,900 6,000 6,998 8,297
Specifications and Dimensions are approximate. We reserve the right to change specifications and/or dimensions without notice.
A
B
E
C
D
7/23/2019 CALDEROS HORIZONTALES
8/8
www.fulton.comFulton is a global manufacturer of steam,
hot water & thermal fluid heat transfer systems.
FB-S IC BRO
051007
Printed in USA
The Fulton Companies3981 Port Street
Pulaski, NY 13142
Call: (315) 298-5121
Fax: (315) 298-6390
Recommended