Accepted Manuscript Experimental results with a variable geometry ejector using R600a as working fluid Paulo R. Pereira, Szabolcs Varga, João Soares, Armando C. Oliveira, António M. Lopes, Fernando G. de Almeida, João F. Carneiro PII: S0140-7007(14)00166-2 DOI: 10.1016/j.ijrefrig.2014.06.016 Reference: JIJR 2822 To appear in: International Journal of Refrigeration Received Date: 25 March 2014 Revised Date: 11 June 2014 Accepted Date: 29 June 2014 Please cite this article as: Pereira, P.R., Varga, S., Soares, J., Oliveira, A.C., Lopes, A.M., de Almeida, F.G., Carneiro, J.F., Experimental results with a variable geometry ejector using R600a as working fluid, International Journal of Refrigeration (2014), doi: 10.1016/j.ijrefrig.2014.06.016. This is a PDF file of an unedited manuscript that has been accepted for publication. As a service to our customers we are providing this early version of the manuscript. The manuscript will undergo copyediting, typesetting, and review of the resulting proof before it is published in its final form. Please note that during the production process errors may be discovered which could affect the content, and all legal disclaimers that apply to the journal pertain.

Experimental results with a variable geometry ejector

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Experimental results with a variable geometry ejector

Accepted Manuscript

Experimental results with a variable geometry ejector using R600a as working fluid

Paulo R. Pereira, Szabolcs Varga, João Soares, Armando C. Oliveira, António M.Lopes, Fernando G. de Almeida, João F. Carneiro

PII: S0140-7007(14)00166-2

DOI: 10.1016/j.ijrefrig.2014.06.016

Reference: JIJR 2822

To appear in: International Journal of Refrigeration

Received Date: 25 March 2014

Revised Date: 11 June 2014

Accepted Date: 29 June 2014

Please cite this article as: Pereira, P.R., Varga, S., Soares, J., Oliveira, A.C., Lopes, A.M., de Almeida,F.G., Carneiro, J.F., Experimental results with a variable geometry ejector using R600a as working fluid,International Journal of Refrigeration (2014), doi: 10.1016/j.ijrefrig.2014.06.016.

This is a PDF file of an unedited manuscript that has been accepted for publication. As a service toour customers we are providing this early version of the manuscript. The manuscript will undergocopyediting, typesetting, and review of the resulting proof before it is published in its final form. Pleasenote that during the production process errors may be discovered which could affect the content, and alllegal disclaimers that apply to the journal pertain.

Page 2: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

1

Experimental results with a variable geometry ejector

using R600a as working fluid

Résultats expérimentaux avec un éjecteur à géométrie variable utilisant R600a comme réfrigèrent

Paulo R. Pereira, Szabolcs Varga*, João Soares, Armando C. Oliveira, António M.

Lopes, Fernando G. de Almeida, João F. Carneiro

Department of Mechanical Engineering

Faculty of Engineering, University of Porto

Rua Dr Roberto Frias, 4200-465 Porto – Portugal

* corresponding author

e-mail: [email protected]

Phone: +351 220414366

Fax: +351 225082153

Page 3: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

2

Abstract

Experimental results with the first laboratory scale variable geometry ejector (VGE)

using isobutane (R600a) are presented. Two geometrical factors, the area ratio and the

nozzle exit position, can be actively controlled. The control of the area ratio is achieved

by a movable spindle installed in the primary nozzle. The influence of the spindle

position (SP) and condenser pressure on ejector performance are studied. The results

indicate very good ejector performance for a generator and evaporator temperature of 83

ºC and 9 ºC, respectively. COP varied between 0.4 and 0.8, depending on operating

conditions. The existence of an optimal SP, depending on the back pressure, is

identified. A comparison of the benefit of applying the variable geometry design over a

fixed geometry configuration is assessed. For example, for a condenser pressure of 3

bar, an 80% increase in the COP was obtained when compared to the performance of a

fixed geometry ejector.

Keywords: Ejector cooling system; Variable geometry design; Experimental work; Performance enhancement.

Mots-clés: Système de refroidissement par éjecteur; Conception à géométrie variable;

Travaux expérimentaux; Amélioration de la performance.

Symbols

COP coefficient of performance

Page 4: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

3

diameter (m)

mass flow rate (kg s-1)

NXP nozzle exit position (mm)

pressure (bar)

heat (kW)

area ratio,

temperature (°C)

Greek letters

λ entrainment ratio

Subscripts

condenser

critical

diffuser

evaporator

heat generator

constant area section

primary nozzle throat

Page 5: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

4

primary nozzle exit

1. Introduction

The increased demand on human thermal comfort has led to a massive growth of air

conditioning applications over the last two decades, in both developed and developing

countries. In order to counteract its negative effect on electricity consumption, the

development of efficient and reliable thermally driven cooling systems seems to be a

logical solution, especially in the context of supplying the necessary heat from already

available solar collectors. Ejector cooling fits well into these requirements, since

ejectors are simple in construction, they have long durability and require little

maintenance. This has been realised by many researchers, and a significant effort has

been dedicated to improve ejector cooling efficiencies since the mid-nineties. A recent

review on the advances of ejector technology can be found in Chen et al. (2013).

Such as most thermally driven cooling cycles, ejector refrigeration is strongly

influenced by operating conditions and the properties of the working fluid. The

influence of working temperatures and pressures on ejector cooling cycle performance

is relatively well established. Several experimental (e.g. Chunnanond and Aphornratana,

2004b; Selvaraju and Mani, 2006; Yapıcı et al., 2008) and theoretical works have been

carried out (e.g. Hemidi et al., 2009; Huang et al., 1999; Varga et al., 2009a) to assess

the effect of generator, evaporator and condenser conditions. Comparative studies of

cooling performance using different refrigerants are limited to theoretical analyses, such

as in (Sun, 1999) and (Cizungu et al., 2001). More recently, studies (Roman and

Page 6: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

5

Hernandez, 2011; Varga et al., 2013b) that involved the analysis of hydrocarbon

refrigerants, for ejector cooling, such as R600a, concluded that they provide high

performance; however, precautions should be taken into consideration due to their

flammability.

Ejector design, for a given working fluid and cooling capacity, has a strong dependence

on the operating conditions (Varga et al., 2009b; Yapıcı et al., 2008). In other words, an

ejector with fixed geometry only works with high COP in a narrow range of operating

temperatures/pressures, called design conditions. Operating conditions influence ejector

geometry mostly through the area ratio, rA (ratio between the constant area section and

primary nozzle throat area). A potential solution to this problem has led to the concept

of a variable geometry ejector (VGE). Sun (1996) was one of the first authors analysing

geometrical requirements for an ejector using water as working fluid. Recently, Dennis

and Garzoli (2011) presented research results of a VGE using R141b under variable

operating conditions. In both cases the advantages of the concept were clearly

demonstrated; however, no technical solutions were given. Potential technical

implementations for controlling the area ratio can be found in Kim et al. (2006) for air;

in Elbel and Hrnjak (2008) for carbon dioxide (R744); and in Ma et al. (2010) and

Varga et al. (2011) for water as the working fluid. The use of air as a working fluid has

a very limited application in refrigeration. R744 has a very low critical temperature and

high critical pressure; therefore, its use requires adequate technical features and robust

construction that would contribute to an increase in the initial cost of the cooling

system. Water has been used widely as a refrigerant in ejector cooling; however, it has

the disadvantage of resulting in relatively low COPs for moderate generator

Page 7: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

6

temperatures, which is the case when using low-cost solar collectors as primary heat

source (Varga et al., 2013b).

Numerical studies with hydrocarbon refrigerants (e.g. Roman and Hernandez, 2011),

such as R600a (e.g. Pridasawas and Lundqvist, 2007), have shown that a good cooling

cycle performance can be achieved, even for moderate generator temperatures (80 – 90

ºC). Although R600a is already widely used in domestic refrigerators, because of the

flammable nature of R600a there is only a very limited number of experimental

investigations regarding ejector cooling. According to the authors’ knowledge, until this

date the only experimental investigations with R600a in an ejector cooling system were

presented by Butrymowicz et al. (2012) and Butrymowicz et al. (2013). In these works

relatively low COPs were obtained (~0.15); however, the generator temperatures

applied were also very low (63.5 ºC). In a previous study, Varga et al. (2013a)

developed a CFD model to assess the benefit of a VGE design for an R600a ejector.

Predicted entrainment ratios varied in a wide range (0.15 – 0.65) depending on the

operating conditions. It was concluded that installing a spindle in the primary nozzle

could lead to increased ejector performance, with an increase as high as 177% for low

condenser pressures, when compared to a fixed geometry design. Based on these

findings, an R600a ejector prototype with variable geometry was developed and

installed in a test rig. The ejector geometry can be actively controlled by changing the

area ratio through a movable spindle and by changing the nozzle exit position. The

present work summarises the first results obtained with the experimental setup. The

benefit of applying a variable geometry over a fixed geometry is experimentally

demonstrated for the first time.

Page 8: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

7

2. Experimental Setup

The experimental ejector test rig is composed by: i) the ejector refrigeration cycle with

the variable geometry ejector; plus three sub-cycles, which are: ii) one on the high

temperature side connected to the generator; iii) one on the low temperature side

connected to the evaporator; and iv) one on the heat dissipation side connected to the

ejector cycle condenser, as shown in Fig. 1. The objective of the three sub-cycles (ii-iv)

was to simulate operational conditions, so that the heat transfer in the generator,

evaporator and condenser can be independently controlled.

In the ejector cycle, the motive (primary) fluid is pressurized according to the desired

saturation temperature by using a magnetic drive sliding vane pump (Gemmecotti,

Italy). The desired pressure was set by adjusting the pump velocity with a general

purpose frequency inverter. Upstream to the fluid circulating pump (after the condenser)

a vapor separator was installed in order to assure that the working fluid enters on the

suction side in liquid state. In addition, the pump was placed at the lowest location of

the rig in order to prevent cavitation problems. From the pump, the high pressure

motive fluid enters the generator that is connected to the external heat source (electric

heater). The generator is composed by two plate heat exchangers (Alfa Laval, Sweden).

In the first one, the motive fluid receives energy mostly in the form of sensible heat,

while it leaves the second heat exchanger with a small amount of superheat (~ 5 - 15

ºC). The primary fluid is led to the variable geometry ejector where it mixes with the

secondary stream coming from the evaporator. A more detailed discussion of the VGE

is presented in Section 3. The mixed R600a vapour leaving the ejector is condensed in

another plate heat exchanger (Alfa Laval, Sweden) connected to a water chiller. On the

Page 9: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

8

low pressure side of the ejector, there is an expansion valve (Swagelok, USA), that is

manually adjusted to the desired evaporator pressure. The cooling effect is obtained in

the evaporator also with a plate type configuration (Alfa Laval, Sweden). All the

installation, including connecting pipes was supplied with thermal insulation (Armacell,

Germany), in order to minimize heat losses.

The high temperature heat source, supplying the thermal energy for the generator of the

cooling cycle, was a 6 kW electric temperature controller (SHINI, Taiwan). It can

produce high temperature pressurized water up to 120 °C. A thermal bath (JULABO,

Germany), with a heating capacity of 2 kW was used to simulate the thermal load in the

evaporator. The condenser was connected to a water chiller of about 1.4 kW cooling

capacity. The water chiller is equipped with a cold water tank of approximately 150 l to

provide steady state operation for a given period of time.

In order to monitor the system variables along the ejector cycle, a number of

instruments were installed including: pressure transducers (Kobold, Germany) with 6

and 25 bar measuring range and an accuracy of 0.5% of the full scale; calibrated T-type

thermocouples (Tecnisis, Portugal) with a maximum error of 0.35 °C; RTDs (KIMO,

France) with 0 to 100 °C range and an accuracy of ±0.08 °C; and two variable area flow

meters (Kobold, Germany) with an accuracy of 2.2% of the full scale. Additionally, the

water temperature at the inlet and outlet of both the generator and the evaporator sub-

cycles were measured in order to evaluate the global performance of the system. The

water flow rate through the generator was monitored with a high precision

electromagnetic flow meter (ABB, USA) with an accuracy of 0.5% of the read value.

Page 10: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

9

On the evaporator side, the water flow rate was constant (13.3 l/min) and it was

manually determined by measuring the displaced water volume with a chronometer

(estimated error of 3%). For the locations of the installed sensors the reader is referred

to Fig. 1. The data acquisition system integrated a data logger module (HP Agilent

34970A, USA) connected to a personal computer. A control and monitoring application

was developed in LabVIEW 2011 (National Instruments, USA). The data were sampled

every 10 s and saved in a text file for data analysis, carried out in MS Excel and

Engineering Equation Solver (EES) (F-Chart, USA). A general overview of the rig with

its key components is presented in Fig. 2.

3 Ejector Operation and VGE design

The key component of the experimental setup, and the heart of the refrigeration cycle, is

the ejector. The schematic cross section of a typical ejector is shown in Fig. 3. The high

pressure stream (motive or primary fluid) coming from the generator (g) enters the

primary nozzle at low velocity (Varga et al., 2013a). Because of the converging section,

the primary flow gets accelerated and choked in the nozzle throat (dt). In the divergent

section, the stream is expanded such that it fans out from the primary nozzle to the

suction chamber typically with supersonic speed and low static pressure (Chunnanond

and Aphornratana, 2004a; Varga et al., 2013b). At this condition there is a difference

between the pressure at the mixing chamber and the evaporator (Chen et al., 2014), the

former being lower. This pressure difference draws the secondary fluid from the

evaporator (e) into the mixing chamber. Due to the velocity difference between the two

fluids and the resulting shear, the secondary stream gets accelerated. Under normal

conditions, the secondary fluid starts mixing with the primary fluid after it gets choked.

Page 11: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

10

Due to the interaction of both fluid streams and the ejector wall, the mixing process

downstream the nozzle exit plane is rather complex. The flow of the primary jet can be

characterized by a series of oblique/normal shock waves, known as the shock train

(Bartosiewicz et al., 2006; Bouhanguel et al., 2011). During this process, the static

pressure of the motive stream gradually increases and levels with the pressure of the

secondary fluid. Somewhere in the constant area section, or in the beginning of the

diffuser (depending on operation conditions), the mixing process completes and a final

shock occurs. From there, the flow essentially becomes subsonic and thus the increasing

cross section of the diffuser leads to deceleration of the mixed streams and to a

simultaneous increase of the static pressure. The exit pressure is governed by the

condenser (c) conditions (ejector back pressure/temperature).

Entrainment ratio (λ) and cooling cycle COP are the most important global performance

indicators for characterising an ejector. The entrainment ratio is defined as:

(1)

In the experimental test rig, the flow meters measured the volumetric flow rates of the

secondary and the mixed streams at evaporator outlet and at condenser inlet,

respectively (see Fig. 1). The conversion to mass flow rate was carried out by

determining the fluid density, based on the pressure and temperature readings at the

same locations, and using the property functions of EES. Additionally, the primary mass

Page 12: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

11

flow rate was obtained through the difference between mass flow rates of the mixed

stream and the secondary fluid. Once λ is determined, COP was obtained by:

(2)

In Eq. 2 the enthalpy change in the evaporator (∆he) and in the generator (∆hg) were

determined using EES physical property functions with the measured pressure and

temperature data. Note that in Eq. 2, it is assumed that the pump energy consumption is

negligible.

As all thermally driven cooling technologies, the ejector cycle has a strong dependence

between its performance and the operational conditions, i.e. the generator, evaporator

and condenser temperatures (Varga et al., 2013b). This is particularly important for the

generator temperature in the context of solar driven ejector cooling systems, where

temperature oscillations are expected during operation. For instance, when a fixed

geometry ejector is designed to operate at Tg=90 °C, for any higher value, the primary

flow rate increases, leading to a decrease in the entrainment ratio. This decrease is a

combined effect of the increased primary mass flow (larger heat input), and also the fact

that the primary stream leaves the nozzle slightly under-expanded, which results in

decreasing the secondary mass flow (reduced cooling). In contrast, a decrease in the

generator temperature results in insufficient momentum transfer, and thus mixing

between the two streams, leading to poorer ejector performance (Yapıcı et al., 2008).

Page 13: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

12

Regarding the condenser temperature (pressure), the performance of the ejector cooling

system is limited by the critical back pressure (pc,cr) (Chunnanond and Aphornratana,

2004a). Fig. 4 presents a typical operating curve of an ejector where the entrainment

ratio is depicted with the condenser pressure, at specified generator and evaporator

temperatures. It is possible to distinguish two operating regimes depending on the

condenser pressure. In the double choking region, the entrainment ratio is constant and

independent from condenser pressure. This can be explained by the choking of the

secondary flow in the ejector tail (Varga et al., 2013a), namely that when a gas flow is

chocked, the mass flow rate is only dependent on the upstream condition. In contrast, in

the single choking region the secondary flow remains subsonic, its mass flow rate

depends on both upstream and downstream conditions and thus λ quickly falls with pc.

The boundary between the two regions is defined as the critical condenser pressure

(back pressure) and it can be considered as another performance parameter. The higher

pc,cr is, the wider the range of condenser pressures at which the ejector operates with

constant performance. Since beyond pc,cr, the secondary flow is not choked, ejector

operation depends also on downstream conditions, and thus the pressure in the mixing

chamber increases with condenser pressure. Eventually, it can be higher than evaporator

pressure, leading to a reverse flow on the secondary side of the ejector, and thus ejector

failure (see Fig. 4) (Allouche et al., 2014). Regarding the evaporator temperature

(pressure), an increase in pe results in higher secondary mass flow rate and consequently

in an increase of both entrainment ratio and COP. It should be noted that the critical

condenser pressure also increases with evaporator pressure (Chunnanond and

Aphornratana, 2004a).

Page 14: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

13

Considering the benefits presented in the introduction, a variable geometry ejector

prototype was developed. The variable geometry is achieved by active control of: i) the

nozzle exit position (NXP) in the converging part of the ejector tail; and ii) the area

ratio, with a movable spindle that changes the primary nozzle cross section on the high

pressure side of the nozzle throat. These two degrees of freedom can be independently

set, allowing a full adaptation to the operating conditions. The desired position of the

spindle (SP) and NXP can be adjusted by two actuators driven by small stepper motors.

Fig. 5 presents a schematic view of the flow channel of the ejector prototype with its

characteristic dimensions, including NXP and SP. As can be seen from Fig. 5, the

spindle can travel forward to a position where it completely blocks the free passage for

the primary fluid, by touching the primary nozzle wall. This position was considered the

zero position. Thus, each SP (in mm) was referred to this zero position when moving

the spindle upstream. Likewise, the nozzle exit can be moved upstream into the mixing

chamber, up to a point when there is no free cross section available for the secondary

flow. This was considered again as zero for the NXP. A given position is measured

upstream from this zero position (in mm).

4. Experimental Procedure and Data Analysis

The main objective of the present experimental approach is to demonstrate the

performance benefits of the variable geometry ejector prototype, based on operating

conditions and spindle position. In this preliminary work, a series of experiments were

carried out by using constant generator and evaporator conditions, with controlled

temperatures of 85 °C and 15 °C in the electric heater and the thermal bath respectively,

for several spindle positions. Due to some limitations inherent to the capacity of the

Page 15: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

14

pump and the high temperature heat source, it was only possible to collect experimental

data for a range of spindle positions between 3.75 to 6.25 mm, representing an area ratio

variation ranging from 9.6 to 5.4. During these tests, the nozzle exit position has been

fixed at 3 mm. This position was previously found to provide the lowest pressure on the

suction side of the ejector, by changing NXP while maintaining constant generator

conditions and the expansion valve closed. In order to make sure that both SP and NXP

are in the correct position during each run, both variables were set to zero (fully closed)

and then retracted to the desired set points using the stepper motors. Each experiment

started when the temperature of the working fluid at the primary inlet of the ejector

reached steady state, at approximately 83 °C (approx. 15 ºC superheat) and pressure of

about 10 bar. At the outlet, the condenser pressure always started below the critical back

pressure by adjusting the condenser temperature with the water chiller in the beginning

of the test run. During the test, it was allowed to increase constantly beyond pc,cr. This

way, the entire operating curve of the ejector could be determined, identifying double

choking, critical operation and single choking regimes in a single experimental run. The

expansion valve was adjusted to set an evaporator pressure of about 2 bar, resulting in

an evaporator temperature of approximately 9 °C (with 2 °C of superheat).

Each experimental run was stopped when one of the recorded flow rates became smaller

than the minimum range indicated for the flow meters. The data were then analyzed

according to the ejector flow regimes. Mass flow rates and enthalpies were calculated

from the measured data using EES. Below the critical back pressure, both and

remained constant, and so did the performance parameters (COP and λ). Here, the

ejector performance was assessed by simple arithmetic average. Beyond the critical

back pressure, the ejector operates in single choking regime, with decreasing secondary

Page 16: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

15

mass flow rate, COP and λ. In this regime, a linear regression line for the COP and λ as

a function of back pressure (temperature) was fitted. Then, the critical back pressure

was determined by intersecting this regression line with average values of the double

chocking regime (see Fig. 4).

5. Results and Discussion

Fig. 6 shows the experimental cooling cycle COP as a function of condenser pressure,

for a spindle position of 5.00 mm (Tg=83 °C, Te=9 °C). It can be seen from Fig. 6 that

the critical back pressure was approximately 3.48 bar, corresponding to a condensation

temperature of 24.8ºC. Below pc,cr, COP was approximately constant with a value of

about 0.58. This corresponds to an entrainment ratio of 0.72 and a cooling capacity of

1.52 kW. Beyond the critical back pressure, ejector performance fell quickly, with a

COP as low as 0.2 for a condenser pressure of 3.9 bar (Tc=28.7ºC).

It is important to note that the entrainment ratio follows the same evolution as COP. The

spindle tip position influences the primary nozzle throat area and thus affects . Fig. 7

presents the steady state primary and secondary mass flow rates as function of spindle

position, for constant generator and evaporator pressures/temperatures. Additionally, a

line representing the equivalent fixed geometry ejector primary mass flow rate is

indicated. When the spindle traveled between 3.75 and 5.25 mm, the mass flow rate

variation was almost constant (linear) leading to an overall increase of about 74 %.

When SP was varied between 5.25 to 5.75 mm, the change in was only about 5%.

This latter variation was within the range of the accuracy of the flow meters, and

Page 17: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

16

therefore it can be concluded that a further increase in SP had almost no influence on

. One may also observe that was kept almost constant around 5.5 g/s, for all

spindle positions.

The determination of the operating curve (e.g. in Fig. 6) was carried out for all the

spindle positions within the considered range. Fig. 8 depicts the results obtained for

spindle positions from 4 to 6 mm, with constant Tg and Te of 83 °C and 9 °C,

respectively. The critical operational line resulting from the experimental data is also

indicated in Fig. 8. Since the generator and evaporator conditions were kept constant

during these experiments, this line can be considered as the optimal operation line as a

function of the condenser pressure. For instance, for a condenser pressure of 3.2 bar

(Tc= 21.9 °C) (vertical solid line), operating the ejector with a SP of 5 mm, resulted in a

COP of 0.58 (horizontal dotted line). Moving SP to 4.5 mm, the ejector operated with a

COP of 0.68 (horizontal solid line), which represents a 16% performance improvement.

By moving SP further to 4 mm, the measured COP was 0.65 (horizontal dashed line),

which was actually 7% smaller than the COP obtained with SP=4.50 mm. Therefore,

this latter value of SP can be considered as optimal, allowing the ejector to operate near

critical condition. With an increase in the condenser pressure, e.g. to 3.4 bar (Tc= 23.9

°C) (vertical dashed line) with 4.50 mm SP, the ejector works under single choking

regime and COP drops to approximately 0.5 (horizontal double dotted line). However, if

the spindle is opened to 5.00 mm, the ejector continues working in double choking

regime and the COP is higher (approximately 0.58).

The evolution of the evaporator cooling capacity, COP and λ with spindle position, for

the cases with double choked flow inside the ejector is presented in Fig. 9. One may

Page 18: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

17

note that both performance indicators decreased with SP between 3.75 and 5.25 mm.

This tendency can be explained by the fact that during the experiments, secondary flow

rate remained essentially constant, while the primary flow rate increased, leading to a

constant decrease of the performance indicators (see Fig. 7). This phenomenon is also

demonstrated by the approximately constant cooling capacity, as shown in Fig. 9. For

spindle positions between 5.75-6.25 mm, the performance parameters remained almost

constant, since the primary mass flow rate became independent of the SP, as also shown

in Fig. 7. The small variation on the cooling capacity (relative standard deviation bellow

3%) can be associated to the repeatability of the experiment runs, since not all

experimental conditions could be fully controlled (e.g. room temperature).

Based on Fig. 9, one may conclude that for optimal operation, the optimal SP is 3.75

mm. However, closing the spindle, the critical back pressure drops as indicated by Fig.

8. These two characteristics allow the optimization of the VGE control (SP), and the

results are shown in Fig. 10, where COP, pc and SP are depicted in the same diagram.

The dotted curves in the figure indicate a critical operating line for COP and pc,cr. This

analysis allows the identification of optimal SP control, as well as the assessment of the

benefit of applying a VGE instead of a fixed geometry ejector. Fig. 10 shows that pc,cr

varied from 2.8 to 3.8 bar (Tc from 17.4 to 27.8 °C) depending on the spindle position.

The critical back pressure of 3.8 bar (Tc= 27.8 °C) was obtained with an SP of 5.75 mm

or higher. The corresponding cooling cycle COP was approximately 0.48. This value of

COP also corresponds to the performance of a fixed geometry ejector working in double

choking regime, since in this case the spindle has no influence on the primary mass flow

rate and thus on ejector operation. Condenser pressure typically depends on the climatic

conditions and it varies with time. In a situation when the ambient temperature

Page 19: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

18

decreases with time (end of the day), condenser pressure also reduces. For instance,

considering a condenser pressure of about 3.65 bar (about 26 °C condenser temperature)

(solid arrows), the spindle position that resulted in optimal operation conditions was

5.25 mm, ensuring critical operation with a COP of 0.5. This represents an improvement

of about 6.4%, comparing to the fixed geometry ejector under the same generator and

evaporator conditions. Likewise, if the condenser pressure decreased about 0.65 bar

(condenser pressure of 3 bar, about 20 °C condenser temperature) (dashed arrows), the

optimal operation condition corresponding SP was 4.00 mm, and this corresponds to a

COP improvement of about 70%. The benefits of a VGE with R600a working fluid

have already been demonstrated by Varga et al. (2013a), using CFD simulations.

However, these are the first experimental results that empirically prove the benefit of a

VGE over a fixed geometry ejector.

The choice of the optimal spindle position can be perhaps better understood through the

experimental data presented in Fig. 11. The figure shows COP as a function of the

spindle position, for 3 sets of condenser pressures. For each set, it is possible to select

the optimal SP resulting in the highest COP. For instance, for a condenser pressure of

3.48 bar (Tc= 24.7 °C), if the SP is 5.00 mm, COP is higher than with the ejector

operating with a SP position above or below that value, and the ejector runs under

critical condition. The figure also shows the same tendency for 3.22 bar (Tc= 22.1 °C)

and 3.76 bar (Tc= 27.5 °C) condenser pressures. In general, the higher the condenser

pressure, the more open the spindle should be for optimal operation.

Page 20: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

19

An attempt was made to compare the present performance results to previously

published data using fixed geometry ejectors and R600a as working fluid. A direct

comparison is however difficult, since most published data with R600a rely on

simulation studies. For example, Pridasawas and Lundqvist (2007) presented simulation

results. In their work, the entrainment ratio, as function of the condenser and generator

(70 to 120°C) temperatures, for an evaporator temperature of 15 °C, was studied. For a

Tg= 80°C, λ was about 0.32. Since the present experimental results were obtained for a

considerably lower evaporator temperature of 9 °C and somewhat higher generator

temperature (83ºC), it could be expected that the entrainment ratio would be lower than

0.32. In the present work λ was found to be always above 0.5 (see Fig. 9), for all studied

spindle positions. As mentioned before, Butrymowicz et al. (2013) carried out

experimental analysis with an R600a ejector which, according to the authors’

knowledge, are the only experimental data with isobutane available in the literature until

this date. The ejector performance indicators were presented for a single generator and

evaporator temperature, 63.5ºC and 7ºC, respectively. Considerably lower values were

reported (λ= 0.19 and COP= 0.15) which suggests that these preliminary results can be

considered rather promising.

6 Conclusions

In the present paper, the experimental performance results with a small (1.6 kW cooling

capacity) variable geometry ejector using isobutene (R600a) were presented. The work

aimed to characterize the performance of the VGE prototype, with active adjustment of

the primary nozzle geometry, for fixed generator and evaporator conditions, while

changing condenser pressure.

Page 21: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

20

Under constant upstream and downstream conditions, changing the spindle position

(SP) resulted in a variation of about 80% in the primary flow rate, without significantly

affecting the stream pressure. Within the range of condenser pressures considered, COP

values ranged between 0.45 and 0.88, which can be considered as excellent, especially

for the generator and evaporator temperatures applied.

The benefits of using a variable geometry ejector, compared to a fixed geometry design,

were also demonstrated. It was found that the larger the difference between the actual

and design condenser pressure, the larger the benefits of using the VGE. The

improvement in COP was as high as 85%. The existence of an optimal SP, dependent

on operating conditions, was also experimentally demonstrated for the first time.

The present work should be considered as preliminary, since it only covers a single

generator and evaporator temperature condition. In order to develop an adequate

algorithm that allows for the optimal control of the SP and also NXP, the presented

experimental work will be extended to cover a range of operational conditions

(generator, evaporator and condenser temperatures) that can be expected in a solar

driven air-conditioning system. This way, a complete optimal operation map can be

built. Future work will allow the full characterisation of the VGE cooling cycle, with

the objective to develop and implement an adequate control strategy depending on

operating conditions.

Page 22: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

21

Acknowledgments

The present work was developed within the framework of the “Investigation into an

Improved Ejector for Variable Operating Conditions” research project. The authors

wish to acknowledge the financial support of “Fundação para a Ciência e a Tecnologia

(FCT)”, through contract PTDC/EME-MFE/113007/2009.

The authors wish to acknowledge Armacell for supplying thermal insulations used in

the test rig. The authors would also like to express their gratitude to BaxiRoca for

providing the equipment used to charge the ejector cycle.

References

Allouche, Y., Bouden, C., Varga, S., 2014. A CFD analysis of the flow structure inside

a steam ejector to identify the suitable experimental operating conditions for a solar-

driven refrigeration system. International Journal of Refrigeration 39, 186-195.

Bartosiewicz, Y., Aidoun, Z., Mercadier, Y., 2006. Numerical assessment of ejector

operation for refrigeration applications based on CFD. Applied Thermal Engineering

26, 604-612.

Bouhanguel, A., Desevaux, P., Gavignet, E., 2011. Flow visualization in supersonic

ejectors using laser tomography techniques. International Journal of Refrigeration 34,

1633-1640.

Butrymowicz, D., Smierciew, K., Gagan, J., Karwacki, J., Bergander, M., 2012.

Numerical And Experimental Investigation Of Solar Ejection Refrigeration Cycle

Page 23: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

22

Utilizing Natural Refrigerants, in: Franković, B., Dalenback, J.-O. (Eds.), Eurosun2012.

International Solar Energy Society, Opatija, Croatia.

Butrymowicz, D., Śmierciew, K., Karwacki, J., Gagan, J., 2013. Experimental

investigations of low-temperature driven ejection refrigeration cycle operating with

isobutane. International Journal of Refrigeration.

Chen, X., Omer, S., Worall, M., Riffat, S., 2013. Recent developments in ejector

refrigeration technologies. Renewable and Sustainable Energy Reviews 19, 629-651.

Chunnanond, K., Aphornratana, S., 2004a. Ejectors: applications in refrigeration

technology. Renewable and Sustainable Energy Reviews 8, 129-155.

Chen, J., Havtun. H., Palm, B., 2014. Investigation of ejectors in refrigeration system:

Optimum performance evaluation and ejector area ratios perspectives. Applied Thermal

Engineering 64, 182-191.

Chunnanond, K., Aphornratana, S., 2004b. An experimental investigation of a steam

ejector refrigerator: the analysis of the pressure profile along the ejector. Applied

Thermal Engineering 24, 311-322.

Cizungu, K., Mani, A., Groll, M., 2001. Performance comparison of vapour jet

refrigeration system with environment friendly working fluids. Applied Thermal

Engineering 21, 585-598.

Dennis, M., Garzoli, K., 2011. Use of variable geometry ejector with cold store to

achieve high solar fraction for solar cooling. International Journal of Refrigeration 34,

1626-1632.

Page 24: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

23

Elbel, S., Hrnjak, P., 2008. Experimental validation of a prototype ejector designed to

reduce throttling losses encountered in transcritical R744 system operation.

International Journal of Refrigeration 31, 411-422.

Hemidi, A., Henry, F., Leclaire, S., Seynhaeve, J.-M., Bartosiewicz, Y., 2009. CFD

analysis of a supersonic air ejector. Part II: Relation between global operation and local

flow features. Applied Thermal Engineering 29, 2990-2998.

Huang, B.J., Chang, J.M., Wang, C.P., Petrenko, V.A., 1999. A 1-D analysis of ejector

performance. International Journal of Refrigeration 22, 354-364.

Kim, H.D., Rajesh, G., Setoguchi, T., Matsuo, S., 2006. Optimization study of a Coanda

ejector. Journal of Thermal Science 15, 331-336.

Ma, X., Zhang, W., Omer, S.A., Riffat, S.B., 2010. Experimental investigation of a

novel steam ejector refrigerator suitable for solar energy applications. Applied Thermal

Engineering 30, 1320-1325.

Pridasawas, W., Lundqvist, P., 2007. A year-round dynamic simulation of a solar-

driven ejector refrigeration system with iso-butane as a refrigerant. International Journal

of Refrigeration 30, 840-850.

Roman, R., Hernandez, J.I., 2011. Performance of ejector cooling systems using low

ecological impact refrigerants. International Journal of Refrigeration 34, 1707-1716.

Selvaraju, A., Mani, A., 2006. Experimental investigation on R134a vapour ejector

refrigeration system. International Journal of Refrigeration 29, 1160-1166.

Sun, D.-W., 1996. Variable geometry ejectors and their applications in ejector

refrigeration systems. Energy 21, 919-929.

Page 25: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

24

Sun, D.-W., 1999. Comparative study of the performance of an ejector refrigeration

cycle operating with various refrigerants. Energy Conversion and Management 40, 873-

884.

Varga, S., Lebre, P.M.S., Oliveira, A.C., 2013a. CFD study of a variable area ratio

ejector using R600a and R152a refrigerants. International Journal of Refrigeration 36,

157-165.

Varga, S., Lebre, P.S., Oliveira, A.C., 2013b. Readdressing working fluid selection with

a view to designing a variable geometry ejector. International Journal of Low-Carbon

Technologies.

Varga, S., Oliveira, A.C., Diaconu, B., 2009a. Analysis of a solar-assisted ejector

cooling system for air conditioning. International Journal of Low-Carbon Technologies

4, 2-8.

Varga, S., Oliveira, A.C., Diaconu, B., 2009b. Influence of geometrical factors on steam

ejector performance – A numerical assessment. International Journal of Refrigeration

32, 1694-1701.

Varga, S., Oliveira, A.C., Ma, X., Omer, S.A., Zhang, W., Riffat, S.B., 2011.

Experimental and numerical analysis of a variable area ratio steam ejector. International

Journal of Refrigeration 34, 1668-1675.

Yapıcı, R., Ersoy, H.K., Aktoprakoğlu, A., Halkacı, H.S., Yiğit, O., 2008. Experimental

determination of the optimum performance of ejector refrigeration system depending on

ejector area ratio. International Journal of Refrigeration 31, 1183-1189.

Page 26: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

Fig. 1 – Schematic drawing of the experimental test rig.

Page 27: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

Fig. 2 – A photograph of the experimental apparatus (1 - ejector; 2 - generator, 3 - evaporator, 4 - condenser, 5 - circulating pump, 6 - expansion valve, 7 - vapor separator, 8 - SP and NXP stepper motors).

Page 28: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

Fig. 3 – Schematic view of a typical ejector.

Page 29: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

Fig. 4 – Ejector operation regimes for constant Tg and Te.

Page 30: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

Fig. 5 – Detailed dimensions of the ejector internal geometry.

Page 31: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

Fig. 6 – COP as function of condenser pressure for SP=5.00 mm, with Tg= 83 °C and Te= 9 °C. Condenser temperatures range from 17 ºC (2.8 bar) to 30 ºC (4 bar).

Page 32: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

Fig. 7 – Influence of spindle position on the primary and secondary flow rates for Tg= 83 °C.

Page 33: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

Fig. 8 – COP as function of condenser pressure for different spindle positions, with Tg= 83 °C and Te= 9 °C. Condenser temperatures range from 15 ºC (2.6 bar) to 31 ºC (4.2 bar).

Page 34: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

Fig. 9 – Performance parameters and evaporator cooling capacity at different spindle positions, with Tg= 83 °C and Te= 9 °C.

Page 35: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

Fig. 10 – Influence of the spindle position on COP and critical back pressure, with Tg= 83 °C and Te= 9 °C. Condenser temperatures range from 12 ºC (2.4 bar) to 31 ºC (4.2 bar).

Page 36: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

Fig. 11 – COP as a function of the spindle position for three different condenser pressures (temperatures), with Tg= 83 °C and Te= 9 °C.

Page 37: Experimental results with a variable geometry ejector

MANUSCRIP

T

ACCEPTED

ACCEPTED MANUSCRIPT

• An experimental study with a variable geometry ejector with isobutane is

presented

• The influence of the spindle position on the ejector performance is assessed

• The critical condenser pressures are determined

• The existence of an optimal spindle position was experimentally verified

• The performance improvements compared to a fixed geometry ejector are

demonstrated